Product characteristics/function |
Performance features/benefits |
Automatic parameterization |
Extremely easy commissioning and reliability even under changing load conditions |
Hybrid switching devices and three-phase motor control |
Minimum power loss and optimum/symmetrical motor control |
Integration into TIA Portal – communication modules optional |
Efficient configuration and maximum flexibility in automation engineering |
Detachable HMI with color display, local interface, slot for micro SD card |
Maximum flexibility with regard to user interface and intuitive menu guidance |
Pump stop and torque control |
Reduced mechanical loading and optimum pump stop control |
Certified according to ATEX/IECEx directives |
Suitable for the starting of explosion-proof motors |
Fail-safe disconnection up to SIL 3/PL e – STO |
Reduced costs and space requirements thanks to direct wiring of the EMERGENCY STOP mushroom pushbutton to the soft starter for SIL 1 |
ype |
|
3RW5513 |
3RW5514 |
3RW5515 |
3RW5516 |
3RW5517 |
---|---|---|---|---|---|---|
Rated operational current Ie |
A |
13 |
18 |
25 |
32 |
38 |
Power electronics |
||||||
Load rating rated operational current Ie |
|
|
||||
IEC + UL/CSA individual mounting at 40/50/60 °C, AC‑53a |
A |
13/11.5/10.5 |
18/15.9/13.8 |
25/22.3/19.6 |
25/22.3/19.6 |
38/33.5/30.5 |
Permissible rated motor current and starts/h |
||||||
Normal starting (CLASS 10A) |
|
|
||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
13/11.5/10.5 |
18/15.9/13.8 |
25/22.3/19.6 |
32/28.4/26 |
38/33.5/30.5 |
|
|
|
||||
|
1/h |
43 |
43 |
43 |
43 |
43 |
|
1/h |
18 |
18 |
18 |
18 |
18 |
|
|
|
||||
|
1/h |
28 |
28 |
28 |
28 |
28 |
|
1/h |
10 |
10 |
10 |
10 |
10 |
Normal starting (CLASS 10E) |
|
|
||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
13/11.5/10.5 |
18/15.9/13.8 |
25/22.3/19.6 |
32/28.4/26 |
38/33.5/30.5 |
|
|
|
||||
|
1/h |
21 |
21 |
21 |
21 |
21 |
|
1/h |
8 |
8 |
8 |
8 |
8 |
|
|
|
||||
|
1/h |
13 |
13 |
13 |
13 |
13 |
|
1/h |
4 |
4 |
4 |
4 |
4 |
Heavy startup (CLASS 20E) |
|
|
||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
13/11.5/10.5 |
18/15.9/13.8 |
25/22.3/19.6 |
29.6/27.2/23.6 |
33.5/30.5/27.5 |
|
|
|
||||
|
1/h |
10 |
10 |
10 |
10 |
10 |
|
1/h |
4 |
4 |
4 |
4 |
4 |
|
|
|
||||
|
1/h |
7 |
7 |
7 |
7 |
7 |
|
1/h |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
Heavy startup (CLASS 30E) |
|
|
||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
13/11.5/10.5 |
18/15.9/13.8 |
25/22.3/19.6 |
26/23.6/21.2 |
29/26/23 |
|
|
|
||||
|
1/h |
7 |
7 |
7 |
7 |
7 |
|
1/h |
3 |
3 |
