Note | The current is determined by the fuse used, the voltage by the selected LED. If the fuse is faulty, the downstream circuit will not be disconnected. |
---|---|
Number of levels | 1 |
Number of connections | 2 |
Nominal cross section | 4 mm² |
Color | black |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Area of application | Railway industry |
Machine building | |
Plant engineering | |
Maximum power dissipation for nominal condition | 1.6 W |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation | max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload) |
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) | |
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit) | |
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit) | |
LED voltage range | 12 V AC/DC ... 30 V AC/DC |
LED current range | 0.31 mA ... 0.95 mA |
Connection in acc. with standard | IEC 60947-7-3 |
Maximum load current | 6.3 A (the current is determined by the fuse used) |
Nominal current IN | 6.3 A |
Nominal voltage UN | 24 V |
Fuse | G / 5 x 20 |
Fuse type | Glass / ceramics / ... |
Open side panel | No |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Static insulating material application in cold | -60 °C |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Width | 6.2 mm |
---|---|
Length | 57.8 mm |
Height NS 35/7,5 | 73 mm |
Height NS 35/15 | 80.5 mm |
Conductor cross section solid min. | 0.14 mm² |
---|---|
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 6 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 10 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
2 conductors with same cross section, solid min. | 0.14 mm² |
2 conductors with same cross section, solid max. | 1.5 mm² |
2 conductors with same cross section, stranded min. | 0.14 mm² |
2 conductors with same cross section, stranded max. | 1.5 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum | 0.14 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum | 1.5 mm² |
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum | 0.5 mm² |
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum | 2.5 mm² |
Connection method | Screw connection |
Stripping length | 9 mm |
Internal cylindrical gage | A4 |
Screw thread | M3 |
Tightening torque, min | 0.6 Nm |
Tightening torque max | 0.8 Nm |
Operating temperature | -60 °C ... 105 °C (max. short-term operating temperature 130°C) |
---|---|
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-3 | |
Flammability rating according to UL 94 | V0 |
China RoHS | Environmentally Friendly Use Period = 50 years |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
ECLASS 10.0.1 | 27141116 |
---|---|
ECLASS 11.0 | 27141116 |
ECLASS 4.0 | 27141100 |
ECLASS 4.1 | 27141100 |
ECLASS 5.0 | 27141100 |
ECLASS 5.1 | 27141100 |
ECLASS 6.0 | 27141100 |
ECLASS 7.0 | 27141116 |
ECLASS 9.0 | 27141116 |
ETIM 2.0 | EC000897 |
---|---|
ETIM 3.0 | EC000899 |
ETIM 4.0 | EC000899 |
ETIM 6.0 | EC000899 |
ETIM 7.0 | EC000899 |
UNSPSC 6.01 | 30211811 |
---|---|
UNSPSC 7.0901 | 39121410 |
UNSPSC 11 | 39121410 |
UNSPSC 12.01 | 39121410 |
UNSPSC 13.2 | 39121410 |
UNSPSC 18.0 | 39121410 |
UNSPSC 19.0 | 39121410 |
UNSPSC 20.0 | 39121410 |
UNSPSC 21.0 | 39121410 |