Item | General-purpose Controller 61F-IP |
Controlling materials and operating conditions | For control of ordinary purified water or sewage water |
Supply voltage | 100, 200, 220 VAC; 50/60 Hz |
Operating voltage range | 85% to 110% of rated voltage |
Interelectrode voltage | 8 VAC |
Interelectrode current | Approx. 1 mA AC max. |
Power consumption | Approx. 6.4 VA max. |
Interelectrode operate resistance | 0 to approx. 4 kΩ |
Interelectrode release resistance | Approx. 15 k to |
Response time | Operate: 80 ms max. |
Release: 160 ms max. | |
Cable length *3 | 1 km max. |
Control output | 2 A, 200 VAC (Inductive load: cosφ = 0.4) |
5 A, 200 VAC (Resistive load) | |
Ambient temperature | Operating: -10 to 55°C |
Ambient humidity | Operating: 45% to 85% RH |
Insulation resistance *4 |
100 MΩ min. (at 500 VDC) |
Dielectric strength *4 |
2000 VAC, 50/60 Hz for 1 min. |
Life expectancy | Electrical: 500,000 operations min. |
Mechanical: 5,000,000 operations min. | |
Weight | Approx. 495 g |
*1. The relay in the 61F-G1H/-G2H/-IPH de-energizes when there is water present across the Electrodes, whereas the relay in the 61F-GP-N8HY energizes when there is water present across the Electrodes.
*2. Models are available for 2 km and 4 km.
*3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers.
*4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for Floatless Level Controllers.
*5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
*6. High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the internal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal relay will operate.
Tham khảo thêm các model chi tiết:
Floatless switch for general use, automatic water supply with idling prevention or drought alarm, AC100V
kinds | Floatless switch, general purpose plug-in type |
---|---|
Purpose | Automatic water supply that also serves as a pump idling prevention or drought alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
Purpose | Automatic water supply that also serves as a pump idling prevention or drought alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC100V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
power consumption | Approximately 6.4VA | |
interelectrode voltage | AC8V | |
Interelectrode current | Approximately AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistive load: AC200V 5A Inductive load: AC200V 2A (cosφ=0.4) |
lifespan | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | During use: -10~55℃ | |
Ambient humidity range | In use: 45-85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
mass | Approximately 495g |
Floatless switch for general use, automatic water supply with idling prevention or drought alarm, AC200V
kinds | Floatless switch, general purpose plug-in type |
---|---|
use | Automatic water supply that also serves as a pump idling prevention or drought alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | About 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
use | Automatic water supply that also serves as a pump idling prevention or drought alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC200V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
Consumption of electricity | About 6.4VA | |
interelectrode voltage | AC8V | |
Current between electrodes | About AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | About 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistance load: AC200V 5A Induction load: AC200V 2A (cosφ=0.4) |
life | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | When in use: -10~55℃ | |
Ambient humidity range | During use: 45~85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
quality | Approximately 495g |
Floatless switch for general use, automatic water supply or automatic drainage with water increase alarm, AC100V
kinds | Floatless switch, general purpose plug-in type |
---|---|
use | Automatic water supply or automatic drainage with water rise alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | About 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
use | Automatic water supply or automatic drainage with water rise alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC100V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
Consumption of electricity | About 6.4VA | |
interelectrode voltage | AC8V | |
Current between electrodes | About AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | About 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistance load: AC200V 5A Induction load: AC200V 2A (cosφ=0.4) |
life | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | When in use: -10~55℃ | |
Ambient humidity range | During use: 45~85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
quality | Approximately 495g |
Floatless switch for general use, automatic water supply or automatic drain with water increase alarm, AC200V
kinds | Floatless switch, general purpose plug-in type |
---|---|
use | Automatic water supply or automatic drainage with water rise alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | About 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
use | Automatic water supply or automatic drainage with water rise alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC200V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
Consumption of electricity | About 6.4VA | |
interelectrode voltage | AC8V | |