3 |
3 |
3 |
|
|
|
||||
|
1/h |
4 |
4 |
4 |
4 |
4 |
|
1/h |
1.8 |
1.8 |
1.8 |
1.8 |
1.8 |
Adjustable rated motor current IM |
|
|
||||
|
A |
2.5/13 |
3.5/18 |
5/25 |
6.5/32 |
7.5/38 |
|
A |
4.3/22.5 |
6.1/31.1 |
8.7/43.3 |
11.3/55.4 |
13/65.8 |
Type |
|
3RW5524 |
3RW5525 |
3RW5526 |
3RW5527 |
---|---|---|---|---|---|
Rated operational current Ie |
A |
47 |
63 |
77 |
93 |
Power electronics |
|||||
Load rating rated operational current Ie |
|||||
IEC + UL/CSA individual mounting at 40/50/60 °C, AC‑53a |
A |
47/41.6/36.2 |
63/55.5/50.5 |
77/68/62 |
93/82.5/75.5 |
Permissible rated motor current and starts/h |
|||||
Normal starting (CLASS 10A) |
|
|
|||
Rated motor current IM; Tu = 40/50/60 °C |
A |
47/41.6/36.2 |
63/55.5/50.5 |
77/68/62 |
93/82.5/75.5 |
|
|
|
|||
|
1/h |
43 |
43 |
43 |
43 |
|
1/h |
18 |
18 |
18 |
18 |
|
|
|
|||
|
1/h |
28 |
28 |
28 |
28 |
|
1/h |
10 |
10 |
10 |
10 |
Normal starting (CLASS 10E) |
|
|
|||
Rated motor current IM; Tu = 40/50/60 °C |
A |
47/41.6/36.2 |
63/55.5/50.5 |
77/68/62 |
93/82.5/75.5 |
|
|
|
|||
|
1/h |
21 |
21 |
21 |
21 |
|
1/h |
8 |
8 |
8 |
8 |
|
|
|
|||
|
1/h |
13 |
13 |
13 |
13 |
|
1/h |
4 |
4 |
4 |
4 |
Heavy startup (CLASS 20E) |
|
|
|||
Rated motor current IM; Tu = 40/50/60 °C |
A |
47/41.6/36.2 |
63/55.5/50.5 |
77/68/62 |
93/82.5/75.5 |
|
|
|
|||
|
1/h |
10 |
10 |
10 |
10 |
|
1/h |
4 |
4 |
4 |
4 |
|
|
|
|||
|
1/h |
7 |
7 |
7 |
7 |
|
1/h |
2.5 |
0 |
0 |
0 |
Heavy startup (CLASS 30E) |
|
|
|||
Rated motor current IM; Tu = 40/50/60 °C |
A |
43.4/38/34.4 |
53/48/43 |
68/62/56 |
82.5/75.5/65 |
|
|
|
|||
|
1/h |
7 |
7 |
7 |
7 |
|
1/h |
3 |
3 |
3 |
3 |
|
|
|
|||
|
1/h |
4 |
4 |
4 |
4 |
|
1/h |
1.8 |
1.8 |
1.8 |
1.8 |
Adjustable rated motor current IM |
|
|
|||
|
A |
10/47 |
13/63 |
16/77 |
19/93 |
|
A |
17.3/81.4 |
22.5/109 |
27.7/133 |
32.9/161 |
Type |
|
3RW5534 |
3RW5535 |
3RW5536 |
---|---|---|---|---|
Rated operational current Ie |
A |
113 |
143 |
171 |
Power electronics |
||||
Load rating rated operational current Ie |
|
|
||
IEC + UL/CSA individual mounting at 40/50/60 °C, AC‑53a |
A |
113/101/89 |
143/128/118 |
171/153/141 |
Permissible rated motor current and starts/h |
||||
Normal starting (CLASS 10A) |
|
|
||
Rated motor current IM; Tu = 40/50/60 °C |
A |
113/101/89 |
143/128/118 |
171/153/141 |
|
|
|
||
|
1/h |
43 |
43 |
35 |
|
1/h |
18 |
18 |
13 |
|
|
|
||
|
1/h |
28 |
17 |
10 |
|
1/h |
10 |
4 |
0 |
Normal starting (CLASS 10E) |
|
|
||
Rated motor current IM; Tu = 40/50/60 °C |
A |
113/101/89 |
143/128/118 |
171/153/141 |
|
|
|
||
|
1/h |
21 |
21 |
14 |
|
1/h |
8 |
7 |
4 |
