Width | 68 mm |
Height | 130 mm |
Depth | 160 mm |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Nominal input voltage range | 100 V AC ... 240 V AC |
110 V DC ... 250 V DC | |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
99 V DC ... 275 V DC | |
Dielectric strength maximum | ≤ 300 V AC 15 s |
AC frequency range | 50 Hz ... 60 Hz ±10 % |
Discharge current to PE | < 3.5 mA |
Current consumption | 5.6 A (100 V AC) |
5.4 A (120 V AC) | |
2.6 A (230 V AC) | |
2.4 A (240 V AC) | |
Nominal power consumption | 34 W |
Inrush surge current | 20 A (at 25 °C) |
Mains buffering | > 10 ms (120 V AC) |
> 15 ms (230 V AC) | |
Input fuse | 10 A (internal (device protection)) |
Choice of suitable circuit breakers | 10 A ... 16 A (Characteristics B, C, D, K) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Nominal output voltage | 48 V DC ±1 % |
Setting range of the output voltage (USet) | 36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A |
Dynamic Boost (IDyn.Boost) | 15 A (5 s) |
Derating | > 60 °C ... 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | ≤ 60 V DC |
Circuit breaker against surge voltage at output by invasive foreign matter | ≤ 60 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 50 mVPP (with nominal values) |
Output power | 480 W |
Typical response time | < 1 s |
Peak switching voltages nominal load | < 1000 mVPP |
Maximum power dissipation in no-load condition | < 5.7 W (230 V) |
Power loss nominal load max. | < 44 W |
Net weight | 1.4 kg |
Efficiency | > 93 % (for 230 V AC and nominal values) |
Insulation voltage input/output | 3 kV AC |
1.5 kV AC | |
Protection class | I (in closed control cabinet) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1800000 h (25 °C) |
> 800000 h (40 °C) | |
> 480000 h (60 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | Can be aligned: Horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 10 mm |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 10 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 6 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 8 |
Stripping length | 15 mm |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 1.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 |
Stripping length | 8 mm |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Noise immunity | EN 61000-6-2:2005 |
Standards/regulations | EN 61000-4-2 |
Contact discharge | 4 kV (Test Level 2) |
Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1.4 GHz ... 2 GHz |
Test field strength | 3 V/m (Test Level 2) |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Standards/regulations | EN 61000-6-3 |
EN 61000-4-6 | |
Frequency range | 0.15 MHz ... 80 MHz |
Voltage | 10 V (Test Level 3) |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
UL approvals | UL Listed UL 508 |
UL/C-UL Recognized UL 60950-1 | |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
15 Hz ... 150 Hz, 4g, 90 min. | |
Rail applications | EN 50121-4 |
Assembly instructions | Can be aligned: Horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
eCl@ss 4.0 | 27040702 |
eCl@ss 4.1 | 27040702 |
eCl@ss 5.0 | 27049002 |
eCl@ss 5.1 | 27049002 |
eCl@ss 6.0 | 27049002 |
eCl@ss 7.0 | 27049002 |
eCl@ss 8.0 | 27049002 |
eCl@ss 9.0 | 27040701 |
ETIM 4.0 | EC002540 |
ETIM 5.0 | EC002540 |
ETIM 6.0 | EC002540 |
UNSPSC 13.2 | 39121004 |