Height | 95.2 mm |
Width | 106.8 mm |
Depth | 74.5 mm |
Horizontal pitch | 6 Div. |
Degree of protection | IP20 (only when all terminal points are used) |
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms /3x, X, Y, Z) |
Vibration (operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
IEC test classification | I / II |
T1 / T2 | |
T1 | |
I | |
EN type | T1 / T2 |
T1 | |
IEC power supply system | TN-C |
Mode of protection | L-PEN |
Mounting type | DIN rail: 35 mm |
Color | light grey RAL 7035 |
traffic grey A RAL 7042 | |
Housing material | PA 6.6-FR 20% GF |
PBT-FR | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 3 |
Surge protection fault message | Optical, remote indicator contact |
Nominal voltage UN | 240/415 V AC (TN-C) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Rated load current IL | 125 A (< 55 °C) |
Nominal discharge current In (8/20) µs | 25 kA |
Maximum discharge current Imax (8/20) µs | 50 kA |
Impulse discharge current (10/350) µs, charge | 12.5 As |
Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 25 kA |
Total discharge current Itotal (10/350) µs | 75 kA |
Follow current interrupt rating Ifi | 50 kA |
Short-circuit current rating ISCCR | 50 kA |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 1.5 kV (at In) |
Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
TOV behavior at UT | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / withstand mode) | |
Response time tA | ≤ 100 ns |
Max. backup fuse with branch wiring | 315 A (gG) |
Max. backup fuse with V-type through wiring | 125 A (gG) |
Follow current interrupt rating Ifi | 100 kA (264 V AC) |
Short-circuit current rating ISCCR | 100 kA (264 V AC) |
Switching function | PDT contact |
Operating voltage | 12 V AC ... 250 V AC |
125 V DC (200 mA DC) | |
Operating current | 10 mA AC ... 1 A AC |
1 A DC (30 V DC) | |
Connection method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Connection method | Screw terminal blocks |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 18 mm |
Conductor cross section flexible | 2.5 mm² ... 35 mm² |
Conductor cross section solid | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 13 ... 2 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
SPD Type | 4CA |
Maximum continuous operating voltage MCOV (L-L) | 528 V AC |
Maximum continuous operating voltage MCOV (L-G) | 264 V AC |
Nom. voltage | 240/415 V AC |
Mode of protection | L-L |
L-G | |
Power distribution system | 3D |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-L) | 2450 V |
Measured limiting voltage MLV (L-G) | 1350 V |
Nominal discharge current In (L-L) | 20 kA |
Nominal discharge current In (L-G) | 20 kA |
Operating voltage | 125 V AC |
Operating current | 1 A AC |
Tightening torque | 4 lbf-in. |
Conductor cross section AWG | 30 ... 14 |
Conductor cross section AWG | 12 ... 2 |
Tightening torque | 40 lbf-in. |
Standards/regulations | IEC 61643-11 2011 |
EN 61643-11 2012 |
REACh SVHC | UV -328 25973-55-1 |
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 5.1 | 27130801 |
eCl@ss 6.0 | 27130808 |
eCl@ss 8.0 | 27130802 |
eCl@ss 9.0 | 27130802 |
ETIM 4.0 | EC000381 |
ETIM 5.0 | EC000381 |
ETIM 6.0 | EC000381 |
UNSPSC 13.2 | 39121620 |