|
|
|
||
|
1/h |
13 |
4 |
0 |
|
1/h |
4 |
0 |
0 |
Heavy startup (CLASS 20E) |
|
|
||
Rated motor current IM; Tu = 40/50/60 °C |
A |
109/97/85 |
128/113/103 |
141/129/117 |
|
|
|
||
|
1/h |
10 |
10 |
10 |
|
1/h |
4 |
4 |
4 |
|
|
|
||
|
1/h |
7 |
6 |
6 |
|
1/h |
0 |
0 |
0 |
Heavy startup (CLASS 30E) |
|
|
||
Rated motor current IM; Tu = 40/50/60 °C |
A |
89/81/74 |
108/98/88 |
117/105/93 |
|
|
|
||
|
1/h |
7 |
7 |
7 |
|
1/h |
3 |
3 |
3 |
|
|
|
||
|
1/h |
4 |
4 |
4 |
|
1/h |
1.8 |
1.8 |
1.8 |
Adjustable rated motor current IM |
|
|
||
|
A |
23/113 |
29/143 |
34/171 |
|
A |
39.8/195 |
50.2/247 |
58.9/296 |
Type |
|
3RW5543 |
3RW5544 |
3RW5545 |
3RW5546 |
3RW5547 |
3RW5548 |
---|---|---|---|---|---|---|---|
Rated operational current Ie |
A |
210 |
250 |
315 |
370 |
470 |
570 |
Power electronics |
|||||||
Load rating rated operational current Ie |
|
|
|||||
IEC + UL/CSA individual mounting at 40/50/60 °C, AC‑53a |
A |
210/186/170 |
250/220/200 |
315/279/255 |
370/328/300 |
470/416/380 |
570/504/460 |
Permissible rated motor current and starts/h |
|||||||
Normal starting (CLASS 10A) |
|
|
|||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
210/186/170 |
250/220/200 |
315/279/255 |
370/328/300 |
470/416/380 |
570/504/460 |
|
|
|
|||||
|
1/h |
43 |
43 |
38 |
43 |
32 |
13 |
|
1/h |
13 |
18 |
14 |
18 |
13 |
3 |
|
|
|
|||||
|
1/h |
14 |
28 |
19 |
28 |
19 |
4 |
|
1/h |
0 |
10 |
5 |
10 |
6 |
0.4 |
Normal starting (CLASS 10E) |
|
|
|||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
210/186/170 |
250/220/200 |
315/279/255 |
370/328/300 |
470/416/380 |
551/490/445 |
|
|
|
|||||
|
1/h |
13 |
21 |
14 |
20 |
13 |
5 |
|
1/h |
2 |
8 |
4 |
8 |
3 |
-- |
|
|
|
|||||
|
1/h |
0 |
13 |
5 |
12 |
6 |
1 |
|
1/h |
0 |
4 |
0 |
3 |
0.4 |
-- |
Heavy startup (CLASS 20E) |
|
|
|||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
162/146/130 |
200/180/160 |
231/207/183 |
258/230/202 |
272/254/236 |
284/262/240 |
|
|
|
|||||
|
1/h |
10 |
10 |
10 |
10 |
10 |
10 |
|
1/h |
4 |
4 |
4 |
4 |
4 |
4 |
|
|
|
|||||
|
1/h |
7 |
7 |
7 |
7 |
7 |
7 |
|
1/h |
2 |
2.5 |
2.5 |
2.5 |
2.5 |
2.5 |
Heavy startup (CLASS 30E) |
|
|
|||||
Rated motor current IM; Tu = 40/50/60 °C |
A |
138/122/106 |
160/140/120 |
183/159/135 |
202/174/160 |
210/190/170 |
220/200/180 |
|
|
|
|||||
|
1/h |
7 |
7 |
7 |
7 |
7 |
7 |
|
1/h |
3 |
3 |
3 |
3 |
3 |
3 |
|
|||||||
|
1/h |
4 |
4 |
4 |
4 |
4 |
4 |
|
1/h |
1.8 |
1.8 |
1.8 |
1.8 |
1.8 |
1.8 |
Adjustable rated motor current IM |
|
|
|||||
|
A |
42/210 |
50/250 |
63/315 |
74/370 |
94/470 |
114/570 |
|
A |
72.7/363 |
86.6/433 |
