Product |
Article Number (Market Facing Number) |
Product Description |
Product family |
Product Lifecycle (PLM) |
Price data |
Price Group |
List Price |
Customer Price |
Metal Factor |
Delivery information |
Export Control Regulations |
Standard lead time ex-works |
Net Weight (lb) |
Product Dimensions (W x L x H) |
Packaging Dimension |
Package size unit of measure |
Quantity Unit |
Packaging Quantity |
Additional Product Information |
EAN |
UPC |
Commodity Code |
LKZ_FDB/ CatalogID |
Product Group |
Country of origin |
RoHS Compliance |
Returnable |
Obligation Category for taking back electrical and electronic equipment after use |
Classifications |
Article number |
6EP1322-2BA00 |
|
Product |
SITOP PSU100S |
|
Power supply, type |
12 V/7 A |
|
Input |
|
|
Input |
1-phase AC |
|
Supply voltage |
|
|
|
120 V |
|
|
230 V |
|
|
Automatic range selection |
|
Input voltage |
|
|
|
85 ... 132 V |
|
|
170 ... 264 V |
|
Wide-range input |
No |
|
Overvoltage resistance |
2.3 × Vin rated, 1.3 ms |
|
Mains buffering at Iout rated, min. |
20 ms; at Vin = 93/187 V |
|
Rated line frequency 1 |
50 Hz |
|
Rated line frequency 2 |
60 Hz |
|
Rated line range |
47 ... 63 Hz |
|
Input current |
|
|
|
1.73 A |
|
|
0.99 A |
|
Switch-on current limiting (+25 °C), max. |
45 A |
|
Built-in incoming fuse |
T 3,15 A/250 V (not accessible) |
|
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker: from 6 A characteristic C |
|
Output |
|
|
Output |
Controlled, isolated DC voltage |
|
Rated voltage Vout DC |
12 V |
|
Total tolerance, static ± |
3 % |
|
Static mains compensation, approx. |
0.1 % |
|
Static load balancing, approx. |
1 % |
|
Residual ripple peak-peak, max. |
150 mV |
|
Residual ripple peak-peak, typ. |
20 mV |
|
Spikes peak-peak, max. (bandwidth: 20 MHz) |
240 mV |
|
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
100 mV |
|
Adjustment range |
11.5 ... 15.5 V |
|
Product function Output voltage adjustable |
Yes |
|
Output voltage setting |
via potentiometer |
|
Status display |
Green LED for 12 V OK |
|
Signaling |
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for 12 V OK |
|
On/off behavior |
Overshoot of Vout < 3 % |
|
Startup delay, max. |
0.3 s |
|
Voltage rise, typ. |
10 ms |
|
Rated current value Iout rated |
7 A |
|
Current range |
0 ... 7 A |
|
|
+50 ... +70 °C: Derating 0.75%/K |
|
Supplied active power typical |
84 W |
|
Short-term overload current |
|
|
|
25 A |
|
|
25 A |
|
Duration of overloading capability for excess current |
|
|
|
800 ms |
|
|
800 ms |
|
Parallel switching for enhanced performance |
Yes |
|
Numbers of parallel switchable units for enhanced performance |
2 |
|
Efficiency |
|
|
Efficiency at Vout rated, Iout rated, approx. |
84 % |
|
Power loss at Vout rated, Iout rated, approx. |
15 W |
|
Closed-loop control |
|
|
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. |
5 % |
|
Load step setting time 10 to 90%, typ. |
1 ms |
|
Load step setting time 90 to 10%, typ. |
1 ms |
|
Protection and monitoring |
|
|
Output overvoltage protection |
< 20 V |
|
Current limitation |
7 ... 8.8 A |
|
Property of the output Short-circuit proof |
Yes |
|
Short-circuit protection |
Constant current characteristic |
|
Enduring short circuit current RMS value |
|
|
|
8.8 A |
|
Overcurrent overload capability in normal operation |
overload capability 150 % Iout rated up to 5 s/min |
|
Overload/short-circuit indicator |
- |
|
Safety |
|
|
Primary/secondary isolation |
Yes |
|
Galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
|
Protection class |
Class I |
|
Leakage current |
|
|
|
3.5 mA |
|
|
0.4 mA |
|
CE mark |
Yes |
|
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259, cCSAus (CSA C22.2 No. 60950-1, UL 60950-1, UL 1604) |
|
Explosion protection |
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 |
|
FM approval |
- |
|
CB approval |
Yes |
|
Marine approval |
GL |
|
Degree of protection (EN 60529) |
IP20 |
|
EMC |
|
|
Emitted interference |
EN 55022 Class B |
|
Supply harmonics limitation |
EN 61000-3-2 |
|
Noise immunity |
EN 61000-6-2 |
|
Operating data |
|
|
Ambient temperature |
|
|
|
-25 ... +70 °C |
|
|
with natural convection |
|
|
-40 ... +85 °C |
|
|
-40 ... +85 °C |
|
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
|
Mechanics |
|
|
Connection technology |
screw-type terminals |
|
Connections |
|
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
|
|
+, -: 2 screw terminals each for 0.5 ... 2.5 mm² |
|
|
Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm² |
|
Connections signaling contact |
2 screw terminals for 0.5 ... 2.5 mm² |
|
Width of the enclosure |
50 mm |
|
Height of the enclosure |
125 mm |
|
Depth of the enclosure |
120 mm |
|
Required spacing |
|
|
|
50 mm |
|
|
50 mm |
|
|
0 mm |
|
|
0 mm |
|
Weight, approx. |
0.5 kg |
|
Product feature of the enclosure housing for side-by-side mounting |
Yes |
|
Installation |
Snaps onto DIN rail EN 60715 35x7.5/15 |
|
MTBF at 40 °C |
1 998 441 h |
|
Other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |