Bộ Lập trình điều khiển PLCs

Bộ lập trình PLC Siemens S7-1200 Controller CPU 1214C

Bộ lập trình điều khiển PLC được đề nghị cho S7 với các tùy chọn mở rộng linh hoạt; Có thể mở rộng bằng: 1 bảng tín hiệu (SB), bảng pin (BB) hoặc bảng giao tiếp (CB), 8 mô-đun tín hiệu (SM), Max. 3 mô-đun truyền thông (CM)
Bộ lập trình PLC Siemens S7-1200 Controller CPU 1214C

Overview

Controller for intro to S7 with flexible expansion options

Expandable by:
- 1 signal board (SB), battery board (BB) or communication board (CB)
- 8 signal modules (SM)
- Max. 3 communication modules (CM)


 

Design

The compact CPU 1214C has:

- 3 device versions with different power supply and control voltages
- Integrated power supply either as wide-range AC or DC power supply (85 to 264 V AC or 24 V DC)
- Integrated 24 V encoder/load current supply: 
- For direct connection of sensors and encoders. With 400 mA, the output current can also be used as load power supply
- 14 integrated digital inputs 24 V DC (current sinking/current sourcing (IEC type 1 current sinking))
- 10 integrated digital outputs, either 24 V DC or relay
- 2 integrated analog inputs 0 to 10 V
- 2 pulse outputs (PTO) with a frequency of up to 100 kHz
- Pulse-width modulated outputs (PWM) with a frequency of up to 100 kHz
- Integrated Ethernet interface (TCP/IP native, ISO-on-TCP)
- 6 fast counters (3 with max. 100 kHz; 3 with max. 30 kHz), with parameterizable enable and reset inputs, can be used simultaneously as up and down counters with 2 separate inputs or for connecting incremental encoders
- Expansion by additional communication interfaces, e.g. RS485 or RS232
- Expansion by analog or digital signals directly on the CPU via signal board (with retention of CPU mounting dimensions)
- Expansion by a wide range of analog and digital input and output signals via signal modules
- Optional memory expansion (SIMATIC Memory Card)
- PID controller with auto-tuning functionality
- Integral real-time clock
- Interrupt inputs: 
  For extremely fast response to rising or falling edges of process signals
- Removable terminals on all modules
- Simulator (optional): 
  For simulating the integrated inputs and for testing the user program

Device versions

       

Version

Supply voltage

Input voltage DI

Output voltage DO

Output current

  • DC/DC/DC

24 V DC

24 V DC

24 V DC

0.5 A, transistor

  • DC/DC/relay

24 V DC

24 V DC

5 … 30 V DC / 
5 … 250 V AC

2 A; 
30 W DC / 
200 W AC

  • AC/DC/relay

85 … 264 V AC

24 V DC

5 … 30 V DC / 
5 … 250 V AC

2 A; 
30 W DC / 
200 W AC

 


 

Function

Comprehensive instruction set: 
A wide range of operations facilitates programming:
- Basic operations such as binary logic operations, result allocation, save, count, create times, load, transfer, compare, shift, rotate, create complement, call subprogram (with local variables)
- Integral communication commands (e.g. USS protocol, Modbus RTU, S7 communication "T-Send/T-Receive" or Freeport)
- User-friendly functions such as pulse-width modulation, pulse sequence function, arithmetic functions, floating point arithmetic, PID closed-loop control, jump functions, loop functions and code conversions
- Mathematical functions, e.g. SIN, COS, TAN, LN, EXP


Counting: 
User-friendly counting functions in conjunction with the integrated counters and special commands for high-speed counters open up new application areas for the user.


Interrupt processing: 
- Edge-triggered interrupts (activated by rising or falling edges of process signals on interrupt inputs) support a rapid response to process events.
- Time-triggered interrupts.
- Counter interrupts can be triggered when a setpoint is reached or when the direction of counting changes.
- Communication interrupts allow the rapid and easy exchange of information with peripheral devices such as printers or bar code readers.

Password protection

Test and diagnostics functions: 
Easy-to-use functions support testing and diagnostics, e.g. online/offline diagnostics.

"Forcing" of inputs and outputs during testing and diagnostics: 
Inputs and outputs can be set independently of cycle and thus permanently, for example, to test the user program.

Motion Control in accordance with PLCopen for simple movements.

Library functionality


 

Programming

The STEP 7 Basic programming package permits complete programming of all S7-1200 controllers and the associated I/O.