Current between electrodes | About AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | About 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistance load: AC200V 5A Induction load: AC200V 2A (cosφ=0.4) |
life | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | When in use: -10~55℃ | |
Ambient humidity range | During use: 45~85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
quality | Approximately 495g |
Floatless switch for general use, water level display and alarm, AC100V
kinds | Floatless switch, general purpose plug-in type |
---|---|
Purpose | Water level display and alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
Purpose | Water level display and alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC100V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
power consumption | Approximately 6.4VA | |
interelectrode voltage | AC8V | |
Interelectrode current | Approximately AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistive load: AC200V 5A Inductive load: AC200V 2A (cosφ=0.4) |
lifespan | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | During use: -10~55℃ | |
Ambient humidity range | In use: 45-85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
mass | Approximately 495g |
Floatless switch for general use, water level display and alarm, AC200V
kinds | Floatless switch, general purpose plug-in type |
---|---|
Purpose | Water level display and alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
Purpose | Water level display and alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC200V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
power consumption | Approximately 6.4VA | |
interelectrode voltage | AC8V | |
Interelectrode current | Approximately AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistive load: AC200V 5A Inductive load: AC200V 2A (cosφ=0.4) |
lifespan | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | During use: -10~55℃ | |
Ambient humidity range | In use: 45-85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
mass | Approximately 495g |
Floatless switch for general use, water level display and alarm, AC220V
kinds | Floatless switch, general purpose plug-in type |
---|---|
Purpose | Water level display and alarm |
Control target | General purified water, sewage |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more |
kinds | Floatless switch, general purpose plug-in type |
|
---|---|---|
Purpose | Water level display and alarm | |
Control target | General purified water, sewage | |
Rated voltage | AC220V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
power consumption | Approximately 6.4VA | |
interelectrode voltage | AC8V | |
Interelectrode current | Approximately AC1mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0~4kΩ | |
Interelectrode return resistance (recommended value) | Approximately 15kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistive load: AC200V 5A Inductive load: AC200V 2A (cosφ=0.4) |
lifespan | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | During use: -10~55℃ | |
Ambient humidity range | In use: 45-85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
mass | Approximately 495g |
Switch without float, for low sensitivity, for low sensitivity, water level display and alarm, AC100V
kinds | Switch without float, plug-in type for low sensitivity |
---|---|
use | Water level display and alarm |
Control target | Liquids with low specific resistance such as salt water, sewage, acidic chemicals, alkaline chemicals, etc. |
Interelectrode operating resistance (recommended value) | Approximately 0 to 1.8kΩ |
Interelectrode return resistance (recommended value) | Approximately 5kΩ or more |
kinds | Switch without float, plug-in type for low sensitivity |
|
---|---|---|
use | Water level display and alarm | |
Control target | Liquids with low specific resistance such as salt water, sewage, acidic chemicals, alkaline chemicals, etc. | |
Rated voltage | AC100V | |
Allowable voltage fluctuation range | 85-110% of power supply voltage | |
Consumption of electricity | About 6.4VA | |
interelectrode voltage | AC8V | |
Current between electrodes | About AC1.2mA or less | |
Interelectrode operating resistance (recommended value) | Approximately 0 to 1.8kΩ | |
Interelectrode return resistance (recommended value) | Approximately 5kΩ or more | |
response time | During operation: 80ms or less During recovery: 160ms or less |
|
control output | Opening/closing capacity | Resistance load: AC200V 5A Induction load: AC200V 2A (cosφ=0.4) |
life | Electrical: 500,000 times or more Mechanical: 5 million times or more |
|
Ambient temperature range | When in use: -10~55℃ | |
Ambient humidity range | During use: 45~85%RH | |
insulation resistance | Between the power supply part and the electrode part: 100MΩ or more (at 500V DC megger) Between the power supply part and the contact circuit part: 100MΩ or more (at 500V DC megger) Between the electrode part and the contact circuit part: 100MΩ or more (at 500V DC megger) |
|
Withstand voltage | Between the power supply section and the electrode section: AC2000V 50/60Hz 1min Between the power supply section and the contact circuit section: AC2000V 50/60Hz 1min Between the electrode section and the contact circuit section: AC2000V 50/60Hz 1min |
|
wiring distance | Cable used: 1km or less Note: Value when using fully insulated 600V 0.75mm 2 , 3-core cabtyre cable |
|
quality | Approximately 495g |
Surface connection socket, 14 pin