| General information | ||
| Product type designation | CPU 1517-3 PN/DP | |
| HW functional status | FS06 | |
| Firmware version | V2.6 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated as of version | V15.1 (FW V2.6) / V13 Update 3 (FW V1.6) or higher | |
| Configuration control | ||
| via dataset | Yes | |
| Display | ||
| Screen diagonal [cm] | 6.1 cm | |
| Control elements | ||
| Number of keys | 6 | |
| Mode selector switch | 1 | |
| Supply voltage | ||
| Type of supply voltage | 24 V DC | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Mains buffering | ||
| ● Mains/voltage failure stored energy time | 5 ms | |
| ● Repeat rate, min. | 1/s | |
| Input current | ||
| Current consumption (rated value) | 1.55 A | |
| Inrush current, max. | 2.4 A; Rated value | |
| I²t | 0.02 A²·s | |
| Power | ||
| Infeed power to the backplane bus | 12 W | |
| Power consumption from the backplane bus (balanced) | 30 W | |
| Power loss | ||
| Power loss, typ. | 24 W | |
| Memory | ||
| Number of slots for SIMATIC memory card | 1 | |
| SIMATIC memory card required | Yes | |
| Work memory | ||
| ● integrated (for program) | 2 Mbyte | |
| ● integrated (for data) | 8 Mbyte | |
| Load memory | ||
| ● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
| Backup | ||
| ● maintenance-free | Yes | |
| CPU processing times | ||
| for bit operations, typ. | 2 ns | |
| for word operations, typ. | 3 ns | |
| for fixed point arithmetic, typ. | 3 ns | |
| for floating point arithmetic, typ. | 12 ns | |
| CPU-blocks | ||
| Number of elements (total) | 12 000; Blocks (OB, FB, FC, DB) and UDTs | |
| DB | ||
| ● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
| ● Size, max. | 8 Mbyte; For DBs with absolute addressing, the max. size is 64 KB | |
| FB | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 1 Mbyte | |
| FC | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 1 Mbyte | |
| OB | ||
| ● Size, max. | 1 Mbyte | |
| ● Number of free cycle OBs | 100 | |
| ● Number of time alarm OBs | 20 | |
| ● Number of delay alarm OBs | 20 | |
| ● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 100 µs | |
| ● Number of process alarm OBs | 50 | |
| ● Number of DPV1 alarm OBs | 3 | |
| ● Number of isochronous mode OBs | 3 | |
| ● Number of technology synchronous alarm OBs | 2 | |
| ● Number of startup OBs | 100 | |
| ● Number of asynchronous error OBs | 4 | |
| ● Number of synchronous error OBs | 2 | |
| ● Number of diagnostic alarm OBs | 1 | |
| Nesting depth | ||
| ● per priority class | 24 | |
| Counters, timers and their retentivity | ||
| S7 counter | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC counter | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| S7 times | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC timer | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| Data areas and their retentivity | ||
| Retentive data area (incl. timers, counters, flags), max. | 768 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 700 KB | |
| Extended retentive data area (incl. timers, counters, flags), max. | 8 Mbyte; When using PS 6 0W 24/48/60 V DC HF | |
| Flag | ||
| ● Number, max. | 16 kbyte | |
| ● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte | |
| Data blocks | ||
| ● Retentivity adjustable | Yes | |
| ● Retentivity preset | No | |
| Local data | ||
| ● per priority class, max. | 64 kbyte; max. 16 KB per block | |
| Address area | ||
| Number of IO modules | 16 384; max. number of modules / submodules | |
| I/O address area | ||
| ● Inputs | 32 kbyte; All inputs are in the process image | |
| ● Outputs | 32 kbyte; All outputs are in the process image | |
| per integrated IO subsystem | ||
| — Inputs (volume) | 16 kbyte; 16 KB via the integrated PROFINET IO interface X1, 8 KB via the integrated PROFINET IO interface X2 and via the integrated PROFIBUS DP interface | |
