Number of levels |
2 |
Number of connections |
4 |
Nominal cross section |
4 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Rated surge voltage |
6 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Maximum power dissipation for nominal condition |
1.02 W (the value is multiplied when connecting multiple levels) |
Ambient temperature (operation) |
-60 °C ... 85 °C |
Ambient temperature (storage/transport) |
-25 °C ... 55 °C (For a short time, not exceeding 24 h, -60 to +70 °C) |
Permissible humidity (storage/transport) |
30 % ... 70 % |
Ambient temperature (assembly) |
-5 °C ... 70 °C |
Ambient temperature (actuation) |
-5 °C ... 70 °C |
Connection in acc. with standard |
IEC 60947-7-1 |
Nominal current IN |
32 A |
Maximum load current |
32 A (with 4 mm² conductor cross section) |
Nominal voltage UN |
500 V |
Open side panel |
Yes |
Shock protection test specification |
IEC 60529:2001-02 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Result of surge voltage test |
Test passed |
Surge voltage test setpoint |
7.3 kV |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
1.89 kV |
Checking the mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of bending test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
0.2 mm² / 0.2 kg |
|
4 mm² / 0.9 kg |
Tensile test result |
Test passed |
Conductor cross section tensile test |
0.2 mm² |
Tractive force setpoint |
10 N |
Conductor cross section tensile test |
4 mm² |
Tractive force setpoint |
60 N |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 32/NS 35 |
Setpoint |
1 N |
Result of voltage-drop test |
Test passed |
Requirements, voltage drop |
≤ 3.2 mV |
Result of temperature-rise test |
Test passed |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
4 mm² |
Short-time current |
0.48 kA |
Result of thermal test |
Test passed |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Relative insulation material temperature index (Elec.; UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
130 °C |
Static insulating material application in cold |
-60 °C |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |