Overview

Powerful controller for extremely fast signal processing

Expandable by:
- 1 signal board (SB), battery board (BB) or communication board (CB)
- 8 signal modules (SM)
- Max. 3 communication modules (CM)

 

Design

The compact CPU 1217C has:

- Integrated 24 V encoder/load current supply: 
  For direct connection of sensors and encoders. With a 400 mA output current, it can also be used as load power supply.

- 14 integrated digital inputs, of which:
  + 10 integrated digital 24 V DC inputs (current sinking/current sourcing (IEC type 1 current sinking)).
  + 4 integrated digital 1.5 V DC differential inputs.

- 10 integrated digital outputs, of which:
  + 6 integrated digital 24 V DC outputs.
  + 4 integrated digital 1.5 V DC differential outputs.

- 2 integrated analog inputs 0 ... 10 V.
- 2 integrated analog outputs 0 ... 20 mA.
- 4 pulse outputs (PTO) with a frequency of up to 1 MHz.
- Pulse-width modulated outputs (PWM) with a frequency of up to 100 kHz.
- 2 integrated Ethernet interfaces (TCP/IP native, ISO-on-TCP).
- 6 fast counters (max. 1 MHz), with parameterizable enable and reset inputs, can be used simultaneously as up and down counters with - 2 separate inputs or for connecting incremental encoders.
- Expansion by additional communication interfaces, e.g. RS485, RS232, PROFIBUS.
- Expansion by analog or digital signals directly on the CPU via signal board (with retention of CPU mounting dimensions).
- Expansion by a wide range of analog and digital input and output signals via signal modules.
- Optional memory expansion (SIMATIC Memory Card).
- Motion Control in accordance with PLCopen for simple movements.
- PID controller with auto-tuning functionality.
- Integral real-time clock.
- Password protection.
- Interrupt inputs: 
  For extremely fast response to rising or falling edges of process signals.
- Time interrupts.
- Interrupt inputs.
- Library functionality.
- Online/Offline diagnostics.
- Removable terminals on all modules.
- Simulator (optional): 
  For simulating the integrated inputs and for testing the user program.

 

Function

- Comprehensive instruction set: 
  A wide range of operations facilitates programming:
  + Basic operations such as binary logic operations, result allocation, save, count, create times, load, transfer, compare, shift, rotate, create complement, call subprogram (with local variables)
  + Integral communication commands (e.g. USS protocol, Modbus RTU, S7 communication "T-Send/T-Receive" or Freeport)
  + user-friendly functions such as pulse-width modulation, pulse sequence function, arithmetic functions, floating point arithmetic, PID closed-loop control, jump functions, loop functions and code conversions,
  + Mathematical functions, e.g. SIN, COS, TAN, LN, EXP


- Counting: 
  User-friendly counting functions in conjunction with the integrated counters and special commands for high-speed counters open up new application areas for the user.


- Interrupt processing: 
  + Edge-triggered interrupts (activated by rising or falling edges of process signals on interrupt inputs) support a rapid response to process events.
  + Time-triggered interrupts.
  + Counter interrupts can be triggered when a setpoint is reached or when the direction of counting changes.
  + Communication interrupts allow the rapid and easy exchange of information with peripheral devices such as printers or bar code readers.


- Password protection
- Test and diagnostics functions: 
  Easy-to-use functions support testing and diagnostics, e.g. online/offline diagnostics.
- "Forcing" of inputs and outputs during testing and diagnostics: 
  Inputs and outputs can be set independently of cycle and thus permanently, for example, to test the user program.
- Motion Control in accordance with PLCopen for simple movements.
- Library functionality

 

Programming

The STEP 7 programming package permits complete programming of all S7-1200 controllers and the associated I/O.

 

Technical specifications

Article number

6ES7217-1AG40-0XB0

 

CPU 1217C, DC/DC/DC, 14DI/10DQ/2AI/2AQ

General information

 

Product type designation

CPU 1217C DC/DC/DC

Firmware version

V4.2

Engineering with

 

  • ● Programming package

STEP 7 V14 or higher

Supply voltage

 

Rated value (DC)

 

  • ● 24 V DC

Yes

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

Reverse polarity protection

Yes

Load voltage L+

 

  • ● Rated value (DC)

24 V

  • ● permissible range, lower limit (DC)

20.4 V

  • ● permissible range, upper limit (DC)

28.8 V

Input current

 

Current consumption (rated value)

600 mA; CPU only

Current consumption, max.

1 600 mA; CPU with all expansion modules

Inrush current, max.

12 A; at 28.8 V DC

I²t

0.5 A²·s

Output current

 

for backplane bus (5 V DC), max.

1 600 mA; Max. 5 V DC for SM and CM

Encoder supply

 

24 V encoder supply

 

  • ● 24 V

L+ minus 4 V DC min.

Power loss

 

Power loss, typ.

12 W

Memory

 

Work memory

 

  • ● integrated

150 kbyte

  • ● expandable

No

Load memory

 

  • ● integrated

4 Mbyte

  • ● Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

Backup

 

  • ● present

Yes

  • ● maintenance-free

Yes

  • ● without battery

Yes

CPU processing times

 

for bit operations, typ.