| — Outputs (volume) | 16 kbyte; 16 KB via the integrated PROFINET IO interface X1, 8 KB via the integrated PROFINET IO interface X2 and via the integrated PROFIBUS DP interface | |
| per CM/CP | ||
| — Inputs (volume) | 8 kbyte | |
| — Outputs (volume) | 8 kbyte | |
| Subprocess images | ||
| ● Number of subprocess images, max. | 32 | |
| Hardware configuration | ||
| Number of distributed IO systems | 64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) | |
| Number of DP masters | ||
| ● integrated | 1 | |
| ● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
| Number of IO Controllers | ||
| ● integrated | 2 | |
| ● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
| Rack | ||
| ● Modules per rack, max. | 32; CPU + 31 modules | |
| ● Number of lines, max. | 1 | |
| PtP CM | ||
| ● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots | |
| Time of day | ||
| Clock | ||
| ● Type | Hardware clock | |
| ● Backup time | 6 wk; At 40 °C ambient temperature, typically | |
| ● Deviation per day, max. | 10 s; Typ.: 2 s | |
| Operating hours counter | ||
| ● Number | 16 | |
| Clock synchronization | ||
| ● supported | Yes | |
| ● to DP, master | Yes | |
| ● in AS, master | Yes | |
| ● in AS, slave | Yes | |
| ● on Ethernet via NTP | Yes | |
| Interfaces | ||
| Number of PROFINET interfaces | 2 | |
| Number of PROFIBUS interfaces | 1 | |
| 1. Interface | ||
| Interface types | ||
| ● Number of ports | 2 | |
| ● integrated switch | Yes | |
| ● RJ 45 (Ethernet) | Yes; X1 | |
| Protocols | ||
| ● IP protocol | Yes; IPv4 | |
| ● PROFINET IO Controller | Yes | |
| ● PROFINET IO Device | Yes | |
| ● SIMATIC communication | Yes | |
| ● Open IE communication | Yes | |
| ● Web server | Yes | |
| ● Media redundancy | Yes; MRP Automanager according to IEC 62439-2 Edition 2.0 | |
| PROFINET IO Controller | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | Yes | |
| — Open IE communication | Yes | |
| — IRT | Yes | |
| — MRP | Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 | |
| — MRPD | Yes; Requirement: IRT | |
| — PROFIenergy | Yes | |
| — Prioritized startup | Yes; Max. 32 PROFINET devices | |
| — Number of connectable IO Devices, max. | 512; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET | |
| — Of which IO devices with IRT, max. | 64 | |
| — Number of connectable IO Devices for RT, max. | 512 | |
| — of which in line, max. | 512 | |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces | |
| — Number of IO Devices per tool, max. | 8 | |
| — Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data | |
| Update time for IRT | ||
| — for send cycle of 250 µs | 250 µs to 4 ms | |
| — for send cycle of 500 µs | 500 µs to 8 ms | |
| — for send cycle of 1 ms | 1 ms to 16 ms | |
| — for send cycle of 2 ms | 2 ms to 32 ms | |
| — for send cycle of 4 ms | 4 ms to 64 ms | |
| — With IRT and parameterization of "odd" send cycles | Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) | |
| Update time for RT | ||
| — for send cycle of 250 µs | 250 µs to 128 ms | |
| — for send cycle of 500 µs | 500 µs to 256 ms | |
| — for send cycle of 1 ms | 1 ms to 512 ms | |
| — for send cycle of 2 ms | 2 ms to 512 ms | |
| — for send cycle of 4 ms | 4 ms to 512 ms | |
| PROFINET IO Device | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | No | |
| — Open IE communication | Yes | |
| — IRT | Yes | |
| — MRP | Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 | |
| — MRPD | Yes; Requirement: IRT | |
| — PROFIenergy | Yes | |
| — Shared device | Yes | |
| — Number of IO Controllers with shared device, max. | 4 | |
| — Asset management record | Yes; Per user program | |
| 2. Interface | ||
| Interface types | ||
| ● Number of ports | 1 | |
| ● integrated switch | No | |
| ● RJ 45 (Ethernet) | Yes; X2 | |
| Protocols | ||
| ● IP protocol | Yes; IPv4 | |
| ● PROFINET IO Controller | Yes | |
