| Width | 70 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 73 mm |
| Degree of protection | IP20 |
|---|---|
| Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
| Ambient temperature (operation) | -40 °C ... 75 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, observe derating) |
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| 110 V DC ... 250 V DC -18 % ... +40 % | |
| Dielectric strength maximum | 300 V AC 60 s |
| Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 % |
| 16.7 Hz (acc. to EN 50163) | |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 6.8 A (100 V AC) |
| 5.5 A (120 V AC) | |
| 2.8 A (230 V AC) | |
| 2.7 A (240 V AC) | |
| Nominal power consumption | 520 VA |
| Inrush current | typ. 10 A (at 25 °C) |
| Mains buffering time | typ. 36 ms (120 V AC) |
| typ. 36 ms (230 V AC) | |
| Input fuse | 12 A (slow-blow, internal) |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
| Nominal output voltage | 24 V DC |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (constant capacity) |
| Nominal output current (IN) | 20 A |
| Static Boost (IStat.Boost) | 25 A |
| Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
| Selective Fuse Breaking (ISFB) | 120 A (15 ms) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | < 30 V DC (double protection incl. shutdown) |
| Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
| < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
| < 0.25 % (change in input voltage ±10 %) | |
| Residual ripple | < 30 mVPP (with nominal values) |
| Output power | 480 W |
| Typical response time | 300 ms (from SLEEP MODE) |
| Maximum power dissipation in no-load condition | < 5 W (120 V AC) |
| < 5 W (230 V AC) | |
| Power loss nominal load max. | < 38 W (120 V AC) |
| < 30 W (230 V AC) |
| Net weight | 1.3 kg |
|---|---|
| Efficiency | typ. 92.7 % (120 V AC) |
| typ. 94.2 % (230 V AC) | |
| MTBF (IEC 61709, SN 29500) | > 868000 h (25 °C) |
| > 524000 h (40 °C) | |
| > 239000 h (60 °C) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Degree of protection | IP20 |
| Protection class | I |
| Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | Alignable: horizontally 0 mm at Pout <50% PN, 5 mm at Pout ≥50% PN, next to active components 15 mm, vertically 50 mm |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 30 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| EMC requirements for noise immunity | EN 61000-6-1 |
|---|---|
| EN 61000-6-2 | |
| EMC requirements for noise emission | EN 61000-6-3 |
| EN 61000-6-4 | |
| EMC requirements, power plant | IEC 61850-3 |
| EN 61000-6-5 | |
| HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
| Standard - Safety of transformers | EN 61558-2-16 |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) |
| EN 60204-1 (PELV) | |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Explosive atmosphere | IEC 60079-0 |
| Mains variation/undervoltage | SEMI F47-0706; EN 61000-4-11 |
| Rail applications | EN 50121-3-2 |
| EN 50121-4 | |
| EN 50121-5 | |
| EN 50163 | |
| IEC 62236-3-2 | |
| IEC 62236-4 | |
| IEC 62236-5 |
| UL approvals | UL Listed UL 508 |
|---|---|
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| CSA | CAN/CSA-C22.2 No. 60950-1-07 |
| CSA-C22.2 No. 107.1-01 | |
| SIQ | BG (type approved) |
| Shipbuilding approval | DNV GL applied for |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Harmonic currents | EN 61000-3-2 |
| EN 61000-3-2 (Class A) | |
| Flicker | EN 61000-3-3 |
| EN 61000-3-3 | |
| DNV GL conducted interference | Class A |
| Additional text | Area power distribution |
| DNV GL noise radiation | Class B |
| Additional text | Bridge and deck area |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 8 kV (Test Level 4) |
| Discharge in air | 15 kV (Test Level 4) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 20 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 6 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Output | 4 kV (Test Level 4 - asymmetrical) |
| Signal | 4 kV (Test Level 4 - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | EN 61000-4-5 |
| Input | typ. 3 kV (Test Level 4 - symmetrical) |
| typ. 6 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) | |
| Signal | 4 kV (Test Level 4 - asymmetrical) |
| Comments | Criterion A |
| I/O/S | asymmetrical |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Frequency | 16.7 Hz |