0.08 µs; / instruction

for word operations, typ.

1.7 µs; / instruction

for floating point arithmetic, typ.

2.3 µs; / Operation

CPU-blocks

 

Number of blocks (total)

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

 

  • ● Number, max.

Limited only by RAM for code

Data areas and their retentivity

 

Retentive data area (incl. timers, counters, flags), max.

10 kbyte

Flag

 

  • ● Number, max.

8 kbyte; Size of bit memory address area

Local data

 

  • ● per priority class, max.

16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Process image

 

  • ● Inputs, adjustable

1 kbyte

  • ● Outputs, adjustable

1 kbyte

Hardware configuration

 

Number of modules per system, max.

3 comm. modules, 1 signal board, 8 signal modules

Time of day

 

Clock

 

  • ● Hardware clock (real-time)

Yes

  • ● Backup time

480 h; Typical

  • ● Deviation per day, max.

±60 s/month at 25 °C

Digital inputs

 

Number of digital inputs

14; Integrated

  • ● of which inputs usable for technological functions

6; HSC (High Speed Counting)

Source/sink input

Yes

Number of simultaneously controllable inputs

 

all mounting positions

 

  • — up to 40 °C, max.

14

Input voltage

 

  • ● Rated value (DC)

24 V

  • ● for signal "0"

5 V DC at 1 mA

  • ● for signal "1"

15 V DC at 2.5 mA

Input delay (for rated value of input voltage)

 

for standard inputs

 

  • — parameterizable

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

  • — at "0" to "1", min.

0.2 ms

  • — at "0" to "1", max.

12.8 ms

for interrupt inputs

 

  • — parameterizable

Yes

for technological functions

 

  • — parameterizable

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Cable length

 

  • ● shielded, max.

500 m; 50 m for technological functions

  • ● unshielded, max.

300 m; For technological functions: No

Digital outputs

 

Number of digital outputs

10

  • ● of which high-speed outputs

4; 100 kHz Pulse Train Output

Limitation of inductive shutdown voltage to

L+ (-48 V)

Switching capacity of the outputs

 

  • ● with resistive load, max.

0.5 A

  • ● on lamp load, max.

5 W

Output voltage

 

  • ● for signal "0", max.

0.1 V; with 10 kOhm load

  • ● for signal "1", min.

20 V

Output current

 

  • ● for signal "1" rated value

0.5 A

  • ● for signal "0" residual current, max.

0.1 mA

Output delay with resistive load

 

  • ● "0" to "1", max.

1 µs

  • ● "1" to "0", max.

5 µs

Switching frequency

 

  • ● of the pulse outputs, with resistive load, max.

100 kHz

Cable length

 

  • ● shielded, max.

500 m

  • ● unshielded, max.

150 m

Analog inputs

 

Number of analog inputs

2

Input ranges

 

  • ● Voltage

Yes

Input ranges (rated values), voltages

 

  • ● 0 to +10 V

Yes

  • ● Input resistance (0 to 10 V)

≥100k ohms

Cable length

 

  • ● shielded, max.

100 m; twisted and shielded

Analog outputs

 

Number of analog outputs

2

Output ranges, current

 

  • ● 0 to 20 mA

Yes

Analog value generation for the inputs

 

Integration and conversion time/resolution per channel

 

  • ● Resolution with overrange (bit including sign), max.

10 bit

  • ● Integration time, parameterizable

Yes

  • ● Conversion time (per channel)

625 µs

Analog value generation for the outputs

 

Integration and conversion time/resolution per channel

 

  • ● Resolution with overrange (bit including sign), max.

10 bit

Encoder

 

Connectable encoders

 

  • ● 2-wire sensor

Yes

1. Interface

 

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

automatic detection of transmission rate

Yes

Autonegotiation

Yes

Autocrossing

Yes

Interface types

 

  • ● Number of ports

2

  • ● integrated switch

Yes

Protocols

 

  • ● PROFINET IO Controller

Yes

  • ● PROFINET IO Device

Yes

  • ● SIMATIC communication

Yes

  • ● Open IE communication

Yes

  • ● Web server

Yes

  • ● Media redundancy

Yes; as MRP client

PROFINET IO Controller

 

  • ● Transmission rate, max.

100 Mbit/s

Services

 

  • — PG/OP communication

Yes

  • — S7 routing

Yes

  • — Isochronous mode

No

  • — Open IE communication

Yes

  • — IRT

No

  • — MRP

Yes; as MRP client

  • — MRPD

No

  • — PROFIenergy

No

  • — Prioritized startup

Yes

  • — Number of IO devices with prioritized startup, max.

16

  • — Number of connectable IO Devices, max.

16

  • — Number of connectable IO Devices for RT, max.

16

  • — of which in line, max.

16

  • — Activation/deactivation of IO Devices

Yes

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • — Updating time

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

PROFINET IO Device

 

Services

 

  • — PG/OP communication

Yes

  • — S7 routing

Yes

  • — Isochronous mode

No

  • — Open IE communication

Yes

  • — IRT

No

  • — MRP

Yes; as MRP client

  • — MRPD

No

  • — PROFIenergy

Yes

  • — Shared device

Yes

  • — Number of IO Controllers with shared device, max.