| ● PROFINET IO Device | Yes | |
| ● SIMATIC communication | Yes | |
| ● Open IE communication | Yes | |
| ● Web server | Yes | |
| ● Media redundancy | No | |
| PROFINET IO Controller | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | No | |
| — Open IE communication | Yes | |
| — IRT | No | |
| — MRP | No | |
| — MRPD | No | |
| — PROFIenergy | Yes | |
| — Prioritized startup | No | |
| — Number of connectable IO Devices, max. | 128; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET | |
| — Number of connectable IO Devices for RT, max. | 128 | |
| — of which in line, max. | 128 | |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces | |
| — Number of IO Devices per tool, max. | 8 | |
| — Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data | |
| Update time for RT | ||
| — for send cycle of 1 ms | 1 ms to 512 ms | |
| PROFINET IO Device | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | No | |
| — Open IE communication | Yes | |
| — IRT | No | |
| — MRP | No | |
| — MRPD | No | |
| — PROFIenergy | Yes | |
| — Prioritized startup | No | |
| — Shared device | Yes | |
| — Number of IO Controllers with shared device, max. | 4 | |
| — Asset management record | Yes; Per user program | |
| 3. Interface | ||
| Interface types | ||
| ● Number of ports | 1 | |
| ● RS 485 | Yes; X3 | |
| Protocols | ||
| ● PROFIBUS DP master | Yes | |
| ● PROFIBUS DP slave | No | |
| ● SIMATIC communication | Yes | |
| Interface types | ||
| RJ 45 (Ethernet) | ||
| ● 100 Mbps | Yes | |
| ● Autonegotiation | Yes | |
| ● Autocrossing | Yes | |
| ● Industrial Ethernet status LED | Yes | |
| RS 485 | ||
| ● Transmission rate, max. | 12 Mbit/s | |
| Protocols | ||
| Number of connections | ||
| ● Number of connections, max. | 320; via integrated interfaces of the CPU and connected CPs / CMs | |
| ● Number of connections reserved for ES/HMI/web | 10 | |
| ● Number of connections via integrated interfaces | 160 | |
| ● Number of S7 routing paths | 64; in total, only 16 S7-Routing connections are supported via PROFIBUS | |
| Redundancy mode | ||
| ● H-Sync forwarding | Yes | |
| SIMATIC communication | ||
| ● S7 communication, as server | Yes | |
| ● S7 communication, as client | Yes | |
| ● User data per job, max. | See online help (S7 communication, user data size) | |
| Open IE communication | ||
| ● TCP/IP | Yes | |
| — Data length, max. | 64 kbyte | |
| — several passive connections per port, supported | Yes | |
| ● ISO-on-TCP (RFC1006) | Yes | |
| — Data length, max. | 64 kbyte | |
| ● UDP | Yes | |
| — Data length, max. | 2 kbyte; 1 472 bytes for UDP broadcast | |
| — UDP multicast | Yes; Max. 5 multicast circuits | |
| ● DHCP | No | |
| ● SNMP | Yes | |
| ● DCP | Yes | |
| ● LLDP | Yes | |
| Web server | ||
| ● HTTP | Yes; Standard and user pages | |
| ● HTTPS | Yes; Standard and user pages | |
| PROFIBUS DP master | ||
| ● Number of connections, max. | 48; for the integrated PROFIBUS DP interface | |
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Data record routing | Yes | |
| — Isochronous mode | Yes | |
| — Equidistance | Yes | |
| — Number of DP slaves | 125; In total, up to 1 000 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET | |
| — Activation/deactivation of DP slaves | Yes | |
| OPC UA | ||
| ● Runtime license required | Yes | |
| ● OPC UA client | Yes | |
| — Application authentication | Yes | |
| — Security policies | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | |
| — User authentication | "anonymous" or by user name & password | |
| — Number of connections, max. | 40 | |
| — Number of nodes of the client interfaces, max. | 5 000 | |
| — Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max. | 300 | |
| — Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max. | 20 | |
| — Number of elements for one call of OPC_UA_MethodGetHandleList, max. | 100 | |
