Phoenix Contact QUINT-UPS/ 24DC/ 24DC/ 5/1.3AH - 2320254 là Bộ lưu điện UPS DC 24V 5A 1.3AH
Nguồn cung cấp năng lượng liên tục với công nghệ IQ và bộ lưu trữ năng lượng tích hợp để lắp trên thanh ray DIN, đầu vào 24 V DC, đầu ra: 24 V DC / 5 A, bộ lưu trữ năng lượng: chì AGM 1,2 Ah, bao gồm bộ chuyển đổi thanh ray DIN đa năng UTA 107/30 được gắn/
Uninterruptible energy supply with IQ technology and integrated energy storage for DIN rail mounting, input 24 V DC, output: 24 V DC / 5 A, energy storage: lead AGM 1.2 Ah, incl. mounted UTA 107/30 universal DIN rail adapter
- Tài liệu kỹ thuật Phoenix Contact QUINT-UPS/ 24DC/ 24DC/ 5/1.3AH - 2320254 ở đây.
Product description
UPS modules with integrated energy storage are particularly space saving: UPS module and energy storage are combined in one housing. It's just a case of connecting a power supply upstream.
Technical data
Input data
DC operation |
Input voltage |
24 V DC |
Input voltage range |
18 V DC ... 30 V DC |
Input voltage range DC |
18 V DC ... 30 V DC |
Voltage type of supply voltage |
DC |
Buffer period |
50 min. (1 A) |
5 min. (5 A) |
Current consumption |
9.3 A (24 V DC) |
9.7 mA |
1.7 A |
7 A |
Fixed backup threshold |
≤ 22.6 V DC |
Output data
Efficiency |
> 97.1 % (Mains operation, with charged energy storage) |
97.31 % |
Nominal output voltage |
24 V DC |
Output voltage range |
18 V DC ... 30 V DC |
Nominal output current (IN) |
5 A (0 °C ... 40 °C) |
Output current limit |
> 7.5 A (Battery operation) |
Bridging time |
360 s |
Derating |
60 °C ... 70 °C (2.5%/K) |
Output power |
120 W |
Power dissipation |
2.5 W (Mains operation) |
2.7 W (Mains operation) |
1.9 W (Mains operation) |
3.3 W (Battery operation) |
3.3 W (Battery operation) |
4.1 W (Battery operation) |
Output fuse |
1x 15 A |
Connection in parallel |
2 |
Connection in series |
No |
Mains operation |
Nominal output voltage |
24 V DC |
Output voltage range |
18 V DC ... 30 V DC (UOUT = UIN - 0,1 V DC) |
Nominal output current (IN) |
5 A (0 °C ... 40 °C) |
POWER BOOST (IBoost) |
7.5 A (0 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) |
30 A (0 °C ... 40 °C) |
Duration |
12 ms (SFB technology) |
Battery operation |
Nominal output voltage |
24 V DC |
Output voltage range |
19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC) |
Nominal output current (IN) |
5 A (0 °C ... 40 °C) |
POWER BOOST (IBoost) |
7.5 A (0 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) |
32.5 A (0 °C ... 40 °C) |
Duration |
15 ms (SFB technology) |
Signal: Alarm |
Output description |
Relay |
Output voltage |
≤ 30 V AC/DC |
Continuous load current |
≤ 100 mA |
Signal: Battery charge |
Output description |
Relay |
Output voltage |
≤ 30 V AC/DC |
Continuous load current |
≤ 100 mA |
Signal: Battery mode |
Output description |
Relay |
Output voltage |
≤ 30 V AC/DC |
Continuous load current |
≤ 100 mA |
Signal |
Continuous load current |
≤ 200 mA |
Energy storage
Nominal voltage UN |
24 V DC |
End-of-charge voltage |
24 V DC ... 29 V DC (temperature compensated) |
Charging current |
0.36 A |
Nominal capacity |
1.2 Ah |
Buffer period |
50 min. (1 A) |
5 min. (5 A) |
Latest startup date (battery only) |
3 Months (0 °C ... 20 °C) |
1 Months (30 °C ... 40 °C) |
Latest startup (battery only) - range |
1 Months ... 3 Months (20 °C ... 30 °C) |
Battery technology |
VRLA-AGM |
Memory medium |
VRLA-AGM Battery 1.2 Ah |
Accumulator type |
2x BB Battery BP1.2-12FR (from UPS V/C-level 05) |
Disposal |
Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
IQ technology |
Yes |
Temperature sensor |
yes |
Network management |
Yes |
Connection data
Input |
Connection method |
Screw connection |
Conductor cross section, rigid min. |
0.2 mm² |
Conductor cross section, rigid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
20 |
Conductor cross section AWG max. |
12 |
Stripping length |
7 mm |
Screw thread |
M4 |
Tightening torque, min |
0.5 Nm |
Tightening torque max |
0.6 Nm |
Output |
Connection method |
Screw connection |
Conductor cross section, rigid min. |
0.2 mm² |
Conductor cross section, rigid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
20 |
Conductor cross section AWG max. |
12 |
Stripping length |
7 mm |
Screw thread |
M4 |
Tightening torque, min |
0.5 Nm |
Tightening torque max |
0.6 Nm |
Signal |
Conductor cross section, rigid min. |
0.2 mm² |
Conductor cross section, rigid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
12 |
Screw thread |
M4 |
Tightening torque, min |
0.5 Nm |
Tightening torque max |
0.6 Nm |
Interfaces
Interface |
IFS (Interface system data port) |
Signaling
Types of signaling |
LED |
Relay contact |
Interface/software |
Signal output |
Signalization designation |
Power In OK |
Status display |
LED |
Note on status display |
Static to |
Static to |
Signal output: Switching output |
Signalization designation |
Alarm |
Status display |
LED |
Note on status display |
Static to |
Color |
red |
Note on status display |
Static to |
