Bộ lưu điện UPS DC 24V 40A USB Phoenix Contact QUINT4-UPS/24DC/24DC/40/USB - 2907078
QUINT USV, IQ Technology, USB (Modbus/RTU), DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 40 A, charging current: 5 A
Product description
The intelligent QUINT UPS for integration into established industrial networks: your systems continue to be supplied with uninterrupted power, even in the event of a mains failure. The battery management system with IQ Technology and a powerful battery charger ensures superior system availability.
Technical data
Input data
| Input voltage |
24 V DC |
| Input voltage range |
18 V DC ... 30 V DC |
| 18 V DC ... 32 V DC |
| Electric strength, max. |
35 V DC |
| Internal input fuse |
no |
| Voltage type of supply voltage |
DC |
| Inrush current |
≤ 9 A (≤ 4 ms) |
| Reverse polarity protection |
yes |
| Fixed backup threshold |
22 V DC |
| Dynamic activation threshold |
> 1 V / 100 ms |
| Switch-on time |
max. 3 s |
| Switch-on time during battery operation (Bat.-Start) |
8 s |
| Voltage drop, input/output |
0.5 V DC |
| Current consumption IN (UN, IOUT = IN, Icharge = 0) |
40.1 A |
| Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max) |
51.2 A |
| Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) |
50 mA |
| Current consumption Icharge (UN, IOUT = 0, Icharge = max) |
6.1 A |
| Power consumption PN (UN, IOUT = IN, Icharge = 0) |
965 W |
| Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) |
1120 W |
| Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) |
1.3 W |
| Power consumption Pcharge (UN, IOUT = 0, Icharge = max) |
147 W |
Output data
| Efficiency |
typ. 98 % |
| Number of outputs |
1 |
| Nominal output current (IN) |
40 A (-25 °C ... 50 °C) |
| Short-circuit-proof |
yes |
| No-load proof |
yes |
| Switch-over time |
0 ms |
| Output current limit |
In mains mode according to connected upstream current limiting device |
| > 45 A (Battery operation) |
| Power dissipation |
2.8 W (Mains operation) |
| 13 W (Mains operation) |
| 3.51 W (Battery operation) |
| 16.4 W (Battery operation) |
| UPS connection in parallel |
no |
| UPS connection in series |
no |
| Energy storage device connection in parallel |
Yes, 5 (observe line protection) |
| Energy storage device connection in series |
no |
| Mains operation |
| Output voltage |
24 V DC (UOUT = UIN - 0.5 V DC) |
| Output voltage range |
18 V DC ... 30 V DC |
| 18 V DC ... 32 V DC |
| Output current IN |
40 A |
| Static Boost (IStat.Boost) |
45 A |
| Dynamic Boost (IDyn.Boost) |
60 A (5 s) |
| Selective Fuse Breaking (ISFB) |
215 A (15 ms) |
| Output power POUT (UN, IOUT = IN) |
960 W |
| Output power POUT (UN, IOUT = Istat.Boost) |
1080 W |
| Battery operation |
| Output voltage |
24 V DC (UOUT = UBAT - 0.5 V DC) |
| Output voltage range |
19 V DC ... 32 V DC |
| Output current IN |
40 A |
| Static Boost (IStat.Boost) |
45 A |
| Dynamic Boost (IDyn.Boost) |
60 A (5 s) |
| Selective Fuse Breaking (ISFB) |
215 A (15 ms) |
| Output power POUT (UN, IOUT = IN) |
960 W |
| Output power POUT (UN, IOUT = Istat.Boost) |
1080 W |
Energy storage
| End-of-charge voltage |
32 V DC |
| End-of-charge voltage (temperature-compensated) |
25 V DC ... 32 V DC |
| Charging current (configurable) |
5 A |
| Nominal capacity (without additional charger) |
7 Ah ... 100 Ah |
| Max. capacity |
135 Ah |
| Charging time |
202.5 h |
| Buffer time |
45 min. (38 Ah) |
| Deep discharge protection |
19.2 V DC |
| Battery technology |
VRLA, VRLA-WTR, LI-ION |
| Charge characteristic curve |
IU0U |
| IQ-Technology |
yes |
| Temperature sensor |
yes |
| Temperature compensation (configurable) |
42 mV/K |
Interfaces
| Communication |
| Slave address |
192 |
| Start bit |
1 |
| Data bits |
