Number of levels |
1 |
Number of connections |
2 |
Potentials |
1 |
Nominal cross section |
4.0 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Rated surge voltage |
8 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Maximum power dissipation for nominal condition |
0.77 W |
Maximum load current |
41 A (with 6.2 mm² conductor cross section) |
Nominal current IN |
24 A |
Nominal voltage UN |
800 V |
Open side panel |
Yes |
Shock protection test specification |
IEC 60529:2001-02 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Result of surge voltage test |
Test passed |
Surge voltage test setpoint |
9.8 kV |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
2 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of bending test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
0.2 mm² / 0.2 kg |
|
2.5 mm² / 0.7 kg |
|
4 mm² / 0.9 kg |
Tensile test result |
Test passed |
Conductor cross section tensile test |
0.2 mm² |
Tractive force setpoint |
10 N |
Conductor cross section tensile test |
2.5 mm² |
Tractive force setpoint |
50 N |
Conductor cross section tensile test |
4 mm² |
Tractive force setpoint |
60 N |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 32/NS 35 |
Setpoint |
1 N |
Result of voltage-drop test |
Test passed |
Requirements, voltage drop |
≤ 3.2 mV |
Result of temperature-rise test |
Test passed |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
2.5 mm² |
Short-time current |
0.3 kA |
Conductor cross section short circuit testing |
4 mm² |
Short-time current |
0.48 kA |
Result of thermal test |
Test passed |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Oscillation, broadband noise test result |
Test passed |
Test specification, oscillation, broadband noise |
DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum |
Service life test category 2, bogie-mounted |
Test frequency |
f1 = 5 Hz to f2 = 250 Hz |
ASD level |
6.12 (m/s2)2/Hz |
Acceleration |
3.12 g |
Test duration per axis |
5 h |
Test directions |
X-, Y- and Z-axis |
Shock test result |
Test passed |
Test specification, shock test |
DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form |
Half-sine |
Acceleration |
30g |
Shock duration |
18 ms |
Number of shocks per direction |
3 |
Test directions |
X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
125 °C |
Static insulating material application in cold |
-60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) |
Test passed |
Flame test method (DIN EN 60695-11-10) |
V0 |
Oxygen index (DIN EN ISO 4589-2) |
>32 % |
NF F16-101, NF F10-102 Class I |
2 |
NF F16-101, NF F10-102 Class F |
2 |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |