Bộ lưu điện UPS DC 24V 10A EC Phoenix Contact QUINT4-UPS/24DC/24DC/10/EC - 2907070
QUINT USV, IQ Technology, EtherCAT®, DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 10 A, charging current: 3 A
Product description
The intelligent QUINT UPS for integration into established industrial networks: your systems continue to be supplied with uninterrupted power, even in the event of a mains failure. The battery management system with IQ Technology and a powerful battery charger ensures superior system availability.
Technical data
Input data
Input voltage |
24 V DC |
Input voltage range |
18 V DC ... 30 V DC |
18 V DC ... 32 V DC |
Electric strength, max. |
35 V DC |
Internal input fuse |
no |
Voltage type of supply voltage |
DC |
Inrush current |
≤ 7 A (≤ 4 ms) |
Reverse polarity protection |
yes |
Fixed backup threshold |
22 V DC |
30 V DC |
Dynamic activation threshold |
> 1 V / 100 ms |
Switch-on time |
max. 3 s |
Switch-on time during battery operation (Bat.-Start) |
8 s |
Voltage drop, input/output |
0.4 V DC |
Current consumption IN (UN, IOUT = IN, Icharge = 0) |
10.1 A |
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max) |
16.3 A |
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) |
105 mA |
Current consumption Icharge (UN, IOUT = 0, Icharge = max) |
3.7 A |
Power consumption PN (UN, IOUT = IN, Icharge = 0) |
245 W |
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) |
386 W |
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) |
2.6 W |
Power consumption Pcharge (UN, IOUT = 0, Icharge = max) |
92 W |
Output data
Efficiency |
typ. 97 % |
Number of outputs |
1 |
Short-circuit-proof |
yes |
No-load proof |
yes |
Switch-over time |
0 ms |
UPS connection in parallel |
no |
UPS connection in series |
no |
Energy storage device connection in parallel |
Yes, 5 (observe line protection) |
Energy storage device connection in series |
no |
Mains operation |
Output voltage |
24 V DC (UOUT = UIN - 0.4 V DC) |
Output voltage range |
18 V DC ... 30 V DC |
18 V DC ... 32 V DC |
Output current IN |
10 A |
Static Boost (IStat.Boost) |
12.5 A |
Dynamic Boost (IDyn.Boost) |
20 A (5 s) |
Selective Fuse Breaking (ISFB) |
60 A (15 ms) |
Output power POUT (UN, IOUT = IN) |
240 W |
Output power POUT (UN, IOUT = Istat.Boost) |
300 W |
Output power POUT (UN, IOUT = Idyn.Boost) |
480 W (5 s) |
Power dissipation No load (UN, IOut = 0, ICharge = 0) |
1 W |
Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) |
6 W |
Battery operation |
Output voltage |
24 V DC (UOUT = UBAT - 0.4 V DC) |
Output voltage range |
19 V DC ... 32 V DC |
Output current IN |
10 A |
Static Boost (IStat.Boost) |
12.5 A |
Dynamic Boost (IDyn.Boost) |
20 A (5 s) |
Selective Fuse Breaking (ISFB) |
60 A (15 ms) |
Output power POUT (UN, IOUT = IN) |
240 W |
Output power POUT (UN, IOUT = Istat.Boost) |
300 W |
Output power POUT (UN, IOUT = Idyn.Boost) |
480 W (5 s) |
Energy storage
End-of-charge voltage |
32 V DC |
End-of-charge voltage (temperature-compensated) |
25 V DC ... 32 V DC |
Charging current (configurable) |
3 A |
Nominal capacity (without additional charger) |
1.2 Ah ... 60 Ah |
Max. capacity |
80 Ah |
Charging time |
120 h |
Buffer time |
25 min. (7.2 Ah) |
Deep discharge protection |
19.2 V DC |
Battery technology |
VRLA, VRLA-WTR, LI-ION |
Charge characteristic curve |
IU0U |
IQ-Technology |
yes |
Temperature sensor |
yes |
Temperature compensation (configurable) |
42 mV/K |
Interfaces
Interface |
EtherCAT® |
Number of interfaces |
2 |
Connection method |
RJ45 |
Locking |
Locking clip |
Transmission physics |
Twisted-Pair |
Features |
Autonegotiation |
Autocrossing |
Half- or full-duplex |
automatic recognition |
Topology |
Ring |
Line |
Transmission speed |
100 Mbps |
Transmission length |
max. 100 m |
Cycle time |
< 100 µs |
Access time |
≤ 2 s |
Supported protocols |
CoE |
Chipset |
Renesas R-IN32M3 |
Electrical isolation |
yes |
Device ID |
2C5B74hex |
Vendor ID |
84hex |
Signaling
LED signaling |
Types of signaling |
DC OK (green) |
Alarm (red) |
Bat.-Mode (yellow) |
SOC (red, green) |
Data (red, green) |
Product properties
Product type |
DC UPS |
Product family |
QUINT USV |
MTBF (IEC 61709, SN 29500) |
> 1189000 h (25 °C) |
> 736900 h (40 °C) |
> 372700 h (60 °C) |
Environmental protection directive |
RoHS Directive 2011/65/EU |
WEEE |
Reach |
Insulation characteristics |
Protection class |
III (without PE) |
Degree of pollution |
2 |
Life expectancy (electrolytic capacitors) |
Time |
137895 h |
Dimensions
Item dimensions |
Width |
35 mm |
Height |
130 mm |
Depth |
125 mm |
Item dimensions with alternative mounting |
Width |
123 mm |
Height |
130 mm |
Depth |
37 mm |
Installation dimensions |
Installation distance right/left (active) |
5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (passive) |