2

Protocols

 

Supports protocol for PROFINET IO

Yes

PROFIBUS

Yes; CM 1243-5 required

AS-Interface

Yes; CM 1243-2 required

Protocols (Ethernet)

 

  • ● TCP/IP

Yes

  • ● DHCP

No

  • ● SNMP

Yes

  • ● DCP

Yes

  • ● LLDP

Yes

Open IE communication

 

  • ● TCP/IP

Yes

  • — Data length, max.

8 kbyte

  • ● ISO-on-TCP (RFC1006)

Yes

  • — Data length, max.

8 kbyte

  • ● UDP

Yes

  • — Data length, max.

1 472 byte

Web server

 

  • ● supported

Yes

  • ● User-defined websites

Yes

Further protocols

 

  • ● MODBUS

Yes

Communication functions

 

S7 communication

 

  • ● supported

Yes

  • ● as server

Yes

  • ● as client

Yes

  • ● User data per job, max.

See online help (S7 communication, user data size)

Number of connections

 

  • ● overall

16; dynamically

Test commissioning functions

 

Status/control

 

  • ● Status/control variable

Yes

  • ● Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Forcing

 

  • ● Forcing

Yes

Diagnostic buffer

 

  • ● present

Yes

Traces

 

  • ● Number of configurable Traces

2

  • ● Memory size per trace, max.

512 kbyte

Interrupts/diagnostics/status information

 

Diagnostics indication LED

 

  • ● RUN/STOP LED

Yes

  • ● ERROR LED

Yes

  • ● MAINT LED

Yes

Integrated Functions

 

Number of counters

6

Counting frequency (counter) max.

1 MHz

Frequency measurement

Yes

controlled positioning

Yes

Number of position-controlled positioning axes, max.

8

Number of positioning axes via pulse-direction interface

4; With integrated outputs

PID controller

Yes

Number of alarm inputs

4

Number of pulse outputs

4

Limit frequency (pulse)

1 MHz

Potential separation

 

Potential separation digital inputs

 

  • ● Potential separation digital inputs

No

  • ● between the channels, in groups of

1

Potential separation digital outputs

 

  • ● Potential separation digital outputs

Yes

  • ● between the channels

No

  • ● between the channels, in groups of

1

EMC

 

Interference immunity against discharge of static electricity

 

  • ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes

  • — Test voltage at air discharge

8 kV

  • — Test voltage at contact discharge

6 kV

Interference immunity to cable-borne interference

 

  • ● Interference immunity on supply lines acc. to IEC 61000-4-4

Yes

  • ● Interference immunity on signal cables acc. to IEC 61000-4-4

Yes

Interference immunity against voltage surge

 

  • ● on the supply lines acc. to IEC 61000-4-5

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields

 

  • ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6

Yes

Emission of radio interference acc. to EN 55 011

 

  • ● Limit class A, for use in industrial areas

Yes; Group 1

  • ● Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Degree and class of protection

 

Degree of protection acc. to EN 60529

 

  • ● IP20

Yes

Standards, approvals, certificates

 

CE mark

Yes

UL approval

Yes

cULus

Yes

FM approval

Yes

RCM (formerly C-TICK)

Yes

KC approval

Yes

Marine approval

Yes

Ambient conditions

 

Free fall

 

  • ● Fall height, max.

0.3 m; five times, in product package

Ambient temperature during operation

 

  • ● min.

-20 °C

  • ● max.

60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical

  • ● horizontal installation, min.

-20 °C

  • ● horizontal installation, max.

60 °C

  • ● vertical installation, min.

-20 °C

  • ● vertical installation, max.

50 °C

Ambient temperature during storage/transportation

 

  • ● min.

-40 °C

  • ● max.

70 °C

Air pressure acc. to IEC 60068-2-13

 

  • ● Operation, min.

795 hPa

  • ● Operation, max.

1 080 hPa

  • ● Storage/transport, min.

660 hPa

  • ● Storage/transport, max.

1 080 hPa

Altitude during operation relating to sea level

 

  • ● Installation altitude, min.

-1 000 m

  • ● Installation altitude, max.

2 000 m

Relative humidity

 

  • ● Operation, max.

95 %; no condensation

Vibrations

 

  • ● Vibration resistance during operation acc. to IEC 60068-2-6

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

  • ● Operation, tested according to IEC 60068-2-6

Yes

Shock testing

 

  • ● tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

 

  • ● SO2 at RH < 60% without condensation

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Programming

 

Programming language

 

  • — LAD

Yes

  • — FBD

Yes

  • — SCL

Yes

Know-how protection

 

  • ● User program protection/password protection

Yes

  • ● Copy protection

Yes

  • ● Block protection

Yes

Access protection

 

  • ● Protection level: Write protection

Yes

  • ● Protection level: Read/write protection

Yes

  • ● Protection level: Complete protection

Yes

Cycle time monitoring

 

  • ● adjustable

Yes

Dimensions

 

Width

150 mm

Height

100 mm

Depth

75 mm

Weights

 

Weight, approx.

530 g

 