8 |
| Parity |
even |
| Stop bit |
1 |
| Interface |
USB (Modbus/RTU) |
| Number of interfaces |
1 |
| Connection method |
MINI-USB Type B |
| Connection marking |
X1 |
| Locking |
Screw |
| Transmission physics |
USB 2.0 |
| Topology |
Point-to-point |
| Transmission speed |
9600 baud ... 115200 baud (Default: 115200 baud) |
| Transmission length |
max. 5 m |
| Access time |
≤ 2 s |
| Supported protocols |
Modbus/RTU |
| Chipset |
Silicon Labs CP210x |
| Electrical isolation |
Yes, UL approved |
Signaling
| LED signaling |
| Types of signaling |
DC OK (green) |
| Alarm (red) |
| Bat.-Mode (yellow) |
| SOC (red, green) |
| Data (red, green) |
Product properties
| Product type |
DC UPS |
| Product family |
QUINT USV |
| MTBF (IEC 61709, SN 29500) |
> 1376000 h (25 °C) |
| > 888400 h (40 °C) |
| > 467600 h (60 °C) |
| Environmental protection directive |
RoHS Directive 2011/65/EU |
| WEEE |
| Reach |
| Insulation characteristics |
| Protection class |
III (without PE) |
| Degree of pollution |
2 |
| Life expectancy (electrolytic capacitors) |
| Time |
126720 h |
Dimensions
| Item dimensions |
| Width |
47 mm |
| Height |
130 mm |
| Depth |
125 mm |
| Item dimensions with alternative mounting |
| Width |
123 mm |
| Height |
130 mm |
| Depth |
49 mm |
| Installation dimensions |
| Installation distance right/left (active) |
5 mm / 5 mm (POut ≥50% ) |
| Installation distance right/left (passive) |
0 mm / 0 mm (POut ≥50% ) |
| Installation distance right/left (active, passive) |
0 mm / 0 mm (POut ≤50 %) |
| Installation distance top/bottom (active) |
50 mm / 50 mm (POut ≥50% ) |
| Installation distance top/bottom (passive) |
40 mm / 20 mm (POut ≥50% ) |
| Installation distance top/bottom (active, passive) |
40 mm / 20 mm (POut ≤50 %) |
Mounting
| Mounting type |
DIN rail mounting |
| Mounting position |
On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
Material specifications
| Flammability rating according to UL 94 (housing / terminal blocks) |
V0 |
| Housing material |
Metal |
| Hood version |
Stainless steel X6Cr17 |
| Side element version |
Aluminum AlMg3 |
Environmental and real-life conditions
| Ambient conditions |
| Degree of protection |
IP20 |
| Ambient temperature (operation) |
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
| Ambient temperature (start-up type tested) |
-40 °C |
| Maximum altitude |
≤ 4000 m |
| Climatic class |
3K3 (EN 60721) |
| Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
| Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) |
2.3g |
Standards and regulations
| Protective extra-low voltage |
| Standard designation |
Protective extra-low voltage |
| Standards/specifications |
IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) |
Approvals
| UL approval |
| Identification |
UL/C-UL Listed UL 61010-1 |
| UL approval |
| Identification |
UL/C-UL Listed UL 61010-2-201 |
| UL approval |
| Identification |
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
| CSA |
| Identification |
CAN/CSA-C22.2 No. 61010-1-12 |
| CSA |
| Identification |
CAN/CSA-IEC 61010-2-201 |
| CSA |
| Identification |
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
| CB scheme |
| Identification |
IEC 61010-1 |
| IEC 61010-2-201 |
| DNV |
| Identification |
Class Guideline DNVGL-CG-0339 |
| Note |
Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B |
EMC data
| Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
| EMC requirements for noise emission |
EN 61000-6-3 |
| EN 61000-6-4 |
| EMC requirements for noise immunity |
EN 61000-6-1 |
| EN 61000-6-2 |
| Noise immunity |
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
| Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
| Noise emission |
