Note:
SIMATIC Memory Card required for operation of the CPU
The CPU 1513-1 PN features:
- A powerful processor:
The CPU achieves command execution times as low as 40 ns per binary instruction.
- A large work memory:
300 KB for program, 1.5 MB for data
- SIMATIC Memory Cards as load memory;
permit additional functions such as datalog and archives
- Flexible expansion capability:
single-tier configuration with max. 32 modules (CPU + 31 modules)
- Display with functions for:
Display of overview information such as IP address of the integrated interface, station name, higher level designation, location designation, etc.,
+ Display and acknowledgment of diagnostic and user messages
+ Display of module information
+ Showing display settings
+ Display of a user-definable logo
+ Setting of IP addresses
+ Setting of date and time
+ Selection of the operating mode
+ Resetting of the CPU to factory settings
+ Backup and restoring of the project
+ Disabling/enabling of the display
+ Enabling of protection levels
- PROFINET IO IRT interface for connecting distributed I/O via PROFINET
Performance
- Faster command processing, language extensions and new data types depending on the CPU type
- Even shorter response times of the CPUs due to considerably faster backplane bus
- Powerful network connection:
- each CPU is equipped with PROFINET IO IRT (2-port switch) as standard interface.
Integrated technology
- Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)
- Support of speed-controlled and positioning axes as well as external encoders, precise position gearing between axes, cams/cam tracks and probes
- Trace functions for all CPU tags, both for diagnostics in real time as well as for sporadic error detection; can also be called via the web server of the CPU
- Comprehensive control functionalities, e.g. easy to configure blocks for automatic optimization of the control parameters for optimum control quality
Security Integrated
- Password-based know-how protection against unauthorized read-out and modification of program blocks
- Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card: The block can only run if the configured memory card is inserted into the CPU.
- 4-level authorization concept:
Communication to the HMI devices can also be restricted.
- Manipulation protection:
The controller recognizes changed or unauthorized transmissions of the engineering data.
Design and handling
- Display of overview information:
E.g. Station name, plant identifier, location designation, etc., diagnostic information, module information, display settings.
- Possible operations on the display:
Set addresses of the CPU or connected Ethernet communications processors, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels, acknowledge messages, backup and restoring of the project.
Integrated system diagnostics
System diagnostics information is displayed consistently and in plain text in the display, TIA Portal, HMI devices and Web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
Integrated in the firmware of the CPU, no special configuration is required
SIMATIC Memory Card (required for operation of the CPU)
- Used as a plug-in load memory or for updating the firmware.
- Also for storing additional documents or csv files (for recipes and archives)
- Creation of data blocks for storage/reading of data via SFCs of the user program
Datalog (archives) and recipes
- Storage of csv files for recipes and archives on the SIMATIC Memory Card;
- easy access to plant-relevant operating data using Office tools or via a web server
- Easy access to configuration data of the machine by means of a Web browser or SD card reader (two-way data exchange from and to the controller)
Programming
- Programming with STEP 7 Professional, V12 and higher
- Migration tool for migrating from SIMATIC S7-300/S7-400 to S7-1500; converts the program code largely automatically. Non-convertible code is logged and can be manually adapted.
- STEP 7 V11 projects can continue to be used with STEP 7 V12 in compatibility mode.
- S7-1200 basic programs can be transferred to S7-1500 by copy-paste.
Article number |
6ES7513-1AL02-0AB0 |
|
---|---|---|
|
CPU 1513-1 PN, 300KB Prog., 1,5MB Data |
|
General information |
|
|
Product type designation |
CPU 1513-1 PN |
|
HW functional status |
FS01 |
|
Firmware version |
V2.6 |
|
Product function |
|
|
|
Yes; I&M0 to I&M3 |
|
Engineering with |
|
|
|
