IEC test classification |
B2 |
|
C1 |
|
C2 |
|
C3 |
|
D1 |
Maximum continuous voltage UC |
185 V DC |
|
130 V AC |
Rated current |
≤ 380 mA (25 °C) |
Operating effective current IC at UC |
≤ 6 µA |
Residual current IPE |
≤ 4 µA |
Nominal discharge current In (8/20) µs (Core-Core) |
≤ 5 kA |
Nominal discharge current In (8/20) µs (core-earth) |
≤ 5 kA |
Total discharge current Itotal (8/20) µs |
10 kA |
Nominal pulse current Ian (10/1000) µs (Core-Core) |
100 A |
Nominal pulse current Ian (10/1000) µs (Core-Earth) |
100 A |
Nominal pulse current Ian (10/700) µs (Core-Core) |
150 A |
Nominal pulse current Ian (10/700) µs (Core-Earth) |
150 A |
Output voltage limitation at 1 kV/µs (core-core) static |
≤ 250 V |
Output voltage limitation at 1 kV/µs (core-earth) static |
≤ 250 V |
Residual voltage at In (conductor-conductor) |
≤ 120 V |
Residual voltage at In (conductor-ground) |
≤ 120 V |
Voltage protection level Up (core-core) |
≤ 250 V (B2 - 4 kV / 100 A) |
|
≤ 250 V (C1 - 1 kV/500 A) |
|
≤ 250 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (core-ground) |
≤ 250 V (B2 - 4 kV / 100 A) |
|
≤ 250 V (C1 - 1 kV/500 A) |
|
≤ 250 V (C2 - 10 kV / 5 kA) |
Response time tA (core-core) |
≤ 100 ns |
Response time tA (core-earth) |
≤ 100 ns |
Input attenuation aE, sym. |
typ. 0.5 dB (≤ 5 MHz / 100 Ω) |
|
typ. 0.3 dB (≤ 8 MHz / 150 Ω) |
|
typ. 0.3 dB (≤ 2.5 MHz / 600 Ω) |
Cut-off frequency fg (3 dB), sym. in 100 Ohm system |
typ. 50 MHz |
Capacity (core-core) |
typ. 20 pF (f= 1 MHz / VR= 0 V) |
Capacity (core-earth) |
typ. 20 pF (f= 1 MHz / VR= 0 V) |
Resistance in series |
3.3 Ω 10 % |
Surge protection fault message |
none |
Impulse durability (conductor-conductor) |
B2 - 4 kV/100 A |
|
C1 - 1 kV/500 A |
|
C2 - 10 kV/5 kA |
Impulse durability (conductor-ground) |
B2 - 4 kV/100 A |
|
C1 - 1 kV/500 A |
|
C2 - 10 kV/5 kA |
|
D1 - 1 kA |