Product characteristics/function |
Performance features/benefits |
Small and compact design |
Space-saving, clearly arranged control panel layout |
Motor overload and intrinsic device protection without additional wiring |
Adjustable trip classes, integrated diagnostic functions |
Integrated in the SIRIUS modular system |
Link modules to motor starter protectors |
Hybrid switching devices and two-phase motor control |
Minimum power loss and optimized motor control by avoiding DC components |
Certified according to ATEX Directive 94/9/EC |
Suitable for the starting of explosion-proof motors with "increased safety" type of protection EEx e. |
Optional thermistor motor protection |
Full motor protection |
Type |
|
3RW4024 |
3RW4026 |
3RW4027 |
3RW4028 |
---|---|---|---|---|---|
Power electronics |
|||||
Load rating rated operational current Ie |
|
|
|||
|
A |
12.5/11/10 |
25.3/23/21 |
32.2/29/26 |
38/34/31 |
Smallest adjustable rated motor current I M |
A |
5 |
10 |
17 |
23 |
Power loss |
|
|
|||
|
W |
2 |
8 |
13 |
19 |
|
W |
68 |
188 |
220 |
256 |
Permissible rated motor current and starts per hour |
|
|
|||
|
|
|
|||
|
A |
12.5/11 |
25/23 |
32/29 |
38/34 |
|
1/h |
50/50 |
23/23 |
23/23 |
19/19 |
|
A |
12.5/11 |
25/23 |
32/29 |
38/34 |
|
1/h |
36/36 |
15/15 |
16/16 |
12/12 |
|
|
|
|||
|
A |
10/9 |
21/19 |
27/24 |
31/28 |
|
1/h |
47/47 |
21/21 |
20/20 |
18/18 |
|
A |
10/9 |
21/19 |
27/24 |
31/28 |
|
1/h |
34/34 |
15/15 |
14/14 |
13/13 |
1) Measurement at 60 °C according to UL/CSA not required.
2) Current limiting on soft starter set to 300% IM, Tu = 40/50 °C. Maximum adjustable rated motor current IM dependent on CLASS setting.
3) For intermittent duty S4 with ON period = 30%, Tu = 40/50 °C, stand-alone installation vertical. The quoted switching frequencies do not apply for automatic mode. Factors for permissible switching frequency in other mounting position, direct mounting, side-by-side mounting, and implementation of optional auxiliary fan, see Equipment Manual in Chapter "Configuring".
Type |
|
3RW4036 |
3RW4037 |
3RW4038 |
3RW4046 |
3RW4047 |
---|---|---|---|---|---|---|
Power electronics |
||||||
Load rating rated operational current Ie |
|
|
||||
|
A |
45/42/39 |
63/58/53 |
72/62.1/60 |
80/73/66 |
106/98/90 |
Smallest adjustable rated motor current IMfor motor overload protection |
A |
23 |
26 |
35 |
43 |
46 |
Power loss |
|
|
||||
|
W |
6 |
12 |
15 |
12 |
21 |
|
W |
316 |
444 |
500 |
576 |
768 |
Permissible rated motor current and starts per hour |
|
|
||||
|
|
|
||||
|
A |
45/42 |
63/58 |
72/62 |
80/73 |
106/98 |
|
1/h |
38/38 |
23/23 |
22/22 |
22/22 |
15/15 |
|
A |
45/42 |
63/58 |
72/62 |
80/73 |
106/98 |
|
1/h |
26/26 |
15/15 |
15/15 |
15/15 |
10/10 |
|
|
|
||||
|
A |
38/34 |
46/42 |
50/46 |
64/58 |
77/70 |
|
1/h |
30/30 |
31/31 |
34/34 |
23/23 |
23/23 |
|
A |
38/34 |
46/42 |
50/46 |
64/58 |
77/70 |
|
1/h |
21/21 |
22/22 |
24/24 |
16/16 |
16/16 |
1) Measurement at 60 °C according to UL/CSA not required.
2) Current limiting on soft starter set to 300% IM, Tu = 40/50 °C. Maximum adjustable rated motor current IM dependent on CLASS setting.