109.1/545 |
128.2/640 |
162.8/814 |
197.5/987 |
Type of coordination "1", CLASS 10,
short-circuit breaking capacity Iq in kA, see table
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW5513 |
3RV2032-4TA10 |
65 |
3RV2032-4TA10 |
18 |
3RV2032-4DA10 |
65 |
3RV2032-4DA10 |
18 |
3RW5514 |
3RV2032-4DA10 |
65 |
3RV2032-4DA10 |
15 |
3RV2032-4EA10 |
65 |
3RV2032-4EA10 |
15 |
3RW5515 |
3RV2032-4EA10 |
65 |
3RV2032-4EA10 |
15 |
3RV2032-4VA10 |
65 |
3RV2032-4VA10 |
15 |
3RW5516 |
3RV2032-4VA10 |
65 |
3RV2032-4VA10 |
10 |
3RV2032-4JA10 |
65 |
3RV2032-4JA10 |
10 |
3RW5517 |
3RV2032-4WA10 |
65 |
3RV2032-4WA10 |
10 |
3RV2032-4RA10 |
65 |
3RV2032-4RA10 |
10 |
3RW5524 |
3RV2032-4JA10 |
65 |
3RV2032-4JA10 |
10 |
3RV2032-4RA10 |
65 |
3RV2032-4RA10 |
10 |
3RW5525 |
3VA2163-7MN32-0AA0 |
65 |
3VA2163-7MN32-0AA0 |
20 |
3VA2110-7MN32-0AA0 |
65 |
3VA2110-7MN32-0AA0 |
20 |
3RW5526 |
3VA2110-7MN32-0AA0 |
65 |
3VA2110-7MN32-0AA0 |
20 |
3VA2216-7MN32-0AA0 |
65 |
3VA2216-7MN32-0AA0 |
20 |
3RW5527 |
3VA2216-7MN32-0AA0 |
15 |
3VA2216-7MN32-0AA0 |
10 |
3VA2220-7MN32-0AA0 |
15 |
3VA2220-7MN32-0AA0 |
10 |
3RW5534 |
3VA2216-7MN32-0AA0 |
65 |
-- |
-- |
3VA2220-7MN32-0AA0 |
65 |
-- |
-- |
3RW5535 |
3VA2220-7MN32-0AA0 |
65 |
-- |
-- |
3VA2325-7MN32-0AA0 |
65 |
-- |
-- |
3RW5536 |
3VA2325-7MN32-0AA0 |
30 |
3VA2325-7MN32-0AA0 |
10 |
3VA2440-7MN32-0AA0 |
30 |
3VA2440-7MN32-0AA0 |
10 |
3RW5543 |
3VA2325-7MN32-0AA0 |
65 |
3VA2325-7MN32-0AA0 |
65 |
3VA2440-7MN32-0AA0 |
65 |
3VA2440-7MN32-0AA0 |
65 |
3RW5544 |
3VA2440-7MN32-0AA0 |
65 |
3VA2440-7MN32-0AA0 |
65 |
3VA2450-7MN32-0AA0 |
65 |
3VA2450-7MN32-0AA0 |
65 |
3RW5545 |
3VA2440-7MN32-0AA0 |
65 |
3VA2440-7MN32-0AA0 |
65 |
3VA2580-6HN32-0AA0 |
65 |
3VA2580-6HN32-0AA0 |
65 |
3RW5546 |
3VA2440-7MN32-0AA0 |
65 |
3VA2440-7MN32-0AA0 |
65 |
3VA2580-6HN32-0AA0 |
65 |
3VA2580-6HN32-0AA0 |
65 |
3RW5547 |
3VA2450-7MN32-0AA0 |
65 |
3VA2450-7MN32-0AA0 |
65 |
3VA2510-6HN32-0AA0 |
65 |
3VA2510-6HN32-0AA0 |
65 |
3RW5548 |
3VA2580-6HN32-0AA0 |
65 |
3VA2580-6HN32-0AA0 |
65 |
3VA2510-6HN32-0AA0 |
65 |
3VA2510-6HN32-0AA0 |
65 |
Note:
The service factor or measurement inaccuracies have been taken into account, for example, for the selection of the specified motor starter protectors/circuit breakers; the specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller motor starter protectors/circuit breakers from the same series can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must match the connected three-phase motor, the short-circuit and overload requirements of the application, and the line protection for the cables used.
