Number of levels |
1 |
Number of connections |
2 |
Potentials |
1 |
Nominal cross section |
50 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Rated surge voltage |
8 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Maximum power dissipation for nominal condition |
4.73 W |
Maximum load current |
150 A (with 50 mm² conductor cross section) |
Nominal current IN |
150 A |
Nominal voltage UN |
1000 V |
Open side panel |
No |
Shock protection test specification |
DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Note regarding shock protection |
Finger-safe protection is not guaranteed if bridges are positioned. |
Result of surge voltage test |
Test passed |
Surge voltage test setpoint |
9.8 kV |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
2.2 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of bending test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
25 mm² / 4.5 kg |
|
50 mm² / 9.5 kg |
|
70 mm²/10.4 kg |
Tensile test result |
Test passed |
Conductor cross section tensile test |
25 mm² |
Tractive force setpoint |
135 N |
Conductor cross section tensile test |
50 mm² |
Tractive force setpoint |
236 N |
Conductor cross section tensile test |
70 mm² |
Tractive force setpoint |
285 N |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 32/NS 35 |
Setpoint |
10 N |
Result of voltage-drop test |
Test passed |
Requirements, voltage drop |
≤ 3.2 mV |
Result of temperature-rise test |
Test passed |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
50 mm² |
Short-time current |
6 kA |
Result of thermal test |
Test passed |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
130 °C |
Static insulating material application in cold |
-60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) |
Test passed |
Flame test method (DIN EN 60695-11-10) |
V0 |
Oxygen index (DIN EN ISO 4589-2) |
>32 % |
NF F16-101, NF F10-102 Class I |
2 |
NF F16-101, NF F10-102 Class F |
2 |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |