DC input | 10mV, 50mV, 60mV, 75mV, 100mV, 150mV |
Input impedance | 50KΩ |
Source impedance | 100Ω maximum |
Thermocouple | Types J, K, R, S, T 10 to 50mV |
Thermocouple TBP | Thermocouple break protection upscale drive as standard |
Thermocouple CJC | Cold junction compensation available on request |
Thermocouple overload | 10 x rating continuously |
Nominal frequency | 50/60Hz |
Voltage burden | 3VA maximum |
Voltage overload | 1.2 x rating continuously 1.5 x rating for 10 seconds |
Set point repeatability | >0.5% of full span |
Differential (hysteresis) | Pre-set at 1% Values 1 to 15% available on request |
Trip level adjustment | Low trip: 0 to 80% High trip: 40 to 120% |
Time delay adjustable | 0 to 10 seconds |
AC auxiliary supply voltage | 100V, 110V, 120V, 220V, 240V, 480V, +/- 20% |
DC auxiliary supply voltage | 12V, 24V, 48V, 110V or 125V, +/- 20% Including ripple |
Auxiliary voltage burden | 4VA (max) |
Output relay | 2-pole change over |
Relay contact rating | AC: 240V 5A non inductive DC: 24V 5A resistive |
Relay mechanical life | 0.2 million operations at rated loads |
Relay reset | Automatic |
Operating temperature | 0oC to +60oC (0oC to +40oC for UL models) |
Storage temperature | -20oC to + 70oC |
Temperature co-efficient | 0.05% per oC |
Interference immunity | Electrical stress surge withstand and non-function to ANSI/IEEE C37 90a |
Enclosure style | HIN-rail with wall mounting facility |
Material | Flame retardant polycarbonate/ABS |
Enclosure integrity | IP50 |
Dimensions | 55mm x 70mm x 112mm (WxHxD) |
Weight | 0.4Kg approx. |