Bộ nguồn UNO 1AC 24VDC 240W Phoenix Contact UNO-PS/1AC/24DC/240W - 2904372
=> Đã ngưng sản xuất, và
được thay thế bằng model
UNO2-PS/1AC/24DC/240W - 1096432
Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 10 A, Adjustable from 24 V DC ... 28 V DC
Vui lòng xem Thông số kỹ thuật bên dười:
Bộ nguồn UNO2 1AC 24...48VDC 240W Phoenix Contact UNO2-PS/1AC/24DC/240W - 1096432
Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 10 A, Adjustable from 24 V DC ... 28 V DC
Technical data
Input data
AC operation |
Supply system configuration |
Star network (TN, TT, IT (PE)) |
Nominal input voltage range |
100 V AC ... 240 V AC |
Input voltage range |
100 V AC ... 240 V AC -15 % ... +10 % |
Derating |
< 90 V AC (1 %/V) |
Typical national grid voltage |
120 V AC |
230 V AC |
Voltage type of supply voltage |
AC |
Inrush current |
typ. 10 A (at 25 °C) |
Inrush current integral (I2t) |
< 0.2 A2s |
Frequency range (fN) |
50 Hz ... 60 Hz ±10 % |
Mains buffering time |
typ. 16 ms (120 V AC) |
typ. 20 ms (230 V AC) |
Current consumption |
2.6 A (100 V AC) |
2.2 A (120 V AC) |
1.13 A (230 V AC) |
1.2 A (240 V AC) |
Protective circuit |
Transient surge protection; Varistor, gas-filled surge arrester |
Switch-on time |
typ. 400 ms |
Device mains fuse |
5 A internal (device protection), fast-blow |
Recommended breaker for input protection |
6 A ... 16 A (Characteristic B, C, D, K or comparable) |
Discharge current to PE |
< 3.5 mA |
Output data
Efficiency |
typ. 92 % (120 V AC) |
typ. 94 % (230 V AC) |
Nominal output voltage |
24 V DC |
Setting range of the output voltage (USet) |
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
10 A |
Short-circuit-proof |
yes |
No-load proof |
yes |
Crest factor |
typ. 1.65 (120 V AC) |
typ. 1.63 (230 V AC) |
Output power (PN) |
240 W |
Connection in parallel |
yes, for redundancy |
Connection in series |
yes, for increased output voltage |
Feedback voltage resistance |
≤ 35 V DC |
Protection against overvoltage at the output (OVP) |
≤ 35 V DC |
Residual ripple |
typ. 50 mVPP (with nominal values) |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
< 3 % (change in load, dynamic 10 % ... 90 %) |
< 0.1 % (change in input voltage ±10 %) |
Rise time |
< 1 s (UOut = 10 % ... 90 %) |
Minimum no-load power dissipation |
< 4 W (120 V AC) |
Maximum no-load power dissipation |
< 4 W (230 V AC) |
Minimum nominal load power dissipation |
< 21 W (120 V AC) |
Power loss nominal load max. |
< 16 W (230 V AC) |
Signal relay 13/14 |
Connection level |
3.x |
Connection labeling |
3.1 (13), 3.2 (14) |
Switch contact (floating) |
OptoMOS |
Switching voltage |
max. 30 V AC/DC |
max. 60 V DC |
Current carrying capacity |
max. 50 mA |
State condition |
UOUT > 0,9 x UN (Contact closed) |
UOUT < 0,9 x UN (Contact open) |
Connection data
Input |
Position |
1.x |
Identification |
1.1 (), 1.2 (L), 1.3 (N) |
Conductor connection |
Connection method |
Screw connection |
rigid |
0.2 mm² ... 2.5 mm² |
flexible |
0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve |
0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve |
0.25 mm² ... 2.5 mm² |
rigid (AWG) |
24 ... 14 (Cu) |
Stripping length |
6.5 mm |
Tightening torque |
0.5 Nm ... 0.6 Nm |
4 lbf-in. ... 5 lbf-in. |
Drive form screw head |
Slotted L |
Output |
Position |
2.x |
Identification |
2.1, 2.2 (+), 2.3, 2.4 (-) |
Conductor connection |
Connection method |
Screw connection |
rigid |
0.2 mm² ... 2.5 mm² |
flexible |
0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve |
0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve |
0.25 mm² ... 2.5 mm² |
rigid (AWG) |
24 ... 14 (Cu) |
Stripping length |