 

Technical specifications

Article number

6ES7214-1BG40-0XB0

6ES7214-1AG40-0XB0

6ES7214-1HG40-0XB0

 

CPU 1214C, AC/DC/Relay, 14DI/10DO/2AI

CPU 1214C, DC/DC/DC, 14DI/10DO/2AI

CPU 1214C, DC/DC/Relay, 14DI/10DO/2AI

General information

 

 

 

Product type designation

CPU 1214C AC/DC/relay

CPU 1214C DC/DC/DC

CPU 1214C DC/DC/relay

Firmware version

V4.2

V4.2

V4.2

Engineering with

 

 

 

  • ● Programming package

STEP 7 V14 or higher

STEP 7 V14 or higher

STEP 7 V14 or higher

Supply voltage

 

 

 

Rated value (DC)

 

 

 

  • ● 24 V DC

 

Yes

Yes

permissible range, lower limit (DC)

 

20.4 V

20.4 V

permissible range, upper limit (DC)

 

28.8 V

28.8 V

Rated value (AC)

 

 

 

  • ● 120 V AC

Yes

 

 

  • ● 230 V AC

Yes

 

 

permissible range, lower limit (AC)

85 V

 

 

permissible range, upper limit (AC)

264 V

 

 

Reverse polarity protection

 

Yes

Yes

Line frequency

 

 

 

  • ● permissible range, lower limit

47 Hz

 

 

  • ● permissible range, upper limit

63 Hz

 

 

Load voltage L+

 

 

 

  • ● Rated value (DC)

 

24 V

24 V

  • ● permissible range, lower limit (DC)

 

20.4 V

20.4 V

  • ● permissible range, upper limit (DC)

 

28.8 V

28.8 V

Input current

 

 

 

Current consumption (rated value)

100 mA at 120 V AC; 50 mA at 240 V AC

500 mA; CPU only

500 mA; CPU only

Current consumption, max.

300 mA at 120 V AC; 150 mA at 240 V AC

1 500 mA; CPU with all expansion modules

1 500 mA; CPU with all expansion modules

Inrush current, max.

20 A; at 264 V

12 A; at 28.8 V

12 A; at 28.8 V

I²t

0.8 A²·s

0.5 A²·s

0.8 A²·s

Output current

 

 

 

for backplane bus (5 V DC), max.

1 600 mA; Max. 5 V DC for SM and CM

1 600 mA; Max. 5 V DC for SM and CM

1 600 mA; Max. 5 V DC for SM and CM

Encoder supply

 

 

 

24 V encoder supply

 

 

 

  • ● 24 V

20.4 to 28.8V

L+ minus 4 V DC min.

L+ minus 4 V DC min.

Power loss

 

 

 

Power loss, typ.

14 W

12 W

12 W

Memory

 

 

 

Work memory

 

 

 

  • ● integrated

100 kbyte

100 kbyte

100 kbyte

  • ● expandable

No

No

No

Load memory

 

 

 

  • ● integrated

4 Mbyte

4 Mbyte

4 Mbyte

  • ● Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

with SIMATIC memory card

with SIMATIC memory card

Backup

 

 

 

  • ● present

Yes

Yes

Yes

  • ● maintenance-free

Yes

Yes

Yes

  • ● without battery

Yes

Yes

Yes

CPU processing times

 

 

 

for bit operations, typ.

0.08 µs; / instruction

0.08 µs; / instruction

0.08 µs; / instruction

for word operations, typ.

1.7 µs; / instruction

1.7 µs; / instruction

1.7 µs; / instruction

for floating point arithmetic, typ.

2.3 µs; / instruction

2.3 µs; / instruction

2.3 µs; / instruction

CPU-blocks

 

 

 

Number of blocks (total)

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

 

 

 

  • ● Number, max.

Limited only by RAM for code

Limited only by RAM for code

Limited only by RAM for code

Data areas and their retentivity

 

 

 

Retentive data area (incl. timers, counters, flags), max.

10 kbyte

10 kbyte

10 kbyte

Flag

 

 

 

  • ● Number, max.

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

Local data

 

 

 

  • ● per priority class, max.

16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Process image

 

 

 

  • ● Inputs, adjustable

1 kbyte

1 kbyte

1 kbyte

  • ● Outputs, adjustable

1 kbyte

1 kbyte

1 kbyte

Hardware configuration

 

 

 

Number of modules per system, max.

3 comm. modules, 1 signal board, 8 signal modules

3 comm. modules, 1 signal board, 8 signal modules

3 comm. modules, 1 signal board, 8 signal modules

Time of day

 

 

 

Clock

 

 

 

  • ● Hardware clock (real-time)

Yes

Yes

Yes

  • ● Backup time

480 h; Typical

480 h; Typical

480 h; Typical

  • ● Deviation per day, max.

