range | Acti 9 |
product name | Acti 9 PRD1 Master |
product or component type | Surge arrester with pluggable cartridge |
device short name | PRD1 Master |
device application | Distribution |
poles description | 3P + N |
remote signalling | With |
signal contacts composition | 1 SD (1 C/O) |
surge arrester type | Electrical distribution network |
earthing system | TN-S TT |
surge arrester class type | Type 1 |
surge arrester technology | Spark gap |
[Ue] rated operational voltage | 230 V (+/- 10 %) AC 50 Hz 400 V (+/- 10 %) AC 50 Hz |
nominal discharge current | Common mode : 100 kA N/PE Differential mode : 25 kA L/N |
[Iimp] impulse current | Common mode : 100 kA N/PE 50 A.s Differential mode : 25 kA L/N 12.5 A.s |
[Uc] maximum continuous operating voltage | Common mode : 350 V N/PE Differential mode : 350 V L/N |
[Up] voltage protection level | 1.5 kV type 2 common mode N/PE 1.5 kV type 2 differential mode L/N |
[If] follow current | 50 kA differential mode L/N 0.1 kA common mode N/PE |
disconnector device type | Associated fuse gG 315 A according to standard Associated circuit breaker Compact NSX100F 100 A curve C - Icu 36 kA Associated circuit breaker Compact NSX100N 100 A curve C - Icu 50 kA |
local signalling | Flag color: white/red |
signalling circuit voltage | 1 A/250 V AC 50/60 Hz |
mounting mode | Clip-on |
mounting support | DIN rail |
9 mm pitches | 16 |
height | 90 mm |
width | 142.8 mm |
depth | 70 mm |
product weight | 1.31 kg |
colour | Anthracite grey ( RAL 7016 ) |
material | PBT (polybutylene terephthalate) |
response time | < 100 ns |
connections - terminals | Tunnel type terminal, downside 2.5...35 mm² Tunnel type terminal, upside 2.5...35 mm² |
tightening torque | 4.5 N.m |
standards | EN 61643-11 : 2012 IEC 61643-11 : 2011 |
product certifications | CE |
quality labels | KEMA-KEUR |
IP degree of protection | On front face : IP40 conforming to IEC 60529 Built-in : IP20 conforming to IEC 60529 |
IK degree of protection | IK05 conforming to IEC 62262 |
relative humidity | 5...90 % |
operating altitude | 2000 m |
ambient air temperature for operation | -25...60 °C |
ambient air temperature for storage | -40...80 °C |
RoHS (date code: YYWW) | Compliant - since 0601 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity |
REACh | Reference not containing SVHC above the threshold |
Warranty period | 18 months |