The pluggable electromechanical and solid-state relays in the RIFLINE complete product range and the base are recognized and approved in accordance with UL 508. The relevant approvals can be called up at the individual components in question.
Product type | Relay Module |
Application | Universal |
Operating mode | 100% operating factor |
Mechanical service life | approx. 2x 107 cycles |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Insulation | Basic insulation |
Maximum power dissipation for nominal condition | 1.01 W |
Test voltage Winding/contact | 2.5 kVrms (50 Hz, 1 min., winding/contact) |
Test voltage Changeover contact/changeover contact | 2 kVrms (50 Hz, 1 min., changeover contact/changeover contact) |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 2.5 kV |
Coil side | |
Nominal input voltage UN | 24 V DC |
Input voltage range | 19.2 V DC ... 30 V DC (20 °C) |
Input voltage range in reference to UN | see diagram |
Typical input current at UN | 42 mA |
Typical response time | 13 ms |
Typical release time | 14 ms |
Coil voltage | 24 V DC |
Protective circuit | Freewheeling diode |
Operating voltage display | Yellow LED |
Switching | |
Contact type | 4 changeover contacts |
Type of switch contact | Single contact |
Drive and function | monostable |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 5 V (24 mA) |
Limiting continuous current | 6 A (see diagram) |
Maximum inrush current | 16 A (20 ms, N/O contacts) |
Min. switching current | 5 mA (24 V) |
Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
124 W (at 48 V DC) | |
108 W (at 60 V DC) | |
52 W (at 110 V DC) | |
48 W (at 220 V DC) | |
1500 VA (for 250 V AC) | |
Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact) |
DC13, 2 A/24 V (N/O contact) |
Connection method | Screw connection |
Stripping length | 8 mm |
Conductor cross section solid | 0.5 mm² ... 4 mm² |
Conductor cross-section solid (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.5 mm² ... 4 mm² |
0.5 mm² ... 4 mm² (Ferrule with plastic sleeve) | |
Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² |
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | |
Conductor cross section AWG | 20 ... 10 (solid) |
20 ... 12 (flexible) | |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Width | 27 mm |
Height | 89 mm |
Depth | 75 mm |
Flammability rating according to UL 94 | V2 (Housing) |
Ambient conditions | |
Degree of protection Relay base | IP20 (Relay base) |
Degree of protection Relay | RT I (Relay) |
Ambient temperature (operation) | -40 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Corrosive gas test | |
Identification | ISA-S71.04. G3 Harsh Group |
EN 60068-2-60 |
Standards/regulations | IEC 60947-5-1 |
Mounting type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting position | any |
Item number | 2903320 |
Packing unit | 10 pc |
Minimum order quantity | 1 pc |
Product Key | CK651A |
Catalog Page | Page 343 (C-5-2019) |
GTIN | 4046356732482 |
Weight per Piece (including packing) | 115.53 g |
Weight per Piece (excluding packing) | 115 g |
Customs tariff number | 85364190 |
Country of origin | CN |