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
| Electrostatic discharge |
| Standards/regulations |
EN 61000-4-2 |
| Electrostatic discharge |
| Contact discharge |
8 kV (Test Level 4) |
| Discharge in air |
15 kV (Test Level 4) |
| Comments |
Criterion B |
| Electromagnetic HF field |
| Standards/regulations |
EN 61000-4-3 |
| Electromagnetic HF field |
| Frequency range |
80 MHz ... 1 GHz |
| Test field strength |
20 V/m (Test Level 3) |
| Frequency range |
1 GHz ... 6 GHz |
| Test field strength |
10 V/m (Test Level 3) |
| Frequency range |
1 GHz ... 6 GHz |
| Test field strength |
10 V/m (Test Level 3) |
| Comments |
Criterion A |
| Fast transients (burst) |
| Standards/regulations |
EN 61000-4-4 |
| Fast transients (burst) |
| Input |
4 kV (Test Level 4 - asymmetrical) |
| Output |
4 kV (Test Level 4 - asymmetrical) |
| Signal |
4 kV (Test Level 4 - asymmetrical) |
| Comments |
Criterion B |
| Surge voltage load (surge) |
| Standards/regulations |
EN 61000-4-5 |
| Input |
1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) |
| Output |
1 kV (Test Level 3 - symmetrical) |
| 2 kV (Test Level 3 - asymmetrical) |
| Signal |
1 kV (Test Level 2 - asymmetrical) |
| Comments |
Criterion B |
| Conducted interference |
| Standards/regulations |
EN 61000-4-6 |
| Conducted interference |
| I/O/S |
asymmetrical |
| Frequency range |
0.15 MHz ... 80 MHz |
| Comments |
Criterion A |
| Voltage |
10 V (Test Level 3) |
| Power frequency magnetic field |
| Standards/regulations |
EN 61000-4-8 |
| Frequency |
16.67 Hz |
| 50 Hz |
| 60 Hz |
| Test field strength |
100 A/m |
| Additional text |
60 s |
| Comments |
Criterion A |
| Frequency |
50 Hz |
| 60 Hz |
| Frequency range |
50 Hz ... 60 Hz |
| Test field strength |
1 kA/m |
| Additional text |
3 s |
| Frequency |
0 Hz |
| Test field strength |
300 A/m |
| Additional text |
DC, 60 s |
| Criteria |
| Criterion A |
Normal operating behavior within the specified limits. |
| Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Commercial data
| Item number |
2907078 |
| Packing unit |
1 pc |
| Minimum order quantity |
1 pc |
| Product key |
CMUI43 |
| Catalog page |
Page 323 (C-4-2019) |
| GTIN |
4055626170046 |
| Weight per piece (including packing) |
746.6 g |
| Weight per piece (excluding packing) |
740 g |
| Customs tariff number |
85371091 |
| Country of origin |
CN |
Classifications
ECLASS
| ECLASS-11.0 |
27040705 |
| ECLASS-12.0 |
27040705 |
| ECLASS-13.0 |
27040705 |
ETIM
UNSPSC
Approvals
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
Approval ID: FILE E 123528
cUL Listed
Approval ID: FILE E 123528
EAC
Approval ID: RU-DE.B.00184/20
ABS
Approval ID: 21-2174010-PDA
DNV
Approval ID: TAA00002K4
RINA
Approval ID: ELE382621XG
LR
Approval ID: LR21417906TA
NK
Approval ID: TA22372M
BV
Approval ID: 69394/A0 BV
KC
Approval ID: R-R-PCK-2907078
cUL Listed
Approval ID: FILE E 199827
UL Listed
Approval ID: FILE E 199827
cULus Listed
cULus Listed
Environmental product compliance
| |
| REACh SVHC |
Lead 7439-92-1 |
| |
| China RoHS |
Environmentally Friendly Use Period = 25; |
| For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
- Tài liệu kỹ thuật Phoenix Contact QUINT4-UPS/24DC/24DC/40/USB - 2907078
ở đây.
Compatible products
Energy storage
UPS-BAT/PB/24DC/7AH - 1274118
Energy storage
UPS-BAT/PB/24DC/12AH - 1274119
Energy storage
UPS-BAT/PB/24DC/20AH - 1348516
Energy storage
UPS-BAT/PB/24DC/40AH - 1354641
Energy storage
UPS-BAT/LI/24DC/128WH - 1396415
Energy storage
UPS-BAT/VRLA-WTR/24DC/13AH - 2320416
Energy storage
UPS-BAT/VRLA-WTR/24DC/26AH - 2320429
Configuration software
POWER MANAGEMENT SUITE - 1252232
Configuration software
UPS-CONF - 2320403
Data cable
MINI-SCREW-USB-DATACABLE - 2908217