Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 102.5 mm |
Ambient temperature (operation) | -10 °C ... 60 °C |
Ambient temperature (storage/transport) | -20 °C ... 65 °C |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2:2005 |
Number of inputs | 1 |
Configurable/programmable | no |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
Max. input current | 50 mA |
Input resistance current input | approx. 50 Ω |
Number of outputs | 1 |
Current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
Max. output current | 28 mA |
Load/output load current output | < 500 Ω (at 20 mA) |
Ripple | < 20 mVPP (at 500 Ω) |
Transmission Behavior | 1:1 to input signal |
Nominal supply voltage | 24 V DC ±10 % |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 20 mA |
Power consumption | < 450 mW |
Connection method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
No. of channels | 1 |
Maximum transmission error | < 0.1 % (of final value) |
Maximum temperature coefficient | < 0.01 %/K |
Temperature coefficient, typical | < 0.002 %/K |
Limit frequency (3 dB) | approx. 100 Hz |
Step response (10-90%) | 500 ms |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2:2005 |
Color | green |
Housing material | PBT |
Mounting position | any |
Conformance | CE-compliant |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2:2005 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
REACh SVHC | |
Lead 7439-92-1 | |
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 4.0 | 27210100 |
eCl@ss 4.1 | 27210100 |
eCl@ss 5.0 | 27210100 |
eCl@ss 5.1 | 27210100 |
eCl@ss 6.0 | 27210100 |
eCl@ss 7.0 | 27210120 |
eCl@ss 8.0 | 27210120 |
eCl@ss 9.0 | 27210120 |
ETIM 4.0 | EC002653 |
ETIM 5.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 7.0 | EC002653 |
UNSPSC 6.01 | 30211506 |
UNSPSC 7.0901 | 39121008 |
UNSPSC 11 | 39121008 |
UNSPSC 12.01 | 39121008 |
UNSPSC 13.2 | 39121008 |
UNSPSC 18.0 | 39121008 |
UNSPSC 19.0 | 39121008 |
UNSPSC 20.0 | 39121008 |
UNSPSC 21.0 | 39121008 |