| 50 Hz | |
| 60 Hz | |
| Test field strength | 100 A/m |
| Additional text | 60 s |
| Comments | Criterion A |
| Frequency | 50 Hz |
| 60 Hz | |
| Test field strength | 1 kA/m |
| Additional text | 3 s |
| Frequency | 0 Hz |
| Test field strength | 300 A/m |
| Additional text | DC, 60 s |
| Voltage dips | EN 61000-4-11 |
| Voltage | 230 V AC |
| Frequency | 50 Hz |
| Voltage dip | 70 % |
| Number of periods | 0.5 / 1 / 25 / 30 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A: 0.5 / 1 / 25 / 30 periods |
| Voltage dip | 40 % |
| Number of periods | 5 / 10 / 50 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A |
| Voltage dip | 0 % |
| Number of periods | 0,5 / 1 / 5 / 50 / 250 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods |
| Pulse-shape magnetic field | EN 61000-4-9 |
| Test field strength | 1000 A/m |
| Comments | Criterion A |
| Damped oscillating magnetic field | EN 61000-4-10 |
| Test field strength | 110 A/m |
| Test level 1 | 100 kHz |
| Test field strength | 110 A/m |
| Test level 2 | 1 MHz |
| Comments | Criterion A |
| Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
| Input | 2 kV (Test Level 4 - symmetrical) |
| 4 kV (Test Level 4 - asymmetrical) | |
| Comments | Criterion A |
| Asymmetrical conducted disturbance variables | EN 61000-4-16 |
| Test level 1 | 15 Hz 150 Hz (Test Level 4) |
| Voltage | 30 V 3 V |
| Test level 2 | 150 Hz 1.5 kHz (Test Level 4) |
| Voltage | 3 V |
| Test level 3 | 1.5 kHz 15 kHz (Test Level 4) |
| Voltage | 3 V 30 V |
| Test level 4 | 15 kHz 150 kHz (Test Level 4) |
| Voltage | 30 V |
| Test level 5 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
| Voltage | 30 V (Permanent) |
| Test level 6 | 150 Hz 180 Hz (Test Level 4) |
| Voltage | 30 V (Permanent) |
| Test level 7 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
| Voltage | 300 V (1 s) |
| Comments | Criterion A |
| Attenuated oscillating wave | EN 61000-4-18 |
| Input, output (test level 1) | 100 kHz 1 MHz (Test Level 3 - symmetrical) |
| Voltage | 1 kV |
| Input, output (test level 2) | 10 MHz |
| Voltage | 1 kV |
| Input, output (test level 3) | 100 kHz 1 MHz (Test Level 3 - asymmetrical) |
| Voltage | 2.5 kV |
| Signals (test level 1) | 100 kHz 1 MHz (Test Level 3 - symmetrical) |
| Voltage | 1 kV |
| Signals (test level 2) | 100 kHz 1 MHz (Test Level 3 - asymmetrical) |
| Voltage | 2.5 kV |
| Comments | Criterion A |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| REACh SVHC | Lead 7439-92-1 |
|---|
| eCl@ss 10.0.1 | 27040701 |
|---|---|
| eCl@ss 6.0 | 27049000 |
| eCl@ss 7.0 | 27049002 |
| eCl@ss 8.0 | 27049002 |
| eCl@ss 9.0 | 27040701 |
| ETIM 5.0 | EC002540 |
|---|---|
| ETIM 6.0 | EC002540 |
| ETIM 7.0 | EC002540 |
Siemens 6EP3310-6SB00-0AY0 | LOGO!POWER 5 V / 3 A Stabilized power supply -BộGiá tốt nhất xem...0909186879 Email
Siemens 6EP3333-7LB00-0AX0 | SITOP PSU6200 3.7 A NEC class II -Bộ nguồnGiá tốt nhất xem...0909186879 Email
Bộ nguồn Phoenix Contact UNO-PS/1AC/24DC/240W - 2904372 | 1-phase 24VDC 240WGiá tốt nhất xem...0909186879 Email
Bộ nguồn Phoenix Contact STEP-PS/ 1AC/24DC/0.5 - 2868596 | 1-phase 24VDC 0.5AGiá tốt nhất xem...0909186879 Email
Bộ nguồn Phoenix Contact STEP-PS/ 1AC/24DC/4.2 - 2868664 | 1-phase 24VDC 0.5AGiá tốt nhất xem...0909186879 Email
Bộ nguồn Phoenix Contact TRIO-PS/1AC/24DC/20 - 2866381 | 1AC 24VDC 20AGiá tốt nhất Xem...0909186879 Email
Bộ nguồn Phoenix Contact TRIO-PS/1AC/24DC/10 - 2866323 | 1AC 24VDC 10A Giá tốt nhất Xem...0909186879 Email
Bộ nguồn Phoenix Contact TRIO-PS/1AC/24DC/ 5 - 2866310 | 1P 24VDC 5AGiá tốt nhất Xem...0909186879 Email
Bộ nguồn 24vDC 10A 1AC 120/230V - Siemens - SITOP PSU100S 24 V/10 A - 6EP1334-2BA20Giá tốt nhất Xem...0909186879 Email
Bộ nguồn Siemens 6EP1336-2BA10 | SITOP PSU100S 20A | 120/230VAC 24VDC 20AGiá tốt nhất Xem...0909186879 Email
Bộ nguồn 24vDC-60W Phoenix Contact Power supply unit - UNO-PS/1AC/24DC/ 60W - 2902992Giá tốt nhất Xem...0909186879 Email
Module chuyển đổi nguồn dự phòng Redundancy module 24vDC 20A - Siemens - 6EP1961-3BA21Giá tốt nhất Xem...0909186879 Email
Bộ nguồn Siemens 6EP1333-2BA20 | SITOP PSU100S 24 V/5 A | 120/230VAC 24VDC 5AGiá tốt nhất Xem...0909186879 Email
Bộ nguồn 24vDC-100W Phoenix Contact Power supply unit - UNO-PS/1AC/24DC/100W - 2902993Giá tốt nhất Xem...0909186879 Email