range of product | EasyPact MVS |
range | EasyPact |
product name | MVS10N |
device short name | MVS10N |
product or component type | Circuit breaker |
device application | Distribution |
poles description | 3P |
protected poles description | 3P 3d |
network type | AC |
breaking capacity code | N |
suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category B |
trip unit name | ET2I |
trip unit technology | Electronic |
trip unit rating | 1000 A |
network frequency | 50/60 Hz |
control type | Manually operated |
mounting mode | Fixed |
mounting support | Rail Base plate |
connection position | Vertical Horizontal |
location of connection | Rear |
[In] rated current | 1000 A (40 °C) |
[Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
circuit breaker CT rating | 1000 A |
breaking capacity | 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
electrical durability | 6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2 |
connection pitch | 115 mm (without spreader) |
contact position indicator | Yes |
[Icm] rated short-circuit making capacity | 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
[Icw] rated short-time withstand current | 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
trip unit protection functions | LI |
protection type | Instantaneous short-circuit protection Overload protection (long time) |
fault indication | Internal fault Short-circuit Overload |
long time pick-up adjstment type Ir | Adjustable 9 settings |
long time pick-up adjustment range | 0.4...1 x In |
long time delay adjustment type | Adjustable 9 settings |
[tr] long-time delay adjustment range | 0.5...24 s (6 x Ir) |
thermal memory | 20 minutes before and after tripping |
instantaneous pick-up adjustment type Ii | Adjustable 9 settings |
instantaneous pick-up adjustment range | 1.5...10 x Ir |
zone selective interlocking ZSI | With |
current sensor rating range | 400/2000 A |
maximum breaking time | 25 ms |
closing response time | < 70 ms |
height | 352 mm |
width | 422 mm |
depth | 297 mm |
product weight | 40 kg |
standards | IEC 60947-2 |
product certifications | IEC CCC GOST CCS |
IP degree of protection | IP40 |
pollution degree | 4 conforming to IEC 60664-1 |
ambient air temperature for operation | -5...70 °C |
ambient air temperature for storage | -40...85 °C (without control unit) -25...85 °C (with control unit) |
Sustainable offer status | Not Green Premium product |
RoHS (date code: YYWW) | Will be compliant on 2Q2016 |
REACh | Reference not containing SVHC above the threshold |
Product environmental profile | Available Product environmental |
Product end of life instructions | Available End of life manual |
Warranty period | 18 months |