V15.1 (FW V2.6) / V15 (FW V2.5) or higher; with older TIA Portal versions configurable as 6ES7513-1AL01-0AB0 |
|
Configuration control |
|
|
via dataset |
Yes |
|
Display |
|
|
Screen diagonal [cm] |
3.45 cm |
|
Control elements |
|
|
Number of keys |
8 |
|
Mode buttons |
2 |
|
Supply voltage |
|
|
Type of supply voltage |
24 V DC |
|
permissible range, lower limit (DC) |
19.2 V |
|
permissible range, upper limit (DC) |
28.8 V |
|
Reverse polarity protection |
Yes |
|
Mains buffering |
|
|
|
5 ms |
|
|
1/s |
|
Input current |
|
|
Current consumption (rated value) |
0.7 A |
|
Current consumption, max. |
0.95 A |
|
Inrush current, max. |
1.9 A; Rated value |
|
I²t |
0.02 A²·s |
|
Power |
|
|
Infeed power to the backplane bus |
10 W |
|
Power consumption from the backplane bus (balanced) |
5.5 W |
|
Power loss |
|
|
Power loss, typ. |
5.7 W |
|
Memory |
|
|
Number of slots for SIMATIC memory card |
1 |
|
SIMATIC memory card required |
Yes |
|
Work memory |
|
|
|
300 kbyte |
|
|
1.5 Mbyte |
|
Load memory |
|
|
|
32 Gbyte |
|
Backup |
|
|
|
Yes |
|
CPU processing times |
|
|
for bit operations, typ. |
40 ns |
|
for word operations, typ. |
48 ns |
|
for fixed point arithmetic, typ. |
64 ns |
|
for floating point arithmetic, typ. |
256 ns |
|
CPU-blocks |
|
|
Number of elements (total) |
2 000; Blocks (OB, FB, FC, DB) and UDTs |
|
DB |
|
|
|
1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 |
|
|
1.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
|
FB |
|
|
|
0 ... 65 535 |
|
|
300 kbyte |
|
FC |
|
|
|
0 ... 65 535 |
|
|
300 kbyte |
|
OB |
|
|
|
300 kbyte |
|
|
100 |
|
|
20 |
|
|
20 |
|
|
20; With minimum OB 3x cycle of 500 µs |
|
|
50 |
|
|
3 |
|
|
2 |
|
|
2 |
|
|
100 |
|
|
4 |
|
|
2 |
|
|
1 |
|
Nesting depth |
|
|
|
24 |
|
Counters, timers and their retentivity |
|
|
S7 counter |
|
|
|
2 048 |
|
Retentivity |
|
|
|
Yes |
|
IEC counter |
|
|
|
Any (only limited by the main memory) |
|
Retentivity |
|
|
|
Yes |
|
S7 times |
|
|
|
2 048 |
|
Retentivity |
|
|
|
Yes |
|
IEC timer |
|
|
|
Any (only limited by the main memory) |
|
Retentivity |
|
|
|
Yes |
|
Data areas and their retentivity |
|
|
Retentive data area (incl. timers, counters, flags), max. |
128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB |
|
Extended retentive data area (incl. timers, counters, flags), max. |
1.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF |
|
Flag |
|
|
|
16 kbyte |
|
|
8; 8 clock memory bit, grouped into one clock memory byte |
|
Data blocks |
|
|
|
No |
|
Local data |
|
|
|
64 kbyte; max. 16 KB per block |
|
Address area |
|
|
Number of IO modules |
2 048; max. number of modules / submodules |
|
I/O address area |
|
|
|
32 kbyte; All inputs are in the process image |
|
|
32 kbyte; All outputs are in the process image |
|
per integrated IO subsystem |
|
|
|
8 kbyte |
|
|
8 kbyte |
|
per CM/CP |
|
|
|
8 kbyte |
|
|
8 kbyte |
|
Subprocess images |
|
|
|
32 |
|
Hardware configuration |
|
|
Number of distributed IO systems |
32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) |
|
Number of DP masters |
|
|
|
6; A maximum of 6 CMs (PROFINET + PROFIBUS) can be inserted in total |
|
Number of IO Controllers |
|
|
|
1 |
|
|
6; A maximum of 6 CMs (PROFINET + PROFIBUS) can be inserted in total |
|
Rack |
|
|
|
32; CPU + 31 modules |
|
|
1 |
|
PtP CM |
|
|
|
the number of connectable PtP CMs is only limited by the number of available slots |
|
Time of day |
|
|
Clock |
|
|
|
Hardware clock |
|
|
6 wk; At 40 °C ambient temperature, typically |
|
|
10 s; Typ.: 2 s |
|
Operating hours counter |
|
|
|
16 |
|
Clock synchronization |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Interfaces |
|
|
Number of PROFINET interfaces |
1 |
|
1. Interface |
|
|
Interface types |
|
|
|
2 |
|
|
Yes |
|
|
Yes; X1 |
|
Protocols |
|
|
|
Yes; IPv4 |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes; MRP Automanager according to IEC 62439-2 Edition 2.0 |
|
PROFINET IO Controller |
|
|
Services |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 |
|
|
Yes; Requirement: IRT |
|
|
Yes |
|
|
Yes; Max. 32 PROFINET devices |
|
|
128; In total, up to 512 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET |
|
|
64 |
|
|
128 |
|
|
128 |
|
|
8; in total across all interfaces |
|
|
8 |
|
|
The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
|
Update time for IRT |
|
|
|
250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive |
|
|
500 µs to 8 ms |
|
|
1 ms to 16 ms |