Signal output: Switching output |
Signalization designation |
Battery charge |
Status display |
LED bar graph |
Note on status display |
dynamic |
Color |
red/green |
Note on status display |
dynamic |
Signal output: Switching output |
Signalization designation |
Battery mode |
Status display |
LED |
Note on status display |
Static to |
Color |
yellow |
Note on status display |
Static to |
Product properties
Product type |
DC UPS with integrated energy storage |
Product family |
QUINT UPS ‒ UPS with integrated energy storage |
Disposal |
Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
IQ technology |
Yes |
MTBF (IEC 61709, SN 29500) |
> 806000 h (40 °C) |
Insulation characteristics |
Protection class |
III |
Degree of pollution |
2 |
Life expectancy (electrolytic capacitors) |
Time |
316800 h |
Dimensions
Width |
88 mm |
Height |
138 mm |
Depth |
125 mm |
Installation dimensions |
Installation distance right/left |
5 mm / 5 mm |
Installation distance top/bottom |
50 mm / 50 mm |
Mounting
Mounting type |
DIN rail mounting |
Assembly instructions |
alignable: horizontal 5 mm, vertical 50 mm |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing material |
Metal |
Type of housing |
Steel sheet, zinc-plated |
Side element version |
Galvanized sheet steel, closed |
Housing material |
Steel sheet, zinc-plated |
Environmental and real-life conditions
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (storage/transport) |
-20 °C ... 40 °C |
Ambient temperature (charge) |
0 °C ... 40 °C |
Ambient temperature (discharge) |
-20 °C ... 50 °C |
Climatic class |
3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) |
≤ 95 % (25 °C, non-condensing) |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
15 Hz ... 150 Hz, 2.3g tv = 90 min. |
Standards and regulations
Rail applications |
EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety |
EN 60950-1/VDE 0805 (SELV) |
EN 61558-2-17 |
Approvals
UL approvals |
UL/C-UL Recognized UL 60950-1 |
UL Listed UL 508 |
EMC data
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission |
EN 61000-6-3 |
EN 61000-6-4 |
EMC requirements for noise immunity |
EN 61000-6-1 |
EN 61000-6-2 |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge |
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge |
Contact discharge |
8 kV (Test Level 4) |
Discharge in air |
15 kV (Test Level 4) |
Comments |
Criterion A |
Electromagnetic HF field |
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
20 V/m |
Frequency range |
1 GHz ... 2 GHz |
Test field strength |
10 V/m |
Frequency range |
2 GHz ... 3 GHz |
Test field strength |
3 V/m |
Comments |
Criterion A |
Fast transients (burst) |
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst) |
Input |
2 kV (Test Level 3 - asymmetrical) |
Output |
2 kV (Test Level 3 - asymmetrical) |
Signal |
2 kV (Test Level 4 - asymmetrical) |
Comments |
Criterion A |
Surge voltage load (surge) |
Standards/regulations |
EN 61000-4-5 |
Input |
1 kV (Test Level 2 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) |
Output |
1 kV (Test Level 2 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) |
Signal |
1 kV (Test Level 2 - asymmetrical) |
Comments |
Criterion A |
Conducted interference |
Standards/regulations |
EN 61000-4-6 |
Conducted interference |
I/O/S |
asymmetrical |
Frequency range |
0.15 MHz ... 80 MHz |
Comments |
Criterion A |
Voltage |
10 V (Test Level 3) |
Emitted interference |
Standards/regulations |
EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Commercial data
Item number |
2320254 |
Packing unit |
1 pc |
Minimum order quantity |
1 pc |
Product key |
CMUQV3 |
Catalog page |
Page 344 (C-4-2019) |
GTIN |
4046356554145 |
Weight per piece (including packing) |
2,540 g |
Weight per piece (excluding packing) |
2,137 g |
Customs tariff number |
85371091 |
Country of origin |
CN |
Classifications
ECLASS
ECLASS-11.0 |
27040705 |
ECLASS-13.0 |
27040705 |
ECLASS-12.0 |
27040705 |
ETIM
UNSPSC
Approvals
cUL Recognized
Approval ID: FILE E 211944
UL Recognized
Approval ID: FILE E 211944
EAC
Approval ID: EAC-Zulassung
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
Approval ID: FILE E 123528
cUL Listed
Approval ID: FILE E 123528
KC
Approval ID: R-R-PCK-2320254
cUL Listed
Approval ID: FILE E 199827
UL Listed
Approval ID: FILE E 199827
cULus Recognized
cULus Listed
cULus Listed
Environmental product compliance
|
REACh SVHC |
Lead 7439-92-1 |
|
China RoHS |
Environmentally Friendly Use Period = 3 |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Compatible products
Data cable
IFS-USB-DATACABLE - 2320500
Data cable
IFS-RS232-DATACABLE - 2320490
Data cable
IFS-MINI-DIN-DATACABLE - 2320487
Data cable
IFS-OPEN-END-DATACABLE - 2320450
Mounting adapter
QUINT-PS-ADAPTERS7/1 - 2938196
Mounting adapter
UTA 107/30 - 2320089
Mounting adapter
UWA 182/52 - 2938235
Fuse
FUSE 15A/32V FKS ATO - 2908361
Memory block
IFS-CONFSTICK-L - 2901103
Uninterruptible power supply replacement battery
UPS-BAT-KIT/PB/2X12V/1.2AH - 1283114