| Height | 90 mm |
| Width | 17.7 mm |
| Depth | 74.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms /3x, X, Y, Z) |
| Vibration (operation) | 5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z) |
| IEC test classification | III |
| T3 | |
| EN type | T3 |
| IEC power supply system | TT |
| TN-S | |
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| (L+) - (L-) | |
| (L+/L-) - PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
| Nominal voltage UN | 230 V AC (TN-S) |
| 230 V AC (TT - only in use with RCD) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| 230 V DC | |
| Rated load current IL | 26 A (30 °C) |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In (8/20) µs | 3 kA |
| Standby power consumption PC | ≤ 275 mVA (at UREF) |
| ≤ 300 mVA (at UC) | |
| Reference test voltage UREF | 255 V AC |
| Combination wave UOC | 6 kV |
| Voltage protection level Up (L-N) | ≤ 1.35 kV |
| Voltage protection level Up (L-PE) | ≤ 1.5 kV |
| Voltage protection level Up (N-PE) | ≤ 1.5 kV |
| TOV behavior at UT (L-N) | 440 V AC (5 s / withstand mode) |
| 440 V AC (120 min / withstand mode) | |
| TOV behavior at UT (L-PE) | 440 V AC (5 s / withstand mode) |
| 440 V AC (120 min / withstand mode) | |
| 1455 V AC (200 ms / safe failure mode) | |
| TOV behavior at UT (N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA (L-N) | ≤ 25 ns |
| Response time tA (L-PE) | ≤ 100 ns |
| Response time tA (N-PE) | ≤ 100 ns |
| Short-circuit current rating ISCCR | 1.5 kA AC |
| 0.25 kA DC | |
| Max. backup fuse with branch wiring | not required |
| Maximum backup fuse for through wiring | 25 A (gG / B / C) |
| Switching function | N/C contact |
| Operating voltage | 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 3 A AC |
| 1 A DC (30 V DC) | |
| Connection method | Screw connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| SPD Type | 4CA |
| Maximum continuous operating voltage MCOV | 255 V AC |
| 230 V DC | |
| Nominal voltage | 230 V DC |
| Rated load current IL | 25 A |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| (L+) - (L-) | |
| (L+) - G | |
| (L-) - G | |
| Power distribution system | 1 |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 1290 V |
| Measured limiting voltage MLV (L-G) | 1310 V |
| Measured limiting voltage MLV (N-G) | 1310 V |
| Measured limiting voltage MLV (L+) - (L-) | 1290 V |
| Measured limiting voltage MLV (L+) - G | 1310 V |
| Measured limiting voltage MLV (L-) - G | 1310 V |
| Nominal discharge current In | 3 kA |
| Tightening torque | 5 lbf-in. ... 7 lbf-in. |
| Conductor cross section AWG | 14 ... 12 |
| Conductor cross section AWG | 14 ... 12 |
| Tightening torque | 5 lbf-in. ... 7 lbf-in. |
| Standards/specifications | IEC 61643-11 2011 |
| EN 61643-11 2012 |
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130806 |
| eCl@ss 8.0 | 27130806 |
| eCl@ss 9.0 | 27130806 |
| ETIM 5.0 | EC000942 |
| ETIM 6.0 | EC000942 |
| UNSPSC 13.2 | 39121620 |

Thiết bị chống sét lan truyền đường nguồn 2 pha, 4 dây (L1, L2, N, PE) Loại T2Giá tốt nhất xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 2 pha, 3 dây (L1, L2, PEN) Loại T2 -Giá tốt nhất xem...0909186879 Email
Thiết bị chống sét lan truyền quang điện mặt trời Solar PV T2 1000vDC 40kA -Giá tốt nhất xem...0909186879 Email
Thiết bị kết hợp cắt sét và chống sét lan truyền T1+T2 cho điện mặt trời 600vDCGiá tốt nhất xem...0909186879 Email
Chống sét Phoenix Contact VAL-MS 230/3+1 - 2838209 | T2 3P 40kA 25nsGiá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 3 pha, 4 dây (L1, L2, L3, PEN) Loại T1 -Phoenix Contact -FLT-SEC-P-T1-3C-350/25-FM 2905419Giá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền quang điện mặt trời Solar PV T2 600vDC 40kA - DEHN - DG YPV SCI 600 - Part No. 950531Giá tốt nhất Xem...0909186879 Email
Thiết bị chống sét lan truyền đường nguồn 3 pha, 5 dây (L1, L2, L3, N, PE) loại T2 - Phoenix Contact - VAL-SEC-T2-3S-350-FM 2905340Giá tốt nhất Xem...0909186879 Email
Chống sét Phoenix Contact VAL-MS 230/1+1 - 2804429 | T2 40kA 25ns 1P L1-N-PEGiá tốt nhất Xem...0909186879 Email