Number of levels |
1 |
Number of connections |
2 |
Potentials |
1 |
Nominal cross section |
10 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Area of application |
Railway industry |
|
Machine building |
|
Plant engineering |
|
Process industry |
Rated surge voltage |
8 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Maximum power dissipation for nominal condition |
1.82 W |
Maximum load current |
65 A (with 16 mm² conductor cross section) |
Nominal current IN |
57 A |
Nominal voltage UN |
1000 V |
Open side panel |
Yes |
Ambient temperature (operation) |
-60 °C ... 85 °C |
Ambient temperature (storage/transport) |
-25 °C ... 55 °C (For a short time, not exceeding 24 h, -60 to +70 °C) |
Permissible humidity (storage/transport) |
30 % ... 70 % |
Ambient temperature (assembly) |
-5 °C ... 70 °C |
Ambient temperature (actuation) |
-5 °C ... 70 °C |
Shock protection test specification |
DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Result of surge voltage test |
Test passed |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
2.2 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of bending test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
0.2 mm² / 0.2 kg |
|
10 mm² / 2 kg |
|
16 mm² / 2.9 kg |
Tensile test result |
Test passed |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 35 |
Setpoint |
5 N |
Result of voltage-drop test |
Test passed |
Result of temperature-rise test |
Test passed |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
10 mm² |
Short-time current |
1.2 kA |
Result of thermal test |
Test passed |
Ageing test for screwless modular terminal block temperature cycles |
192 |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Result of aging test |
Test passed |
Oscillation, broadband noise test result |
Test passed |
Test specification, oscillation, broadband noise |
DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum |
Service life test category 1, class B, body mounted |
Test frequency |
f1 = 5 Hz to f2 = 150 Hz |
ASD level |
1.857 (m/s2)2/Hz |
Acceleration |
0,8 g |
Test duration per axis |
5 h |
Test directions |
X-, Y- and Z-axis |
Shock test result |
Test passed |
Test specification, shock test |
DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form |
Half-sine |
Acceleration |
5g |
Shock duration |
30 ms |
Number of shocks per direction |
3 |
Test directions |
X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
125 °C |
Static insulating material application in cold |
-60 °C |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
27,5 MJ/kg |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |