-Phoenix-Contact-Germany-ToanMinhTechnologies-phan-phoi(1).jpg)
![]() |
|
Height |
90 mm |
|
Width |
71 mm |
|
Depth |
58 mm |
|
Horizontal pitch |
4 Div. |
|
Degree of protection |
IP20 (only when all terminal points are used) |
|
Ambient temperature (operation) |
-40 °C ... 80 °C |
|
Ambient temperature (storage/transport) |
-40 °C ... 80 °C |
|
Altitude |
≤ 2000 m (amsl (above mean sea level)) |
|
Permissible humidity (operation) |
5 % ... 95 % |
|
Shock (operation) |
25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z) |
|
Vibration (operation) |
5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
|
IEC test classification |
II |
|
|
T2 |
|
EN type |
T2 |
|
IEC power supply system |
TN-S |
|
|
TT |
|
Mode of protection |
L-N |
|
|
L-PE |
|
|
N-PE |
|
Mounting type |
DIN rail: 35 mm |
|
Color |
jet black RAL 9005 |
|
Housing material |
PA 6.6 |
|
|
PBT |
|
Degree of pollution |
2 |
|
Flammability rating according to UL 94 |
V-0 |
|
Type |
DIN rail module, two-section, divisible |
|
Number of positions |
4 |
|
Surge protection fault message |
optical |
|
Nominal voltage UN |
240/415 V AC (TN-S) |
|
|
240/415 V AC (TT) |
|
Nominal frequency fN |
50 Hz (60 Hz) |
|
Maximum continuous operating voltage UC (L-N) |
275 V AC |
|
Maximum continuous operating voltage UC (L-PE) |
275 V AC |
|
Maximum continuous voltage UC (N-PE) |
260 V AC |
|
Rated load current IL |
80 A |
|
Residual current IPE |
≤ 5 µA |
|
Standby power consumption PC |
≤ 360 mVA |
|
Nominal discharge current In (8/20) µs |
20 kA |
|
Maximum discharge current Imax (8/20) µs |
40 kA |
|
Follow current interrupt rating Ifi (N-PE) |
100 A |
|
Short-circuit current rating ISCCR |
25 kA |
|
Voltage protection level Up (L-N) |
≤ 1.35 kV |
|
Voltage protection level Up (L-PE) |
≤ 1.6 kV |
|
Voltage protection level Up (N-PE) |
≤ 1.5 kV |
|
Residual voltage Ures (L-N) |
≤ 1.35 kV (at In) |
|
|
≤ 1.1 kV (at 10 kA) |
|
|
≤ 1 kV (at 5 kA) |
|
|
≤ 0.9 kV (at 3 kA) |
|
Residual voltage Ures (L-PE) |
≤ 1.6 kV (at In) |
|
|
≤ 1.2 kV (at 10 kA) |
|
|
≤ 1 kV (at 5 kA) |
|
|
≤ 0.9 kV (at 3 kA) |
|
Residual voltage Ures (N-PE) |
≤ 0.4 kV (at In) |
|
|
≤ 0.25 kV (at 10 kA) |
|
|
≤ 0.15 kV (at 5 kA) |
|
|
≤ 0.1 kV (at 3 kA) |
|
TOV behavior at UT (L-N) |
335 V AC (5 s / withstand mode) |
|
|
440 V AC (120 min / safe failure mode) |
|
TOV behavior at UT (N-PE) |
1200 V AC (200 ms / withstand mode) |
|
Response time tA (L-N) |
≤ 25 ns |
|
Response time tA (L-PE) |
≤ 100 ns |
|
Response time tA (N-PE) |
≤ 100 ns |
|
Max. backup fuse with branch wiring |
125 A (gG) |
|
Max. backup fuse with V-type through wiring |
80 A (gG) |
|
Connection method |
Screw connection |
|
Screw thread |
M5 |
|
Tightening torque |
3 Nm (1,5 mm² ... 16 mm²) |
|
|
