Bộ lập trình điều khiển PLC - Siemens - SIMATIC S7-1200, CPU 1212C 6ES7212-1BD30-0XB0


Product
Article Number (Market Facing Number) 6ES7212-1BD30-0XB0
Product Description ***Spare part*** SIMATIC S7-1200, CPU 1212C, compact CPU, AC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 25 KB
Product family Not available
Product Lifecycle (PLM) PM410:Product cancellation
PLM Effective Date Product is cancelled since: 18.09.2012
Notes For this product a successor is available6ES7212-1BE31-0XB0
This product is a Spare Part, please visit the Spares & Service section for more information
If you need assistance please contact our local Siemens office
Successor information
Successor 6ES7212-1BE31-0XB0
Successor Description SIMATIC S7-1200, CPU 1212C, compact CPU, AC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 50 KB
Price data
Price Group 2AP
List Price Show prices
Customer Price Show prices
Surcharge for Raw Materials None
Metal Factor None
Delivery information
Export Control Regulations ECCN : EAR99H / AL : N
Standard lead time ex-works 1 Day/Days
Net Weight (kg) 0,398 Kg
Product Dimensions (W x L x H) Not available
Packaging Dimension 10,40 x 10,60 x 8,70
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1
Additional Product Information
EAN 6940408100299
UPC 040892549980
Commodity Code 85371091
LKZ_FDB/ CatalogID ST9-E5
Product Group 9040
Country of origin China
Compliance with the substance restrictions according to RoHS directive Since: 10.06.2009
Product class D: products made to order / customer's specifications, requiring engineering services, which cannot be re-used or utilized (design to customer)
WEEE (2012/19/EU) Take-Back Obligation No
Classifications
  Not available
 


 
General information
Product type designation CPU 1212C AC/DC/relay
Engineering with
● Programming package STEP 7 V10.5 or higher
Supply voltage
Rated value (AC)  
● 120 V AC Yes
● 230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
● permissible range, lower limit 47 Hz
● permissible range, upper limit 63 Hz
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 5 V
● permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 80 mA at 120 V AC; 40 mA at 240 V AC
Current consumption, max. 240 mA at 120 V AC; 120 mA at 240 V AC
Inrush current, max. 20 A; at 264 V
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Permissible range: 20.4V to 28.8V
Power loss
Power loss, typ. 11 W
Memory
Work memory
● integrated 25 kbyte
● expandable No
Load memory
● integrated 1 Mbyte
● Plug-in (SIMATIC Memory Card), max. 24 Mbyte; with SIMATIC memory card
Backup
● present Yes; Entire project maintenance-free in the integral EEPROM
● without battery Yes
CPU processing times
for bit operations, typ. 0.1 µs; / Operation
for word operations, typ. 12 µs; / Operation
for floating point arithmetic, typ. 18 µs; / Operation
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 2 048 byte
Flag
● Number, max. 4 kbyte; Size of bit memory address area
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 240 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological functions 4; HSC (High Speed Counting)
Source/sink input Yes
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Single phase: 3 at 100 kHz & 1 at 30 kHz, differential: 3 at 80 kHz & 1 at 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 6; Relays
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max. 10 ms; max.
● "1" to "0", max. 10 ms; max.
Switching frequency
● of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
● Number of relay outputs 6
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Protocols
● PROFINET IO Controller Yes
Protocols
Supports protocol for PROFINET IO No
PROFIBUS No
AS-Interface No
Protocols (Ethernet)
● TCP/IP Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
Web server
● supported Yes
● User-defined websites Yes
Further protocols
● MODBUS No
Communication functions
S7 communication
● supported Yes
● as server Yes
Number of connections
● overall 15; dynamically
Test commissioning functions
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
● Forcing Yes
Integrated Functions
Number of counters 4
Counting frequency (counter) max. 100 kHz
Frequency measurement Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Potential separation
Potential separation digital inputs
● Potential separation digital inputs No
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs Yes; Relays
● between the channels No
● between the channels, in groups of 2
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes
● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5 Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
Degree of protection acc. to EN 60529  
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. 0 °C
● max. 55 °C
● horizontal installation, min. 0 °C
● horizontal installation, max. 55 °C
● vertical installation, min. 0 °C
● vertical installation, max. 45 °C
● permissible temperature change 5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 2 000 m
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-6 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● adjustable Yes
Dimensions
Width 90 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 425 g
last modified: 01/31/2019