3) For intermittent duty S4 with ON period = 30%, Tu = 40/50 °C, stand-alone installation vertical. The quoted switching frequencies do not apply for automatic mode. Factors for permissible switching frequency in other mounting position, direct mounting, side-by-side mounting, and implementation of optional auxiliary fan, see Equipment Manual in Chapter "Configuring".
Type of coordination "1", CLASS 10,
short-circuit breaking capacity Iq in kA, see table
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW4024 |
3RV2021-4AA10 |
55 |
3RV2021-4AA10 |
10 |
3RW4026 |
3RV2021-4DA10 |
55 |
3RV2021-4DA10 |
10 |
3RW4027 |
3RV2021-4EA10 |
55 |
3RV2021-4EA10 |
10 |
3RW4028 |
3RV2021-4FA10 |
55 |
3RV2021-4FA10 |
10 |
3RW4036 |
3RV2031-4WA10 |
10 |
3RV2031-4WA10 |
10 |
3RW4037 |
3RV2031-4JA10 |
10 |
3RV2031-4JA10 |
5 |
3RW4038 |
3RV2031-4KA10 |
10 |
3RV2031-4KA10 |
5 |
3RW4046 |
3RV2041-4RA10 |
11 |
3RV2041-4YA10 |
5 |
3RW4047 |
3RV2041-4MA10 |
11 |
3RV2041-4MA10 |
5 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller motor starter protectors/circuit breakers from the same series can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must match the connected three-phase motor, the short-circuit and overload requirements of the application, and the line protection for the cables used.
gG class full-range fuses for cable and line protection
according to IEC 60269‑2, without semiconductor protection
Type of coordination "1",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW4024 |
3NA3820-6 |
3RT2025 |
3RT2025/ |
3RT2025 |
3RW4026 |
3NA3822-6 |
3RT2026 |
3RT2027 |
3RT2037 |
3RW4027 |
3NA3824-6 |
3RT2027 |
3RT2028 |
3RT2037 |
3RW4028 |
3NA3824-6 |
3RT2028 |
3RT2035 |
3RT2037 |
3RW4036 |
3NA3130-6 |
3RT2036 |
3RT2036 |
3RT2038 |
3RW4037 |
3NA3132-6 |
3RT2037 |
3RT2037 |
3RT2046 |
3RW4038 |
3NA3132-6 |
3RT2038 |
3RT2038 |
3RT2046 |
3RW4046 |
3NA3136-6 |
3RT2045 |
3RT2045 |
3RT2047 |
3RW4047 |
3NA3136-6 |
3RT2047 |
3RT2047 |
3RT1054 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
gR class full-range fuses for semiconductor protection,
cable and line protection
Type of coordination "2",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW4024 |
3NE1814-0 |
3RT2025 |
3RT2025/ |
3RT2025 |
3RW4026 |
3NE1803-0 |
3RT2026 |
3RT2027 |
3RT2037 |
3RW4027 |
3NE1020-2 |
3RT2027 |
3RT2028 |
3RT2037 |
3RW4028 |
3NE1020-2 |
3RT2028 |
3RT2035 |
3RT2037 |
3RW4036 |
3NE1020-2 |
3RT2036 |
3RT2036 |
3RT2038 |
3RW4037 |
3NE1820-0 |
3RT2037 |
3RT2037 |
3RT2046 |
3RW4038 |
3NE1820-0 |
3RT2038 |
3RT2038 |
3RT2046 |
3RW4046 |
3NE1021-0 |
3RT2045 |
3RT2045 |
3RT2047 |
3RW4047 |
3NE1022-0 |
3RT2047 |
3RT2047 |
3RT1054 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
aR class partial-range fuses for semiconductor protection
Type of coordination "2",
short-circuit breaking capacity Iq = 65 kA
Note:
For general recommendations on the setup of motor feeders with soft starters, see "SIRIUS 3RW soft starters" → "Overview" → "Motor feeders with soft starters".
