Nominal voltage | 110V, 120V, 208V, 220V, 230V, 240V, 277V, 380V, 400V, 415V, 440V, 480V |
Nominal frequency | 50, 60 or 400Hz |
Voltage burden | 3VA approx. |
Overload | 1.2 x rating continuosly, 1.5 x rating for 10 x seconds to symmetric |
Trip level adjustment | Pre-set at 85% of nominal |
Auxiliaty voltage burden | 4VA (max) |
Output relay | 2-pole change over |
Relay contact rating | AC:240V 5A, non inductive DC: 24V 5A resistive |
Relay mechanical life | 0.2 milion operations at rated loads |
Relay reset | Automatic |
Operating temperature | 0oC to +60oC (0oC to +40oC for UL models) |
Storage temperature | -20oC to +70oC |
Temperature co-efficient | 0.05% per oC |
Interference immunity | Electrical stress surge withstand and non-function to ANSI/IEEE C37 90a |
Enclosure style | DIN-rail with wall mounting facility |
Material | Flame retardent polycarbonate/ABS |
Enclosure integrity | IP50 |
Dimensions | 55mm x 70mm x 112mm (WxHxD) |
Weight | 0.4kg approx. |