4.5 Nm (25 mm² ... 35 mm²) |
|
Stripping length |
16 mm |
|
Conductor cross section flexible |
1.5 mm² ... 25 mm² |
|
Conductor cross section solid |
1.5 mm² ... 35 mm² |
|
Conductor cross section AWG |
15 ... 2 |
|
SPD Type |
4CA |
|
Maximum continuous operating voltage MCOV (L-L) |
550 V AC |
|
Maximum continuous operating voltage MCOV (L-N) |
275 V AC |
|
Maximum continuous operating voltage MCOV (L-G) |
275 V AC |
|
Maximum continuous operating voltage MCOV (N-G) |
260 V AC |
|
Nom. voltage |
230/400 V AC |
|
Mode of protection |
L-L |
|
|
L-N |
|
|
L-G |
|
|
N-G |
|
Power distribution system |
3Y |
|
Nominal frequency |
50/60 Hz |
|
Measured limiting voltage MLV (L-L) |
2720 V |
|
Measured limiting voltage MLV (L-N) |
1910 V |
|
Measured limiting voltage MLV (L-G) |
2630 V |
|
Measured limiting voltage MLV (N-G) |
1370 V |
|
Nominal discharge current In (L-L) |
20 kA |
|
Nominal discharge current In (L-N) |
20 kA |
|
Nominal discharge current In (L-G) |
20 kA |
|
Nominal discharge current In (N-G) |
20 kA |
|
Conductor cross section AWG |
10 ... 2 |
|
Tightening torque |
30 lbf-in. |
|
Standards/regulations |
IEC 61643-11 2011 |
|
|
EN 61643-11 2012 |
eCl@ss
|
eCl@ss 4.0 |
27140201 |
|
eCl@ss 4.1 |
27130801 |
|
eCl@ss 5.0 |
27130801 |
|
eCl@ss 5.1 |
27130801 |
|
eCl@ss 6.0 |
27130805 |
|
eCl@ss 7.0 |
27130805 |
|
eCl@ss 8.0 |
27130805 |
|
eCl@ss 9.0 |
27130805 |
|
ETIM 2.0 |
EC000941 |
|
ETIM 3.0 |
EC000941 |
|
ETIM 4.0 |
EC000941 |
|
ETIM 5.0 |
EC000941 |
|
ETIM 6.0 |
EC000941 |
|
UNSPSC 6.01 |
30212010 |
|
UNSPSC 7.0901 |
39121610 |
|
UNSPSC 11 |
39121610 |
|
UNSPSC 12.01 |
39121610 |
|
UNSPSC 13.2 |
39121620 |
Thiết bị chống sét lan truyền đường nguồn 2 pha, 4 dây (L1, L2, N, PE) Loại T2Giá tốt nhất xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 2 pha, 3 dây (L1, L2, PEN) Loại T2 -Giá tốt nhất xem...0909186879 Email
Thiết bị chống sét lan truyền quang điện mặt trời Solar PV T2 1000vDC 40kA -Giá tốt nhất xem...0909186879 Email
Thiết bị kết hợp cắt sét và chống sét lan truyền T1+T2 cho điện mặt trời 600vDCGiá tốt nhất xem...0909186879 Email
Chống sét Phoenix Contact VAL-MS 230/3+1 - 2838209 | T2 3P 40kA 25nsGiá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 3 pha, 4 dây (L1, L2, L3, PEN) Loại T1 -Phoenix Contact -FLT-SEC-P-T1-3C-350/25-FM 2905419Giá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền quang điện mặt trời Solar PV T2 600vDC 40kA - DEHN - DG YPV SCI 600 - Part No. 950531Giá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 3 pha, 5 dây (L1, L2, L3, N, PE) loại T2 - Phoenix Contact - VAL-SEC-T2-3S-350-FM 2905340Giá tốt nhất Xem...0909186879 Email
Chống sét Phoenix Contact VAL-MS 230/1+1 - 2804429 | T2 40kA 25ns 1P L1-N-PEGiá tốt nhất Xem...0909186879 Email