Operating voltage |
198-264V AC 50/60Hz |
Rated load |
800W (Inductive), 1000W (Resistive) @230V AC |
HF system | 5.8GHz ±75MHz, ISM wave band |
Stand-by Power |
≤0.5W |
Transmitting power |
0.5mW Max. |
Detection zone Max.(D x H) | 6m x 15m |
Motion detection | 0.3~3m/s |
Detection angle | 150°(wall installation) 360°(ceiling installation) |
IP rating | IP20 |
Operation temperature |
-25℃…+60℃ |
Hold time |
5S/ 30S/ 90S/ 3min/ 20min/ 30min |
Detection Area |
100%/ 75%/ 50%/ 10% |
Daylight sensor |
2Lux/ 5Lux/ 10Lux/ 25Lux/ 50Lux/ 100Lux/ Disable |
Stand-by DIM Level |
25% (2.2-2.5V)/ 35% (3.0-3.5V)/ 50% (5.0-5.5V) |
Life time | 50,000 hours |
Guaranty | 5 years |
Detection Area
1 | 2 | ||
Ⅰ | ON | ON | 100% |
Ⅱ | ON | - | 75% |
Ⅲ | - | ON | 50% |
Ⅳ | - | - | 10% |
Hold Time
3 | 4 | 5 | ||
Ⅰ | ON | ON | ON | 5s |
Ⅱ | - | ON | ON | 30s |
Ⅲ | ON | - | ON | 90s |
Ⅳ | - | - | ON | 3min |
Ⅴ | ON | ON | - | 20min |
VI | - | - | - | 30min |
Stand-by Period
6 | 7 | 8 | ||
Ⅰ | ON | ON | ON | 0s |
Ⅱ | - | ON | ON | 5s |
Ⅲ | ON | - | ON | 5min |
Ⅳ | - | - | ON | 10min |
Ⅴ | ON | ON | - | 30min |
VI | - | ON | - | 60min |
VII | - | - | - | +∞ |
Stand-by Dim Level
1 | 2 | ||
Ⅰ | ON | ON | 50% |
Ⅱ | ON | - | 35% |
Ⅲ | - | - | 25% |
Daylight Sensor
1 | 2 | 3 | 4 | 5 | 6 | ||
Ⅰ | ON | ON | ON | ON | ON | ON | 2lux |
Ⅱ | - | ON | ON | ON | ON | ON | 5lux |
Ⅲ | ON | - | ON | ON | ON | ON | 15lux |
Ⅳ | ON | ON | - | ON | ON | ON | 25lux |
Ⅴ | ON | ON | ON | - | ON | ON | 50lux |
VI | ON | ON | ON | ON | - | ON | 100lux |
VII | ON | ON | ON | ON | ON | - | Disable* |
*Disable means the daylight sensor does not work. The sensor will turn on light once motion is detected regardless of ambient light level.
Đối với Model
.. thì điều khiển bằng Remote MH10. Hướng dẫn điều khiển Remote MH10 ở đây.
*The sensor is designed to connect one load only. Connect more than one load may damage the sensor.
1/ On/Off function
After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.
2/ 2-step dimming function
After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it dims the light to a low light level (set by stand-by dim level). During the initialization, the sensor is not able to detect movement.
3/ 3-step dimming function
After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.
Detection area: 100%, Hold Time: 5S,Daylight sensor: Disable, Detection mode: HS
1) The product can work with any kinds of control grear..
2) The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, High installation sensor MC083S RC Version: A0
3) The sensor mounted in a plastic, glass lampshade would reduce the sensitivity of the sensor. For every 3 mm increase in thickness, the sensitivity would reduce by 20%.
4) The sensing distance will be affected by the height of the sensor installation, the size of the object being detected, and the speed of movement.
5) Daylight the value is in a sunny environment with no shadows and ambient light diffuse reflection conditions. The values illumination detected by sensor may vary in different environment, at different times, in different seasons, and in different climates.
6) The parameters of the sensor may need to be reconfigured in different installation environments. Please refer to the following instructions or contact the manufacturer.
7) This sensor is for indoor use only. Outdoor use will affect the waterproof effect, wind and moving objects around would cause false triggering.
8) The distance between any inductive sensors should be greater than 3m.
9) When the sensor is installed in a metal illuminance , a metal reflective surface, or a narrow enclosed environment, the microwave will be reflected repeatedly and cause false triggering. Please reduce the sensitivity or contact the manufacturer for technical support.
10) Do not place the sensor close to high-density objects such as metal, glass, mixed-use walls, etc. The sensor may be triggered by mistake.
11) Please ensure that there are no moving signals around the sensor, such as fan, DC motor, sewer, air outlet, etc., the sensor may generate false triggers.
Car park, etc