- Download Tài liệu kỹ thuật datasheet Bộ lập trình điều khiển PLC - Siemens - SIMATIC S7-1200, CPU 1212C 6ES7212-1BD30-0XB0


Sản phẩm cùng loại
Circuit Breakers (CB) hoạt động thế nào?
Bộ ngắt điện hay còn gọi là máy cắt (Circuit breaker-CB) là thiết bị được thiết kế để bảo vệ một mạch điện khỏi bị hư hỏng gây ra bởi dòng điện
Tụ chống sét Varistor (MOVs)là gì? Nguyên lý hoạt động (Wiki)Tụ chống sét ( Varistor hoặc Metal Varistor Oxit (MOV)) là một điện trở đặc biệt được sử dụng để bảo vệ mạch điện chống lại sự đột biến điện áp
Hãy xem RCCB và ELCB cứu bạn thoát chết vì điện giựt thế nào!Hãy xem tầm qua trong của RCCB và ELCB trong việc cứu nạn nhân bị điện giựt thoát chết như thế nào..
Programmable logic controller
A programmable logic controller (PLC), or programmable controller is an industrial digital computer which has been ruggedisedand adapted for the control of
White paper về Lý thuyết điều khiển tự độngLý thuyết điều khiển tự động là một nhánh liên ngành của kỹ thuật và toán học, liên quan đến hành vi của
Hướng dẫn Lập trình PLC chi tiết cho người mới tìm hiểu (Part 1)Điều khiển quá trình (PLC) được sử dụng rộng rãi trong công nghiệp và cho phép sản xuất hàng loạt các sản phẩm phù hợp với các
Sensors In Agriculture (Comming soon)Sensors In Agriculture. Soil moisture sensors, Agricultural temperature sensors, GPS sensors, Weather sensors, Crop health sensors, Electronic sensors, Light
10 Dự báo về Internet Of Things (IoT) năm 2018Trong một báo cáo mới, dự đoán năm 2018: IoT chuyển từ thử nghiệm sang kinh doanh quy mô, Forrester Research dự đoán rằng IoT sẽ trở thành xương sống của
Top 15 Loại cảm biến Sensor được dùng nhiều trong các thiết bị IoTNền tảng IoT hoạt động và cung cấp các dạng thông minh và dữ liệu có giá trị với việc sử dụng nhiều cảm biến khác nhau. Chúng phục vụ để thu
Năng lượng tương lai: Photovoltaic hay Hydrogen?Hydrogen là một nguyên tố chiếm tỷ lệ cao nhất so với tất cả các nguyên tố khác trên địa cầu. Nhưng hydrogen không hiện diện dưới dạng nguyên tử hay
Năng lượng tái tạo : Một loại ắc quy mới nhiều hứa hẹnNăng lượng tái tạo như điện gió và điện mặt trời có một nhược điểm căn bản, đó là không ổn định. Chúng chỉ vận hành khi có
Chất thải từ người là năng lượng tương lai?BBC Future - Hành tinh của chúng ta gặp một vấn đề. Con người, như tất cả các sinh vật sống khác, thải ra rất nhiều những chất thải không dễ chịu
Tin vui cho phái đẹp: Robot Spermbot có thể giúp điều trị ung thư cổ tử cungKhi robot sinh học này phát hiện ra khối u, bốn cánh tay trên cấu trúc vi mô tự động uốn cong, giải phóng tế bào tinh trùng, xâm
Tương lai nào cho trí tuệ nhân tạo - Artificial intelligence (AI)?
Trí thông minh nhân tạo (AI) là khả năng của một chương trình máy tính hoặc một máy tính để suy nghĩ và học hỏi. Nó
Bạn Biết Có Bao Nhiêu Loại Robot - ROBOTPARK
Các loại Robot là gì? Dưới đây là các loại robot của hệ thống vận động. Chúng tôi sẽ kiểm tra các loại này một cách
Gọi điện thoại