±60 s/month at 25 °C

±60 s/month at 25 °C

±60 s/month at 25 °C

Digital inputs

 

 

 

Number of digital inputs

14; Integrated

14; Integrated

14; Integrated

  • ● of which inputs usable for technological functions

6; HSC (High Speed Counting)

6; HSC (High Speed Counting)

6; HSC (High Speed Counting)

Source/sink input

Yes

Yes

Yes

Number of simultaneously controllable inputs

 

 

 

all mounting positions

 

 

 

  • — up to 40 °C, max.

14

14

14

Input voltage

 

 

 

  • ● Rated value (DC)

24 V

24 V

24 V

  • ● for signal "0"

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

  • ● for signal "1"

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

Input delay (for rated value of input voltage)

 

 

 

for standard inputs

 

 

 

  • — parameterizable

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

  • — at "0" to "1", min.

0.2 ms

0.2 ms

0.2 ms

  • — at "0" to "1", max.

12.8 ms

12.8 ms

12.8 ms

for interrupt inputs

 

 

 

  • — parameterizable

Yes

Yes

Yes

for technological functions

 

 

 

  • — parameterizable

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Cable length

 

 

 

  • ● shielded, max.

500 m; 50 m for technological functions

500 m; 50 m for technological functions

500 m; 50 m for technological functions

  • ● unshielded, max.

300 m; For technological functions: No

300 m; For technological functions: No

300 m; For technological functions: No

Digital outputs

 

 

 

Number of digital outputs

10; Relays

10

10; Relays

  • ● of which high-speed outputs

 

4; 100 kHz Pulse Train Output

 

Limitation of inductive shutdown voltage to

 

L+ (-48 V)

 

Switching capacity of the outputs

 

 

 

  • ● with resistive load, max.

2 A

0.5 A

2 A

  • ● on lamp load, max.

30 W with DC, 200 W with AC

5 W

30 W with DC, 200 W with AC

Output voltage

 

 

 

  • ● for signal "0", max.

 

0.1 V; with 10 kOhm load

 

  • ● for signal "1", min.

 

20 V

 

Output current

 

 

 

  • ● for signal "1" rated value

 

0.5 A

 

  • ● for signal "0" residual current, max.

 

0.1 mA

 

Output delay with resistive load

 

 

 

  • ● "0" to "1", max.

10 ms; max.

1 µs

10 ms; max.

  • ● "1" to "0", max.

10 ms; max.

5 µs

10 ms; max.

Switching frequency

 

 

 

  • ● of the pulse outputs, with resistive load, max.

 

100 kHz

 

Relay outputs

 

 

 

  • ● Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

 

mechanically 10 million, at rated load voltage 100 000

Cable length

 

 

 

  • ● shielded, max.

500 m

500 m

500 m

  • ● unshielded, max.

150 m

150 m

150 m

Analog inputs

 

 

 

Number of analog inputs

2

2

2

Input ranges

 

 

 

  • ● Voltage

Yes

Yes

Yes

Input ranges (rated values), voltages

 

 

 

  • ● 0 to +10 V

Yes

Yes

Yes

  • ● Input resistance (0 to 10 V)

≥100k ohms

≥100k ohms

≥100k ohms

Cable length

 

 

 

  • ● shielded, max.

100 m; twisted and shielded

100 m; twisted and shielded

100 m; twisted and shielded

Analog outputs

 

 

 

Number of analog outputs

0

0

0

Analog value generation for the inputs

 

 

 

Integration and conversion time/resolution per channel

 

 

 

  • ● Resolution with overrange (bit including sign), max.

10 bit

10 bit

10 bit

  • ● Integration time, parameterizable

Yes

Yes

Yes

  • ● Conversion time (per channel)

625 µs

625 µs

625 µs

Encoder

 

 

 

Connectable encoders

 

 

 

  • ● 2-wire sensor

Yes

Yes

Yes

1. Interface

 

 

 

Interface type

PROFINET

PROFINET

PROFINET

Physics

Ethernet

Ethernet

Ethernet

Isolated

Yes

Yes

Yes

automatic detection of transmission rate

Yes

Yes

Yes

Autonegotiation

Yes

Yes

Yes

Autocrossing

Yes

Yes

Yes

Interface types

 

 

 

  • ● Number of ports

1

1

1

  • ● integrated switch

No

No

No

Protocols

 

 

 

  • ● PROFINET IO Controller

Yes

Yes

Yes

  • ● PROFINET IO Device

Yes

Yes

Yes

  • ● SIMATIC communication

Yes

Yes

Yes

  • ● Open IE communication

Yes

Yes

Yes

  • ● Web server

Yes

Yes

Yes

  • ● Media redundancy

No

No

No

PROFINET IO Controller

 

 

 

  • ● Transmission rate, max.

