Bộ PLC Siemens6ES7212-1BE31-0XB0 | CPU 1212C | AC/DC/relay 8DI 6DO 2AI

Bộ PLC Siemens6ES7212-1BE31-0XB0 | CPU 1212C | AC/DC/relay 8DI 6DO 2AI

930
Nhà sản xuất:

Siemens

;   

Xuất xứ: Germany

Giá sỉ:

Giá tốt nhất xem...0909186879 dienelectrics@gmail.com

Khuyến mãi:Có Discount
Bảo hành:12 Tháng (Chính hãng)
Thanh toán:C.O.D / Bảo lãnh TT / Link hoạt
Vận chuyển:Miễn phí Tp.HCM, vùng lân cận
Thông tin nổi bật

Siemens 6ES7212-1BE31-0XB0 | CPU 1212C là Bộ PLC, AC/DC/relay, 8DI 24VDC; 6DO relay 2A; 2AI 0-10VDC, Power supply 85-264VAC, Program/data memory 50KB

 
Product
Article Number (Market Facing Number) 6ES7212-1BE31-0XB0
Product Description SIMATIC S7-1200, CPU 1212C, compact CPU, AC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, Power supply: AC 85-264 V AC at 47-63 Hz, Program/data memory 50 KB
Product family Not available
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 01.10.2014
Notes Sucessor:Successor available: 6ES7212-1BE40-0XB0 (conditionally compatible)
Price data
Price Group 2AP
List Price Show prices
Customer Price Show prices
Surcharge for Raw Materials None
Metal Factor None
Delivery information
Export Control Regulations ECCN : EAR99H / AL : N
Standard lead time ex-works 5 Day/Days
Net Weight (kg) 0,401 Kg
Product Dimensions (W x L x H) Not available
Packaging Dimension 10,50 x 10,80 x 8,60
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1
Additional Product Information
EAN 6940408101364
UPC 040892996722
Commodity Code 85371091
LKZ_FDB/ CatalogID ST9.72
Product Group 9037
Country of origin China
Compliance with the substance restrictions according to RoHS directive Since: 16.09.2013
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back Obligation Yes
REACH Art. 33 Duty of Information
4,4'-isopropylidenediphen... > 0, 1 % (w / w)
Classifications
  Not available


 
General information
Product type designation CPU 1212C AC/DC/relay
Engineering with
● Programming package STEP 7 V11 SP2 or higher
Supply voltage
Rated value (AC)  
● 120 V AC Yes
● 230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
● permissible range, lower limit 47 Hz
● permissible range, upper limit 63 Hz
Input current
Current consumption (rated value) 80 mA at 120 V AC; 40 mA at 240 V AC
Inrush current, max. 20 A; at 264 V
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Permissible range: 20.4V to 28.8V
Power loss
Power loss, typ. 11 W
Memory
Work memory
● integrated 50 kbyte
● expandable No
Load memory
● integrated 1 Mbyte
Backup
● present Yes; maintenance-free
● without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.5 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 10 kbyte
Flag
● Number, max. 4 kbyte; Size of bit memory address area
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. 60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological functions 4; HSC (High Speed Counting)
Source/sink input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 6; Relays
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max. 10 ms; max.
● "1" to "0", max. 10 ms; max.
Switching frequency
● of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
● Number of relay outputs 6
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Protocols
● PROFINET IO Controller Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFIBUS Yes
AS-Interface Yes
Protocols (Ethernet)
● TCP/IP Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes
Further protocols
● MODBUS Yes
Communication functions
S7 communication
● supported Yes
● as server Yes
● as client Yes
Test commissioning functions
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
Integrated Functions
Number of counters 4
Counting frequency (counter) max. 100 kHz
Frequency measurement Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Potential separation
Potential separation digital inputs
● Potential separation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs Relays
● between the channels No
● between the channels, in groups of 2
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes
● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5 Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
Degree of protection acc. to EN 60529  
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 2 000 m
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-6 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● adjustable Yes
Dimensions
Width 90 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 425 g
last modified: 01/31/2019
 