Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Width | 6.2 mm |
---|---|
Height | 93.1 mm |
Depth | 101.2 mm |
Ambient temperature (operation) | -20 °C ... 65 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Configurable/programmable | Yes |
---|---|
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
0 mA ... 10 mA | |
2 mA ... 10 mA | |
Input resistance current input | approx. 50 Ω |
Voltage input signal | 0 V ... 5 V |
1 V ... 5 V | |
0 V ... 10 V | |
2 V ... 10 V | |
Input resistance of voltage input | approx. 110 kΩ |
Number of outputs | 1 |
---|---|
Frequency output | 0 Hz ... 10 kHz |
0 Hz ... 5 kHz | |
0 Hz ... 2.5 kHz | |
0 Hz ... 1 kHz | |
0 Hz ... 500 Hz | |
0 Hz ... 250 Hz | |
0 Hz ... 100 Hz | |
0 Hz ... 50 Hz | |
Load min. | 4 mA ≤ (UL / RL) ≤ 20 mA |
Output signal PWM | 7.8 kHz (10 bit) |
3.9 kHz (10 bit) | |
1.9 kHz (12 bit) | |
977 Hz (12 bit) | |
488 Hz (14 bit) | |
244 Hz (14 bit) | |
122 Hz (16 bit) | |
61 Hz (16 bit) | |
Load min. | 12 mA ≤ (UL / RL) ≤ 20 mA |
Maximum switching voltage | 30 V |
Load current maximum | 20 mA |
Overrange/underrange | Can be set (via DIP switch) |
Type of protection | Short-circuit protection, polarity reversal protection |
Step response (0–99%) | < 15 ms (+ (1/f) smallest filter) |
< 1 s (+ (1/f) largest filter) |
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 10 mA (at 24 V DC) |
Power consumption | < 200 mW |
Connection method | Screw connection |
---|---|
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
No. of channels | 1 |
---|---|
Maximum transmission error | ≤ 0.1 % (> 7 kHz ≤ 0.2 %) |
Maximum temperature coefficient | < 0.02 %/K |
Temperature coefficient, typical | < 0.02 %/K |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 30 V AC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 | |
Certificate of classification | DNV GL TAA00000N1 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 2 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 2 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 2 % |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 4.0 | 27210100 |
---|---|
eCl@ss 4.1 | 27210100 |
eCl@ss 5.0 | 27210100 |
eCl@ss 5.1 | 27210100 |
eCl@ss 6.0 | 27210100 |
eCl@ss 7.0 | 27210120 |
eCl@ss 8.0 | 27210120 |
eCl@ss 9.0 | 27210120 |
ETIM 4.0 | EC002653 |
---|---|
ETIM 5.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 7.0 | EC002653 |
UNSPSC 6.01 | 30211506 |
---|---|
UNSPSC 7.0901 | 39121008 |
UNSPSC 11 | 39121008 |
UNSPSC 12.01 | 39121008 |
UNSPSC 13.2 | 39121008 |
UNSPSC 18.0 | 39121008 |
UNSPSC 19.0 | 39121008 |
UNSPSC 20.0 | 39121008 |
UNSPSC 21.0 | 39121008 |