Width | 96 mm |
---|---|
Height | 96 mm |
Depth | 58 mm |
Ambient temperature (operation) | -10 °C ... 55 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | ≤ 2000 m |
Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
Degree of protection | IP54 (Display (+ EEM-MA-IP)) |
IP20 (Housing) |
Measuring principle | True r.m.s. value measurement (TRMS) |
---|---|
Acquisition of harmonics | up to 63rd harmonic |
Measured value | AC sine (50/60 Hz) |
Input name | Voltage measuring input V1, V2, V3 |
Input voltage range | 35 V AC ... 690 V AC (Phase/Phase) |
20 V AC ... 400 V AC (Phase/neutral conductor) | |
60 V AC ... 2000000 V AC (primary) | |
60 V AC ... 400 V AC (secondary) | |
Surge voltage capacity | 760 V AC (Phase/Phase) |
Precision | 0.2 % |
Input name | Current measurement I1, I2, I3 |
Input current | 1 A (secondary) |
5 A (secondary) | |
Current measuring range | 1 A ... 20000 A (primary) |
Overload capacity | 6 A (Imax) |
Response threshold from measuring range nominal value | 10 mA (1 A) |
Precision | 0.2 % |
Current overload | 50 A for 1 s |
Precision | 0.5 % |
Active energy (IEC 62053-22) | Class 0.5 S |
Reactive power (IEC 62053-23) | Class 2 |
Description of the input | Digital input in accordance with IEC/EN 61131-2 (type 3) |
Number | 1 |
Voltage input signal | 0 V DC ... 30 V DC |
Current input signal | 2 mA ... 15 mA |
Output description | Digital output in accordance with IEC/EN 61131-2 (type 3) |
---|---|
Number | 1 |
Current output signal | ≤ 100 mA |
Designation | Network interface |
---|---|
Communication protocol | Modbus/TCP |
REST | |
Connection method | RJ45 |
Display | LCD display, two-color backlit |
---|---|
Supply voltage range | 100 V AC ... 400 V AC (±20 %) |
150 V DC ... 250 V DC (±20 %) | |
Power consumption | ≤ 4 W |
Mains type | 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor) |
Test voltage | 4 kV AC (50 Hz, 1 min.) |
Product family | EMpro |
Connection name | Current / voltage / supply |
---|---|
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 6 mm² |
Conductor cross section flexible | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 10 |
Torque | 0.5 Nm ... 0.6 Nm |
Connection name | Digital I/O / communication |
---|---|
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 26 ... 14 |
Torque | 0.5 Nm ... 0.6 Nm |
Operating mode | Indoor use |
---|
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
ECLASS 10.0.1 | 27142330 |
---|---|
ECLASS 11.0 | 27142330 |
ECLASS 5.0 | 27200301 |
ECLASS 5.1 | 27200301 |
ECLASS 6.0 | 27142300 |
ECLASS 7.0 | 27142330 |
ECLASS 9.0 | 27142330 |
ETIM 4.0 | EC002301 |
---|---|
ETIM 6.0 | EC002301 |
ETIM 7.0 | EC002301 |