3RW4024 |
3NA3820-6 |
-- |
3NE4101 |
3NE8015-1 |
3NC2240 |
3RT2025 |
3RT2025/ |
3RT2025 |
3RW4026 |
3NA3822-6 |
-- |
3NE4102 |
3NE8017-1 |
3NC2263 |
3RT2026 |
3RT2027 |
3RT2037 |
3RW4027 |
3NA3824-6 |
-- |
3NE4118 |
3NE8018-1 |
3NC2280 |
3RT2027 |
3RT2028 |
3RT2037 |
3RW4028 |
3NA3824-6 |
-- |
3NE4118 |
3NE8020-1 |
3NC2280 |
3RT2028 |
3RT2035 |
3RT2037 |
3RW4036 |
3NA3130-6 |
-- |
3NE4120 |
3NE8020-1 |
3NC2280 |
3RT2036 |
3RT2036 |
3RT2038 |
3RW4037 |
3NA3132-6 |
-- |
3NE4121 |
3NE8021-1 |
-- |
3RT2037 |
3RT2037 |
3RT2046 |
3RW4038 |
3NA3132-6 |
3NE3221 |
-- |
3NE8022-1 |
-- |
3RT2038 |
3RT2038 |
3RT2046 |
3RW4046 |
3NA3136-6 |
3NE3222 |
-- |
3NE8022-1 |
-- |
3RT2045 |
3RT2045 |
3RT2047 |
3RW4047 |
3NA3136-6 |
3NE3224 |
-- |
3NE8024-1 |
-- |
3RT2047 |
3RT2047 |
3RT1054 |
Note:
The specified short-circuit breaking capacities Iq in kA are covered by combination tests. Smaller fuses than those specified can be used at any time as smaller ones trip more quickly in the event of a short circuit (unchanged short-circuit breaking capacity) and thus protect the soft starter in any case. The dimensioning of the short-circuit components must, however, be suitable for the connected three-phase motor and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class full-range fuses for cable and line protection 3NA3 (F1), 3RV2 motor starter protectors/circuit breakers can also be used, possibly with reduced short-circuit breaking capacity, see Table "Motor feeders according to IEC with 3RV2 motor starter protectors (without semiconductor protection)". In these cases, optional line contactors can be dispensed with.
Type |
3RW402. |
3RW403. |
3RW404. |
||
---|---|---|---|---|---|
Mechanics and environment |
|||||
Mounting dimensions (W x H x D) |
|||||
|
![]() |
mm |
45 x 125 x 154 |
55 x 144 x 170 |
70 x 160 x 188 |
|
mm |
45 x 150 x 154 |
55 x 144 x 170 |
70 x 160 x 188 |
|
Permissible ambient temperature |
|||||
Operation |
°C |
-25 ... +60; (derating from +40) |
|||
During storage |
°C |
-40 ... +80 |
|||
Weight |
kg |
0.77 |
1.35 |
1.9 |
|
Permissible mounting position 1) |
|||||
|
![]() |
||||
|
![]() |
||||
Installation type 1) |
Stand-alone installation |
![]() |
![]() |
||
Permissible installation altitude |
m |
5 000 (Derating from 1 000 see characteristic curve → "SIRIUS 3RW soft starters"→ "Overview" → "Constraints") |
|||
Degree of protection |
IP20 for 3RW402.; all others IP00 |
1) In the case of deviations, please observe derating, see Equipment Manual in the chapter"Configuring".
Type |
Terminal |
3RW402., 3RW403., 3RW404. |
||
---|---|---|---|---|
Control electronics |
||||
Rated values |
||||
Rated control supply voltage |
A1/A2 |
V |
24 AC/DC |
110 ... 230 AC/DC |
|
% |
± 20 |
-15/+10 |
|
Rated frequency |
Hz |
50/60 |
||
|
% |
± 10 |
Type |
3RW402.-..B.4, |
3RW402.-..B.5, |
|
---|---|---|---|
Power electronics |
|||
Rated operational voltage |
V AC |
200 ... 480 |
400 ... 600 |
Tolerance |
% |
-15/+10 |
|
Maximum blocking voltage thyristor |
V AC |
1 600 |
|
Rated frequency |
Hz |
50/60 |
|
Tolerance |
% |
± 10 |
|
Uninterrupted duty at 40 °C (% of Ie) |
% |
115 |
|
Minimum load (% of smallest adjustable |
% |
20 (at least 2 A) |
|
Maximum cable length between soft starter and motor |
m |
300 |