gG class full-range fuses for cable and line protection
according to IEC 60269‑2, without semiconductor protection
Type of coordination "1",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW5513 |
3NA3820-6 |
3RT2025 |
3NA3820-6 |
3RT2027 |
3RT2025 |
3RW5514 |
3NA3820-6 |
3RT2026 |
3NA3820-6 |
3RT2027 |
3RT2026 |
3RW5515 |
3NA3822-6 |
3RT2027 |
3NA3822-6 |
3RT2036 |
3RT2027 |
3RW5516 |
3NA3824-6 |
3RT2035 |
3NA3824-6 |
3RT2037 |
3RT2035 |
3RW5517 |
3NA3824-6 |
3RT2035 |
3NA3824-6 |
3RT2038 |
3RT2035 |
3RW5524 |
3NA3824-6 |
3RT2036 |
3NA3824-6 |
3RT2046 |
3RT2036 |
3RW5525 |
3NA3830-6 |
3RT2037 |
3NA3830-6 |
3RT2047 |
3RT2037 |
3RW5526 |
3NA3132-6 |
3RT2038 |
3NA3132-6 |
3RT1055 |
3RT2038 |
3RW5527 |
3NA3136-6 |
3RT2046 |
3NA3136-6 |
3RT1056 |
3RT2046 |
3RW5534 |
3NA3244-6 |
3RT1054 |
3NA3244-6 |
3RT1064 |
3RT1054 |
3RW5535 |
3NA3244-6 |
3RT1055 |
3NA3244-6 |
3RT1065 |
3RT1055 |
3RW5536 |
3NA3365-6 |
3RT1056 |
3NA3365-6 |
3RT1066 |
3RT1056 |
3RW5543 |
2 x 3NA3354-6 |
3RT1064 |
2 x 3NA3354-6 |
3RT1075 |
3RT1064 |
3RW5544 |
2 x 3NA3354-6 |
3RT1065 |
2 x 3NA3354-6 |
3RT1076 |
3RT1065 |
3RW5545 |
2 x 3NA3365-6 |
3RT1075 |
2 x 3NA3365-6 |
3TF68 |
3RT1075 |
3RW5546 |
2 x 3NA3365-6 |
3RT1075 |
2 x 3NA3365-6 |
3TF69 |
3RT1075 |
3RW5547 |
2 x 3NA3365-6 |
3RT1076 |
2 x 3NA3365-6 |
3TF69 |
3RT1076 |
3RW5548 |
2 x 3NA3365-6 |
3TF68 |
2 x 3NA3365-6 |
-- |
3TF68 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
gR class full-range fuses for semiconductor protection,
cable and line protection
Type of coordination "2",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW5513 |
3NE1815-0 |
3RT2025 |
3RW5514 |
3NE1802-0 |
3RT2026 |
3RW5515 |
3NE1817-0 |
3RT2027 |
3RW5516 |
3NE1818-0 |
3RT2035 |
3RW5517 |
3NE1820-0 |
3RT2035 |
3RW5524 |
3NE1021-2 |
3RT2036 |
3RW5525 |
3NE1022-0 |
3RT2037 |
3RW5526 |
3NE1224-0 |
3RT2038 |
3RW5527 |
3NE1224-0 |
3RT2046 |
3RW5534 |
3NE1225-0 |
3RT1054 |
3RW5535 |
3NE1227-0 |
3RT1055 |
3RW5536 |
3NE1230-0 |
3RT1056 |
3RW5543 |
3NE1230-2 |
3RT1064 |
3RW5544 |
3NE1331-0 |
3RT1065 |
3RW5545 |
3NE1334-2 |
3RT1075 |
3RW5546 |
3NE1334-2 |
3RT1075 |
3RW5547 |
3NE1436-2 |
3RT1076 |
3RW5548 |
3NE1437-2 |
3TF68 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
In inside-delta circuits, a gR class full-range fuse could not provide the semiconductor protection of the delta-connected soft starter with a short-circuit breaking capacity that is adequate for practical use. In this case, we recommend using aR class partial-range fuses for semiconductor protection for type of coordination "2", see next table.