6.5 mm |
Tightening torque |
0.5 Nm ... 0.6 Nm |
4 lbf-in. ... 5 lbf-in. |
Drive form screw head |
Slotted L |
Signal |
Position |
3.x |
Identification |
3.1 (13), 3.2 (14) |
Conductor connection |
Connection method |
Screw connection |
rigid |
0.2 mm² ... 2.5 mm² |
flexible |
0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve |
0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve |
0.25 mm² ... 2.5 mm² |
rigid (AWG) |
24 ... 14 (Cu) |
Stripping length |
6.5 mm |
Tightening torque |
0.5 Nm ... 0.6 Nm |
4 lbf-in. ... 5 lbf-in. |
Drive form screw head |
Slotted L |
Signaling
LED signaling |
Types of signaling |
LED DC OK – signal state operation (UN = 24 V DC, IOut = IN) |
Function |
Visual operating state display |
Color |
green |
LED off |
Supply voltage input AC not present (Off) |
LED on (green), DC OK |
UOUT > 0,9 x UN (On (green), DC OK) |
LED on (flashing green) DC OK < 0.9 x UN |
UOUT < 0,9 x UN (on (flashing green)) |
Electrical properties
Number of phases |
1.00 |
Insulation voltage input/output |
4 kV AC (type test) |
3 kV AC (routine test) |
Insulation voltage input / PE |
3.5 kV AC (type test) |
2.4 kV AC (routine test) |
Product properties
Product type |
Power supply |
Product family |
UNO POWER |
MTBF (IEC 61709, SN 29500) |
> 1219000 h (25 °C) |
> 678000 h (40 °C) |
> 366000 h (55 °C) |
Environmental protection directive |
RoHS Directive 2011/65/EU |
WEEE |
Reach |
Insulation characteristics |
Protection class |
I |
Degree of pollution |
2 |
Dimensions
Item dimensions |
Width |
45 mm |
Height |
130 mm |
Depth |
129 mm |
125 mm (Device depth (DIN rail mounting)) |
Installation dimensions |
Installation distance right/left (active, passive) |
0 mm / 0 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) |
30 mm / 30 mm (POut ≥50% ) |
Mounting
Mounting type |
DIN rail mounting |
Assembly instructions |
alignable: 0 mm horizontally, 30 mm vertically |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
With protective coating |
No |
Material specifications
Flammability rating according to UL 94 |
V0 (Housing, terminal blocks) |
Housing material |
Metal |
Hood version |
Stainless steel |
Side element version |
Aluminum |
Foot latch material |
Sheet steel, zinc-plated |
Housing material |
Aluminum (AlMg3) / sheet steel, zinc-plated |
Environmental and real-life conditions
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Ambient temperature (start-up type tested) |
-40 °C |
Maximum altitude |
≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Shock (operation) |
18 ms, 30g, per spatial direction (IEC 60068-2-27) |
Vibration (operation) |
10 Hz ... 50 Hz, amplitude ±0.2 mm |
50 Hz to 150 Hz, 2.3 g, 90 min. |
Standards and regulations
Overvoltage category |
EN 61010-1 |
II (≤ 3000 m) |
Overvoltage category |
EN 62477-1 |
III (≤3000 m) |
Safety of power supply units up to 1100 V (insulation distances) |
Standard designation |
Safety of power supply units up to 1100 V (insulation distances) |
Standards/specifications |
DIN EN 61558-2-16 |
Electrical safety |
Standard designation |
Electrical safety |
Standards/specifications |
IEC 61010-2-201 (SELV) |
Electronic equipment for use in power installations |
Standard designation |
Equipping high voltage installations with electronic equipment |
Standards/specifications |
EN 50178/VDE 0160 (PELV) |
Safety for measurement, control, and laboratory equipment |
Standard designation |
Safety for equipment for measurement, control, and laboratory use |
Standards/specifications |
IEC 61010-1 |
Protective extra-low voltage |
Standard designation |
Protective extra-low voltage |
