range | Acti 9 | |
product name | Acti 9 PRD1 Master | |
product or component type | Surge arrester with pluggable cartridge | |
device short name | PRD1 Master | |
device application | Distribution | |
poles description | 3P | |
remote signalling | With | |
signal contacts composition | 1 SD (1 C/O) | |
surge arrester type | Electrical distribution network | |
earthing system | TN-C |
surge arrester class type | Type 1 | |
surge arrester technology | Spark gap | |
[Ue] rated operational voltage | 230 V (+/- 10 %) AC 50 Hz 400 V (+/- 10 %) AC 50 Hz |
|
nominal discharge current | Common mode : 25 kA L/PE | |
[Iimp] impulse current | Common mode : 25 kA L/PE 12.5 A.s | |
[Uc] maximum continuous operating voltage | Common mode : 350 V L/PE | |
[Up] voltage protection level | 1.5 kV type 2 common mode L/PE | |
[Ut] temporary overvoltage | Withstand : 1200 V N/PE for 200 ms Withstand : 415 V L/N for 5 s Safe failure mode : 440 V L/N for 7200 ms |
|
[If] follow current | 100 A common mode N/PE 50 kA differential mode L/N |
|
disconnector device type | Associated fuse gG 315 A according to standard Associated circuit breaker Compact NSX100F 100 A curve C - Icu 36 kA Associated circuit breaker Compact NSX100N 100 A curve C - Icu 50 kA |
|
short-circuit withstand | 50 kA | |
local signalling | Flag color: white/red | |
signalling circuit voltage | 1 A/250 V AC 1 A/30 V DC |
|
mounting mode | Clip-on | |
mounting support | DIN rail | |
9 mm pitches | 12 | |
height | 90 mm | |
width | 108 mm | |
depth | 71 mm | |
product weight | 1175 g | |
colour | Anthracite grey ( RAL 7016 ) | |
material | PBT (polybutylene terephthalate) | |
response time | < 100 ns | |
connections - terminals | Tunnel type terminal, top or bottom 10...35 mm² cable(s) rigid Tunnel type terminal, top or bottom 10...25 mm² cable(s) flexible |
|
tightening torque | 4.5 N.m |
standards | EN 61643-11 : 2012 IEC 61643-11 : 2011 |
|
product certifications | CE | |
quality labels | KEMA-KEUR | |
IP degree of protection | On front face : IP40 conforming to IEC 60529 Built-in : IP20 conforming to IEC 60529 |
|
IK degree of protection | IK05 conforming to IEC 62262 | |
relative humidity | 5...95 % | |
operating altitude | 2000 m | |
ambient air temperature for operation | -25...60 °C | |
ambient air temperature for storage | -40...80 °C |
RoHS (date code: YYWW) | Compliant - since 0601 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity | |
REACh | Reference not containing SVHC above the threshold |
Warranty period | 18 months |