range | Acti 9 |
product name | Acti 9 iPRD |
product or component type | Surge arrester with pluggable cartridge |
device short name | IPRD65r |
device application | Distribution |
poles description | 1P |
remote signalling | With |
signal contacts composition | 1 SD (1 C/O) |
surge arrester type | Electrical distribution network |
earthing system | TN-C TT |
surge arrester class type | Type 2 |
surge arrester technology | MOV |
[Ue] rated operational voltage | 230 V (+/- 10 %) AC 50/60 Hz 400 V (+/- 10 %) AC 50/60 Hz |
nominal discharge current | Common mode : 20 kA L/PE Common mode : 20 kA N/PE |
maximum discharge current | Common mode : 65 kA L/PE |
[Uc] maximum continuous operating voltage | Common mode : 350 V L/PE Common mode : 350 V N/PE |
[Up] voltage protection level | 1.5 kV type 2 common mode L/PE |
[Ut] temporary overvoltage | Withstand : 337 V L/N for 5 s Safe failure mode : 1200 V N/PE for 200 ms |
disconnector device type | Associated circuit breaker iC60H 50 A curve C - Icu 15 kA Associated circuit breaker iC60N 50 A curve C - Icu 10 kA Associated circuit breaker NG125N 50 A curve C - Icu 25 kA Associated circuit breaker NG125H 100 A curve C - Icu 36 kA Associated circuit breaker NG125L 100 A curve C - Icu 50 kA |
short-circuit withstand | 50 kA |
local signalling | Flag color: white/red |
signalling circuit voltage | 0.25 A/250 V AC 50/60 Hz |
mounting mode | Clip-on |
mounting support | DIN rail |
9 mm pitches | 2 |
height | 85 mm |
width | 18 mm |
depth | 69 mm |
product weight | 0.136 kg |
colour | White ( RAL 9003 ) |
response time | <= 25 ns |
residual current | 0.6 mA 0.003 mA |
connections - terminals | Tunnel type terminal, downside 2.5...35 mm² Tunnel type terminal, upside 2.5...35 mm² |
tightening torque | 2.5 N.m |
standards | EN 61643-11 : 2012 IEC 61643-11 : 2011 |
product certifications | CE |
quality labels | NF KEMA-KEUR |
IP degree of protection | On front face : IP40 conforming to IEC 60529 Built-in : IP20 conforming to IEC 60529 |
IK degree of protection | IK03 conforming to IEC 62262 |
relative humidity | 5...95 % |
operating altitude | 2000 m |
ambient air temperature for operation | -25...60 °C |
ambient air temperature for storage | -40...85 °C |
Sustainable offer status | Green Premium product |
RoHS (date code: YYWW) | Compliant - since 0844 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity |
REACh | Reference not containing SVHC above the threshold |
Product environmental profile | Available Product environmental |
Product end of life instructions | Available End of life manual |
Warranty period | 18 months |