Standards/specifications |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
Safe isolation |
Standard designation |
Safe isolation |
Standards/specifications |
IEC 61558-2-16 |
IEC 61010-2-201 |
Limitation of harmonic line currents |
Standard designation |
Limitation of harmonic line currents |
Standards/specifications |
EN 61000-3-2 |
Mains voltage dips |
Standard designation |
Requirement of the semiconductor industry with regard to mains voltage dips |
Standards/specifications |
SEMI F47 - 0706 (185 V AC) |
Approvals
UL |
Identification |
UL/C-UL Listed UL 61010-1 |
UL |
Identification |
UL/C-UL Listed UL 61010-2-201 |
UL |
Identification |
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
SIQ |
Identification |
CB scheme (IEC 61010-1, IEC 61010-2-201) |
EMC data
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Interference emission |
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
EMC requirements for noise immunity |
EN 61000-6-2 |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Conducted noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Noise emission |
EN 55016 |
EN 61000-6-3 (Class B) |
Harmonic currents |
Standards/regulations |
EN 61000-3-2 |
EN 61000-3-2 (Class A) |
Frequency range |
0 kHz ... 2 kHz |
Flicker |
Standards/regulations |
EN 61000-3-3 |
Frequency range |
0 kHz ... 2 kHz |
Electrostatic discharge |
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge |
Contact discharge |
6 kV (Test Level 3) |
Discharge in air |
8 kV (Test Level 3) |
Comments |
Criterion A |
Electromagnetic HF field |
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
1 GHz ... 6 GHz |
Test field strength |
10 V/m (Test Level 3) |
Comments |
Criterion A |
Fast transients (burst) |
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst) |
Input |
4 kV (Test Level 4 - asymmetrical) |
Output |
2 kV (Test Level 3 - asymmetrical) |
Comments |
Criterion A |
Surge voltage load (surge) |
Standards/regulations |
EN 61000-4-5 |
Input |
2 kV (Test Level 4 - symmetrical) |
4 kV (Test Level 4 - asymmetrical) |
Output |
1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) |
Comments |
Criterion A |
Conducted interference |
Standards/regulations |
EN 61000-4-6 |
Conducted interference |
Input/Output |
asymmetrical |
Frequency range |
0.15 MHz ... 80 MHz |
Comments |
Criterion A |
Voltage |
10 V (Test Level 3) |
Voltage dips |
Standards/regulations |
EN 61000-4-11 |
Voltage |
230 V AC |
Frequency |
50 Hz |
Voltage dip |
70 % |
Number of periods |
25 / 30 periods |
Comments |
Criterion A |
Voltage dip |
40 % |
Number of periods |
12 periods |
Additional text |
Test Level 2 |
Comments |
Criterion A |
Voltage dip |
0 % |
Number of periods |
1 period |
Additional text |
Test Level 2 |
Comments |
Criterion B |
Criteria |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Commercial data
Item number |
1096432 |
Packing unit |
1 pc |
Minimum order quantity |
1 pc |
Sales key |
CM15 |
Product key |
CMPV13 |
GTIN |
4055626930466 |
Weight per piece (including packing) |
862 g |
Weight per piece (excluding packing) |
862 g |
Customs tariff number |
85044095 |
Country of origin |
TH |
Classifications
ECLASS
ECLASS-11.0 |
27040701 |
ECLASS-12.0 |
27040701 |
ECLASS-13.0 |
27040701 |
ETIM
UNSPSC
Approvals
cULus Listed
Approval ID: FILE E 123528
EAC
Approval ID: RU S-DE.BL08.W.00764
EAC
Approval ID: RU S-DE.BL08.W.00764
cULus Listed
Approval ID: FILE E 199827
Environmental product compliance
|
REACh SVHC |
Lead 7439-92-1 |
|
China RoHS |
Environmentally Friendly Use Period = 25; |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
- Tài liệu kỹ thuật Phoenix Contact UNO2PS/1AC/24DC/240W - 1096432