| — Number of simultaneous calls of the client instructions per connection (except OPC_UA_ReadList,OPC_UA_WriteList,OPC_UA_MethodCall), max. | 1 | |
| — Number of simultaneous calls of the client instructions OPC_UA_ReadList,OPC_UA_WriteList and OPC_UA_MethodCall, max. | 5 | |
| — Number of registerable nodes, max. | 5 000 | |
| — Number of registerable method calls of OPC_UA_MethodCall, max. | 100 | |
| — Number of inputs/outputs when calling OPC_UA_MethodCall, max. | 20 | |
| ● OPC UA server | Yes; Data access (read, write, subscribe), method call, custom address space | |
| — Application authentication | Yes | |
| — Security policies | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | |
| — User authentication | "anonymous" or by user name & password | |
| — Number of sessions, max. | 64 | |
| — Number of accessible variables, max. | 200 000 | |
| — Number of registerable nodes, max. | 50 000 | |
| — Number of subscriptions per session, max. | 20 | |
| — Sampling time, min. | 10 ms | |
| — Send time, min. | 10 ms | |
| — Number of server methods, max. | 100 | |
| — Number of inputs/outputs per server method, max. | 20 | |
| — Number of monitored items, max. | 10 000; For 1 s sampling interval and 1 s send interval | |
| — Number of server interfaces, max. | 10 | |
| — Number of nodes for user-defined server interfaces, max. | 30 000 | |
| Further protocols | ||
| ● MODBUS | Yes; MODBUS TCP | |
| Media redundancy | ||
| ● Switchover time on line break, typ. | 200 ms; For MRP, bumpless for MRPD | |
| ● Number of stations in the ring, max. | 50 | |
| Isochronous mode | ||
| Isochronous operation (application synchronized up to terminal) | Yes; Distributed and central; with minimum OB 6x cycle of 250 µs (distributed) and 1 ms (central) | |
| Equidistance | Yes | |
| S7 message functions | ||
| Number of login stations for message functions, max. | 32 | |
| Program alarms | Yes | |
| Number of configurable program messages, max. | 10 000; Program messages are generated by the "Program_Alarm" block, ProDiag or GRAPH | |
| Number of loadable program messages in RUN, max. | 5 000 | |
| Number of simultaneously active program alarms | ||
| ● Number of program alarms | 1 000 | |
| ● Number of alarms for system diagnostics | 200 | |
| ● Number of alarms for motion technology objects | 160 | |
| Test commissioning functions | ||
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 10 engineering systems | |
| Status block | Yes; Up to 16 simultaneously (in total across all ES clients) | |
| Single step | No | |
| Number of breakpoints | 20 | |
| Status/control | ||
| ● Status/control variable | Yes | |
| ● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
| ● Number of variables, max. | ||
| — of which status variables, max. | 200; per job | |
| — of which control variables, max. | 200; per job | |
| Forcing | ||
| ● Forcing, variables | Peripheral inputs/outputs | |
| ● Number of variables, max. | 200 | |
| Diagnostic buffer | ||
| ● present | Yes | |
| ● Number of entries, max. | 3 200 | |
| — of which powerfail-proof | 1 000 | |
| Traces | ||
| ● Number of configurable Traces | 8; Up to 512 KB of data per trace are possible | |
| Interrupts/diagnostics/status information | ||
| Diagnostics indication LED | ||
| ● RUN/STOP LED | Yes | |
| ● ERROR LED | Yes | |
| ● MAINT LED | Yes | |
| ● Connection display LINK TX/RX | Yes | |
| Supported technology objects | ||
| Motion Control | Yes; Note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER | |
| ● Number of available Motion Control resources for technology objects (except cam disks) | 10 240 | |
| ● Required Motion Control resources | ||
| — per speed-controlled axis | 40 | |
| — per positioning axis | 80 | |
| — per synchronous axis | 160 | |
| — per external encoder | 80 | |
| — per output cam | 20 | |
| — per cam track | 160 | |
| — per probe | 40 | |