aR class partial-range fuses for semiconductor protection
Type of coordination "2",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW5513 |
3NA3820-6 |
3NE8017-1 |
3RT2025 |
3NA3820-6 |
3NE8017-1 |
3RT2027 |
3RT2025 |
3RW5514 |
3NA3820-6 |
3NE8020-1 |
3RT2026 |
3NA3820-6 |
3NE8020-1 |
3RT2027 |
3RT2026 |
3RW5515 |
3NA3822-6 |
3NE8021-1 |
3RT2027 |
3NA3822-6 |
3NE8021-1 |
3RT2036 |
3RT2027 |
3RW5516 |
3NA3824-6 |
3NE8022-1 |
3RT2035 |
3NA3824-6 |
3NE8022-1 |
3RT2037 |
3RT2035 |
3RW5517 |
3NA3824-6 |
3NE8024-1 |
3RT2035 |
3NA3824-6 |
3NE8024-1 |
3RT2038 |
3RT2035 |
3RW5524 |
3NA3824-6 |
3NE8024-1 |
3RT2036 |
3NA3824-6 |
3NE8024-1 |
3RT2046 |
3RT2036 |
3RW5525 |
3NA3830-6 |
3NE3227 |
3RT2037 |
3NA3830-6 |
3NE3227 |
3RT2047 |
3RT2037 |
3RW5526 |
3NA3132-6 |
3NE3227 |
3RT2038 |
3NA3132-6 |
3NE3227 |
3RT1055 |
3RT2038 |
3RW5527 |
3NA3136-6 |
3NE3227 |
3RT2046 |
3NA3136-6 |
3NE3227 |
3RT1056 |
3RT2046 |
3RW5534 |
3NA3244-6 |
3NE3231 |
3RT1054 |
3NA3244-6 |
3NE3231 |
3RT1064 |
3RT1054 |
3RW5535 |
3NA3244-6 |
3NE3233 |
3RT1055 |
3NA3244-6 |
3NE3233 |
3RT1065 |
3RT1055 |
3RW5536 |
3NA3365-6 |
3NE3334-0B |
3RT1056 |
3NA3365-6 |
3NE3334-0B |
3RT1066 |
3RT1056 |
3RW5543 |
2 x 3NA3354-6 |
3NE3333 |
3RT1064 |
2 x 3NA3354-6 |
3NE3333 |
3RT1075 |
3RT1064 |
3RW5544 |
2 x 3NA3354-6 |
3NE3335 |
3RT1065 |
2 x 3NA3354-6 |
3NE3335 |
3RT1076 |
3RT1065 |
3RW5545 |
2 x 3NA3365-6 |
-- |
3RT1075 |
2 x 3NA3365-6 |
-- |
3TF68 |
3RT1075 |
3RW5546 |
2 x 3NA3365-6 |
-- |
3RT1075 |
2 x 3NA3365-6 |
-- |
3TF69 |
3RT1075 |
3RW5547 |
2 x 3NA3365-6 |
3NE3340-8 |
3RT1076 |
2 x 3NA3365-6 |
3NE3340-8 |
3TF69 |
3RT1076 |
3RW5548 |
2 x 3NA3365-6 |
3NC3342-1U |
3TF68 |
2 x 3NA3365-6 |
3NC3342-1U |
-- |
3TF68 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class full-range fuses for cable and line protection 3NA3 (F1), 3RV2/3VA motor starter protectors/circuit breakers can also be used, possibly with reduced short-circuit breaking capacity, see Table "Motor feeders according to IEC with 3RV2 / 3VA motor starter protectors (without semiconductor protection)". In these cases, optional line contactors can be dispensed with.