|
|
2 ms to 32 ms |
|
|
4 ms to 64 ms |
|
|
Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) |
|
Update time for RT |
|
|
|
250 µs to 128 ms |
|
|
500 µs to 256 ms |
|
|
1 ms to 512 ms |
|
|
2 ms to 512 ms |
|
|
4 ms to 512 ms |
|
PROFINET IO Device |
|
|
Services |
|
|
|
Yes |
|
|
Yes |
|
|
No |
|
|
Yes |
|
|
Yes |
|
|
Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 |
|
|
Yes; Requirement: IRT |
|
|
Yes |
|
|
Yes |
|
|
4 |
|
|
Yes; Per user program |
|
Interface types |
|
|
RJ 45 (Ethernet) |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Protocols |
|
|
Number of connections |
|
|
|
128; via integrated interfaces of the CPU and connected CPs / CMs |
|
|
10 |
|
|
88 |
|
|
16 |
|
Redundancy mode |
|
|
|
Yes |
|
SIMATIC communication |
|
|
|
Yes |
|
|
Yes |
|
|
See online help (S7 communication, user data size) |
|
Open IE communication |
|
|
|
Yes |
|
|
64 kbyte |
|
|
Yes |
|
|
Yes |
|
|
64 kbyte |
|
|
Yes |
|
|
2 kbyte; 1 472 bytes for UDP broadcast |
|
|
Yes; Max. 5 multicast circuits |
|
|
No |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Web server |
|
|
|
Yes; Standard and user pages |
|
|
Yes; Standard and user pages |
|
OPC UA |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
|
|
"anonymous" or by user name & password |
|
|
4 |
|
|
1 000 |
|
|
300 |
|
|
20 |
|
|
100 |
|
|
1 |
|
|
5 |
|
|
5 000 |
|
|
100 |
|
|
20 |
|
|
Yes; Data access (read, write, subscribe), method call, custom address space |
|
|
Yes |
|
|
Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
|
|
"anonymous" or by user name & password |
|
|
32 |
|
|
50 000 |
|
|
10 000 |
|
|
20 |
|
|
100 ms |
|
|
500 ms |
|
|
20 |
|
|
20 |
|
|
1 000; For 1 s sampling interval and 1 s send interval |
|
|
10 |
|
|
1 000 |
|
Further protocols |
|
|
|
Yes; MODBUS TCP |
|
Media redundancy |
|
|
|
200 ms; For MRP, bumpless for MRPD |
|
|
50 |
|
Isochronous mode |
|
|
Isochronous operation (application synchronized up to terminal) |
Yes; Distributed and central; with minimum OB 6x cycle of 500 µs (distributed) and 1 ms (central) |
|
Equidistance |
Yes |
|
S7 message functions |
|
|
Number of login stations for message functions, max. |
32 |
|
Program alarms |
Yes |
|
Number of configurable program messages, max. |
5 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH |
|
Number of loadable program messages in RUN, max. |
2 500 |
|
Number of simultaneously active program alarms |
|
|
|
300 |
|
|
100 |
|
|
80 |
|
Test commissioning functions |
|
|
Joint commission (Team Engineering) |
Yes; Parallel online access possible for up to 5 engineering systems |
|
Status block |
Yes; Up to 8 simultaneously (in total across all ES clients) |
|
Single step |
No |
|
Number of breakpoints |
8 |
|
Status/control |
|
|
|
Yes |
|
|
Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
|
|
|
|
|
200; per job |
|
|
200; per job |
|
Forcing |
|
|
|
Peripheral inputs/outputs |
|
|
200 |
|
Diagnostic buffer |
|
|
|
Yes |
|
|
1 000 |
|
|
500 |
|
Traces |
|
|
|
4; Up to 512 KB of data per trace are possible |
|
Interrupts/diagnostics/status information |
|
|
Diagnostics indication LED |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Supported technology objects |
|
|
Motion Control |
Yes; Note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER |
|
|
800 |
|
|
|
|
|
40 |
|
|
80 |
|
|
160 |
|
|
80 |
|
|
20 |
|
|
160 |
|
|
40 |
|
|
|
|
|
5 |
|
|
10 |
|
Controller |
|
|
|
Yes; Universal PID controller with integrated optimization |
|
|
Yes; PID controller with integrated optimization for valves |
|
|
Yes; PID controller with integrated optimization for temperature |
|
Counting and measuring |
|
|
|
Yes |
|
Ambient conditions |
|
|
Ambient temperature during operation |
|
|
|
0 °C |
|
|
60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off |
|
|
0 °C |
|
|
40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off |
|
Ambient temperature during storage/transportation |
|
|
|
-40 °C |
|
|
70 °C |
|
Configuration |
|
|
Programming |
|
|
Programming language |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Know-how protection |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Access protection |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Cycle time monitoring |
|
|
|
adjustable minimum cycle time |
|
|
adjustable maximum cycle time |
|
Dimensions |
|
|
Width |
35 mm |
|
Height |
147 mm |
|
Depth |
129 mm |
|
Weights |
|
|
Weight, approx. |
405 g |