100 Mbit/s

100 Mbit/s

100 Mbit/s

Services

 

 

 

  • — PG/OP communication

Yes

Yes

Yes

  • — S7 routing

Yes

Yes

Yes

  • — Isochronous mode

No

No

No

  • — Open IE communication

Yes

Yes

Yes

  • — IRT

No

No

No

  • — MRP

No

No

No

  • — MRPD

No

No

No

  • — PROFIenergy

No

No

No

  • — Prioritized startup

Yes

Yes

Yes

  • — Number of IO devices with prioritized startup, max.

16

16

16

  • — Number of connectable IO Devices, max.

16

16

16

  • — Number of connectable IO Devices for RT, max.

16

16

16

  • — of which in line, max.

16

16

16

  • — Activation/deactivation of IO Devices

Yes

Yes

Yes

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8

8

8

  • — Updating time

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

PROFINET IO Device

 

 

 

Services

 

 

 

  • — PG/OP communication

Yes

Yes

Yes

  • — S7 routing

Yes

Yes

Yes

  • — Isochronous mode

No

No

No

  • — Open IE communication

Yes

Yes

Yes

  • — IRT

No

No

No

  • — MRP

No

No

No

  • — MRPD

No

No

No

  • — PROFIenergy

Yes

Yes

Yes

  • — Shared device

Yes

Yes

Yes

  • — Number of IO Controllers with shared device, max.

2

2

2

Protocols

 

 

 

Supports protocol for PROFINET IO

Yes

Yes

Yes

PROFIBUS

Yes; CM 1243-5 required

Yes; CM 1243-5 required

Yes; CM 1243-5 required

AS-Interface

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Protocols (Ethernet)

 

 

 

  • ● TCP/IP

Yes

Yes

Yes

  • ● DHCP

No

No

No

  • ● SNMP

Yes

Yes

Yes

  • ● DCP

Yes

Yes

Yes

  • ● LLDP

Yes

Yes

Yes

Open IE communication

 

 

 

  • ● TCP/IP

Yes

Yes

Yes

  • — Data length, max.

8 kbyte

8 kbyte

8 kbyte

  • ● ISO-on-TCP (RFC1006)

Yes

Yes

Yes

  • — Data length, max.

8 kbyte

8 kbyte

8 kbyte

  • ● UDP

Yes

Yes

Yes

  • — Data length, max.

1 472 byte

1 472 byte

1 472 byte

Web server

 

 

 

  • ● supported

Yes

Yes

Yes

  • ● User-defined websites

Yes

Yes

Yes

Further protocols

 

 

 

  • ● MODBUS

Yes

Yes

Yes

Communication functions

 

 

 

S7 communication

 

 

 

  • ● supported

Yes

Yes

Yes

  • ● as server

Yes

Yes

Yes

  • ● as client

Yes

Yes

Yes

  • ● User data per job, max.

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

Number of connections

 

 

 

  • ● overall

16; dynamically

16; dynamically

16; dynamically

Test commissioning functions

 

 

 

Status/control

 

 

 

  • ● Status/control variable

Yes

Yes

Yes

  • ● Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Forcing

 

 

 

  • ● Forcing

Yes

Yes

Yes

Diagnostic buffer

 

 

 

  • ● present

Yes

Yes

Yes

Traces

 

 

 

  • ● Number of configurable Traces

2

2

2

  • ● Memory size per trace, max.

512 kbyte

512 kbyte

512 kbyte

Interrupts/diagnostics/status information

 

 

 

Diagnostics indication LED

 

 

 

  • ● RUN/STOP LED

Yes

Yes

Yes

  • ● ERROR LED

Yes

Yes

Yes

  • ● MAINT LED

Yes

Yes

Yes

Integrated Functions

 

 

 

Number of counters

6

6

6

Counting frequency (counter) max.

100 kHz

100 kHz

100 kHz

Frequency measurement

Yes

Yes

Yes

controlled positioning

Yes

Yes

Yes

Number of position-controlled positioning axes, max.