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
Soft starter |
Reversing contactor assembly |
Reversing contactor |
---|---|---|
|
for systems up to 480 V |
for systems up to 480 V |
Q11 |
Q21 / Q22 |
Q21 / Q22 |
Type |
Type |
Type |
3RW5513 |
3RA2325 |
3RT2025 |
3RW5514 |
3RA2326 |
3RT2026 |
3RW5515 |
3RA2327 |
3RT2027 |
3RW5516 |
3RA2335 |
3RT2035 |
3RW5517 |
3RA2335 |
3RT2035 |
3RW5524 |
3RA2336 |
3RT2036 |
3RW5525 |
3RA2337 |
3RT2037 |
3RW5526 |
3RA2338 |
3RT2038 |
3RW5527 |
3RA2346 |
3RT2046 |
3RW5534 |
-- |
3RT1054 |
3RW5535 |
-- |
3RT1055 |
3RW5536 |
-- |
3RT1056 |
3RW5543 |
-- |
3RT1064 |
3RW5544 |
-- |
3RT1065 |
3RW5545 |
-- |
3RT1075 |
3RW5546 |
-- |
3RT1075 |
3RW5547 |
-- |
3RT1076 |
3RW5548 |
-- |
3TF68 |
Article number |
|
3RW551.-.HF.4 |
3RW552.-.HF.4 |
3RW554.-.HF.4 |
|
---|---|---|---|---|---|
Installation/ mounting/ dimensions |
|
|
|
|
|
Width x Height x Depth |
mm |
170 × 275 × 152 |
185 × 306 × 203 |
210 × 393 × 203 |
|
mounting type |
|
screw fixing |
|||
mounting position |
|
Vertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°) |
|||
required spacing with side-by-side mounting |
|
|
|
|
|
|
mm |
100 |
|||
|
mm |
5 |
|||
|
mm |
75 |
|||
installation altitude at height above sea level maximum 1) |
m |
2 000 |
|||
protection class IP |
|
IP00 |
|||
Ambient conditions |
|
|
|
|
|
ambient temperature |
|
|
|
|
|
|
°C |
-25 ... +60 |
|||
|
°C |
-40 ... +80 |
|||
environmental category acc. to IEC 60721 |
|
|
|
|
|
|
|
3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
|||
|
|
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
|||
|
|
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
Article number |
|
3RW55..-.HF04 |
3RW55..-.HF14 |
|
---|---|---|---|---|
Control circuit/ Control |
|
|
|
|
control supply voltage |
|
|
|
|
|
|
24/24 |
--/-- |
|
|
V |
-- |
110 ... 250 |
|
relative negative tolerance/relative positive tolerance of the control supply voltage |
|
|
|
|
|
|
-20/20 |
-15/10 |
|
|
|
-20/20 |
--/-- |
|
control supply voltage frequency |
Hz |
50 ... 60 |
||
relative negative tolerance/relative positive tolerance of the control supply voltage frequency |
|
-10/10 |
||
design of the overvoltage protection |
|
Varistor |
||
design of short-circuit protection for control circuit 1) |
|
4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A) |
Article number |
|
3RW55..-.HF.4 |
|
---|---|---|---|
Power Electronics |
|
|
|
operating voltage rated value |
V |
200 ... 480 |
|
relative negative tolerance/relative positive tolerance of the operating voltage |
|
-15/10 |
|
operating voltage at inside-delta circuit rated value |
V |
200 ... 480 |
|
relative negative tolerance/relative positive tolerance of the operating voltage at inside-delta circuit |
|
-15/10 |
|
Operating frequency |
Hz |
50 ... 60 |
|
relative negative tolerance/relative positive tolerance of the operating frequency |
|
-10/10 |
|
minimum load [%] 1) |
% |
10 |
|
wire length between soft starter and motor maximum |
m |
800 |