Height | 89.8 mm |
Width | 53.4 mm |
Depth | 65.7 mm |
Horizontal pitch | 3 Div. |
Degree of protection | IP20 (only when all terminal points are used) |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 3000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5-500 Hz/2.5 h/XYZ) |
IEC test classification | PV II |
PV T2 | |
EN type | T2 |
IEC power supply system | DC |
SPD failure behavior | OCM (Open-circuit mode) |
Connection configuration | Y configuration |
Installation location | Inside |
Accessibility | Accessible |
Installation location of the disconnect device | Internal |
Mode of protection | (L+) - (L-) |
(L+) - PE | |
(L-) - PE | |
Mounting type | DIN rail: 35 mm |
Color | jet black RAL 9005 |
Housing material | PA 6.6-FR |
PBT-FR | |
Degree of pollution | 2 |
Distance between live and grounded parts | 8 mm |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Surge protection fault message | optical |
Chú ý | Thiết bị này được thiết kế để lắp đặt bằng chứng cảm ứng trong vỏ hộp. Đảm bảo rằng có khoảng cách ít nhất 8 mm giữa các bộ phận hoạt động và nối đất trong khu vực kết nối. |
Maximum continuous operating voltage UCPV | 1500 V DC |
Open circuit voltage UOCSTC | ≤ 1250 V DC |
Short-circuit current rating ISCPV | 2000 A |
Continuous operating current ICPV | < 350 µA |
Rated load current IL | 80 A |
Residual current IPE | ≤ 350 µA DC |
≤ 600 µA AC | |
Standby power consumption PC | ≤ 250 mVA |
Nominal discharge current (8/20) µs | 15 kA |
Maximum discharge current Imax (8/20) µs | 30 kA |
Total discharge current Itotal (8/20) µs | 30 kA |
Voltage protection level Up | ≤ 5 kV |
Residual voltage Ures | ≤ 5 kV (at In) |
≤ 6 kV (at 30 kA) | |
Response time tA | ≤ 25 ns |
Connection method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
4.5 Nm (25 mm² ... 35 mm²) | |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section solid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
SPD Type | 1CA |
Maximum continuous operating voltage MCOV | 1500 V DC |
Nominal voltage | 1500 V DC |
Mode of protection | (DC+) - (DC-) |
(DC+) - G | |
(DC-) - G | |
Power distribution system | DC PV |
Voltage protection rating VPR | 4 kV |
Nominal discharge current In | 10 kA |
Short-circuit current rating (SCCR) | 50 kA |
Conductor cross section AWG | 10 ... 2 |
Tightening torque | 30 lbf-in. |
Standards/regulations | EN 50539-11 2013 |
eCl@ss 6.0 | 27130800 |
eCl@ss 7.0 | 27130805 |
eCl@ss 8.0 | 27130805 |
eCl@ss 9.0 | 27130805 |
ETIM 5.0 | EC000941 |
ETIM 6.0 | EC000941 |