8

8

8

Number of positioning axes via pulse-direction interface

Up to 4 with SB 1222

4; With integrated outputs

Up to 4 with SB 1222

PID controller

Yes

Yes

Yes

Number of alarm inputs

4

4

4

Number of pulse outputs

 

4

 

Limit frequency (pulse)

 

100 kHz

 

Potential separation

 

 

 

Potential separation digital inputs

 

 

 

  • ● Potential separation digital inputs

500V AC for 1 minute

No

500V AC for 1 minute

  • ● between the channels, in groups of

1

1

1

Potential separation digital outputs

 

 

 

  • ● Potential separation digital outputs

Relays

Yes

Relays

  • ● between the channels

No

No

No

  • ● between the channels, in groups of

2

1

2

EMC

 

 

 

Interference immunity against discharge of static electricity

 

 

 

  • ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes

Yes

Yes

  • — Test voltage at air discharge

8 kV

8 kV

8 kV

  • — Test voltage at contact discharge

6 kV

6 kV

6 kV

Interference immunity to cable-borne interference

 

 

 

  • ● Interference immunity on supply lines acc. to IEC 61000-4-4

Yes

Yes

Yes

  • ● Interference immunity on signal cables acc. to IEC 61000-4-4

Yes

Yes

Yes

Interference immunity against voltage surge

 

 

 

  • ● on the supply lines acc. to IEC 61000-4-5

Yes

Yes

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields

 

 

 

  • ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6

Yes

Yes

Yes

Emission of radio interference acc. to EN 55 011

 

 

 

  • ● Limit class A, for use in industrial areas

Yes; Group 1

Yes; Group 1

Yes; Group 1

  • ● Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Degree and class of protection

 

 

 

Degree of protection acc. to EN 60529

 

 

 

  • ● IP20

Yes

Yes

Yes

Standards, approvals, certificates

 

 

 

CE mark

Yes

Yes

Yes

UL approval

Yes

Yes

Yes

cULus

Yes

Yes

Yes

FM approval

Yes

Yes

Yes

RCM (formerly C-TICK)

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Marine approval

Yes

Yes

Yes

Ambient conditions

 

 

 

Free fall

 

 

 

  • ● Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

 

 

 

  • ● min.

-20 °C

-20 °C

-20 °C

  • ● max.

60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical

60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical

60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical

  • ● horizontal installation, min.

-20 °C

-20 °C

-20 °C

  • ● horizontal installation, max.

60 °C

60 °C

60 °C

  • ● vertical installation, min.

-20 °C

-20 °C

-20 °C

  • ● vertical installation, max.

50 °C

50 °C

50 °C

Ambient temperature during storage/transportation

 

 

 

  • ● min.

-40 °C

-40 °C

-40 °C

  • ● max.

70 °C

70 °C

70 °C

Air pressure acc. to IEC 60068-2-13

 

 

 

  • ● Operation, min.

795 hPa

795 hPa

795 hPa

  • ● Operation, max.

1 080 hPa

1 080 hPa

1 080 hPa

  • ● Storage/transport, min.

660 hPa

660 hPa

660 hPa

  • ● Storage/transport, max.

1 080 hPa

1 080 hPa

1 080 hPa

Altitude during operation relating to sea level

 

 

 

  • ● Installation altitude, min.

-1 000 m

-1 000 m

-1 000 m

  • ● Installation altitude, max.

2 000 m

2 000 m

2 000 m

Relative humidity

 

 

 

  • ● Operation, max.

95 %; no condensation

95 %; no condensation

95 %; no condensation

Vibrations

 

 

 

  • ● Vibration resistance during operation acc. to IEC 60068-2-6

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

  • ● Operation, tested according to IEC 60068-2-6

Yes

Yes

Yes

Shock testing

 

 

 

  • ● tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

 

 

 

  • ● SO2 at RH < 60% without condensation

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Programming

 

 

 

Programming language

 

 

 

  • — LAD

Yes

Yes

Yes

  • — FBD

Yes

Yes

Yes

  • — SCL

Yes

Yes

Yes

Know-how protection

 

 

 

  • ● User program protection/password protection

Yes

Yes

Yes

  • ● Copy protection

Yes

Yes

Yes

  • ● Block protection

Yes

Yes

Yes

Access protection

 

 

 

  • ● Protection level: Write protection

Yes

Yes

Yes

  • ● Protection level: Read/write protection

Yes

Yes

Yes

  • ● Protection level: Complete protection

Yes

Yes

Yes

Cycle time monitoring

 

 

 

  • ● adjustable

Yes

Yes

Yes

Dimensions

 

 

 

Width

110 mm

110 mm

110 mm

Height

100 mm

100 mm

100 mm

Depth

75 mm

75 mm

75 mm

Weights

 

 

 

Weight, approx.

455 g

415 g

435 g


 

(Nguyễn Thảo Trường - http://DienElectric.com theo Siemens)


 