0 mm / 0 mm (POut ≥50% ) |
Installation distance right/left (active, passive) |
0 mm / 0 mm (POut ≤50 %) |
Installation distance top/bottom (active) |
50 mm / 50 mm (POut ≥50% ) |
Installation distance top/bottom (passive) |
40 mm / 20 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) |
40 mm / 20 mm (POut ≤50 %) |
Mounting
Mounting type |
DIN rail mounting |
Mounting position |
On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) |
V0 |
Housing material |
Metal |
Hood version |
Stainless steel X6Cr17 |
Side element version |
Aluminum AlMg3 |
Environmental and real-life conditions
Ambient conditions |
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Ambient temperature (start-up type tested) |
-40 °C |
Maximum altitude |
≤ 4000 m |
Climatic class |
3K3 (EN 60721) |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
2.3g |
Standards and regulations
Overvoltage category |
EN 61010-1 |
II (≤ 4000 m) |
EN 61010-2-201 |
II (≤ 4000 m) |
Protective extra-low voltage |
Standard designation |
Protective extra-low voltage |
Standards/specifications |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
Approvals
UL approval |
Identification |
UL/C-UL Listed UL 61010-1 |
UL approval |
Identification |
UL/C-UL Listed UL 61010-2-201 |
UL approval |
Identification |
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CSA |
Identification |
CAN/CSA-C22.2 No. 61010-1-12 |
CSA |
Identification |
CAN/CSA-IEC 61010-2-201 |
CSA |
Identification |
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CB scheme |
Identification |
IEC 61010-1 |
IEC 61010-2-201 |
DNV |
Identification |
Class Guideline DNVGL-CG-0339 |
Note |
Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B |
EMC data
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission |
EN 61000-6-3 |
EN 61000-6-4 |
EMC requirements for noise immunity |
EN 61000-6-1 |
EN 61000-6-2 |
Noise immunity |
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Noise emission |
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Electrostatic discharge |
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge |
Contact discharge |
8 kV (Test Level 4) |
Discharge in air |
15 kV (Test Level 4) |
Comments |
Criterion B |
Electromagnetic HF field |
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field |
Frequency range |
80 MHz ... 1 GHz |
Test field strength |
20 V/m (Test Level 3) |
Frequency range |
1 GHz ... 6 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
1 GHz ... 6 GHz |
Test field strength |
10 V/m (Test Level 3) |
Comments |
Criterion A |
Fast transients (burst) |
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst) |
Input |
4 kV (Test Level 4 - asymmetrical) |
Output |
4 kV (Test Level 4 - asymmetrical) |
Signal |
4 kV (Test Level 4 - asymmetrical) |
Comments |
Criterion B |
Surge voltage load (surge) |
Standards/regulations |
EN 61000-4-5 |
Input |
1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) |
Output |
1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) |
Signal |
1 kV (Test Level 2 - asymmetrical) |
Comments |
Criterion B |
Conducted interference |
Standards/regulations |
EN 61000-4-6 |
Conducted interference |
I/O/S |
asymmetrical |
Frequency range |
0.15 MHz ... 80 MHz |
Comments |
Criterion A |
Voltage |
10 V (Test Level 3) |
Power frequency magnetic field |
Standards/regulations |
EN 61000-4-8 |
Frequency |
16.67 Hz |
50 Hz |
60 Hz |
Test field strength |
100 A/m |
Additional text |
60 s |
Comments |
Criterion A |
Frequency |
50 Hz |
60 Hz |
Frequency range |
50 Hz ... 60 Hz |
Test field strength |
1 kA/m |
Additional text |
3 s |
Frequency |
0 Hz |
Test field strength |
300 A/m |
Additional text |
DC, 60 s |
Criteria |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Notes
General |
EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany. |
Commercial data
Item number |
2907070 |
Packing unit |
1 pc |
Minimum order quantity |
1 pc |
Product key |
CMUI43 |
Catalog page |
Page 321 (C-4-2019) |
GTIN |
4055626171265 |
Weight per piece (including packing) |
544.7 g |
Weight per piece (excluding packing) |
544.7 g |
Customs tariff number |
85371091 |
Country of origin |
CN |
Classifications
ECLASS
ECLASS-11.0 |
27040705 |
ECLASS-12.0 |
27040705 |
ECLASS-13.0 |
27040705 |
ETIM
UNSPSC
Approvals
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
Approval ID: FILE E 123528
cUL Listed
Approval ID: FILE E 123528
EAC
Approval ID: RU-DE.B.00184/20
DNV
Approval ID: TAA00002K4
cUL Listed
Approval ID: FILE E 199827
UL Listed
Approval ID: FILE E 199827
cULus Listed
cULus Listed
Environmental product compliance
|
REACh SVHC |
Lead 7439-92-1 |
|
China RoHS |
Environmentally Friendly Use Period = 25; |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
- Tài liệu kỹ thuật Phoenix Contact QUINT4-UPS/24DC/24DC/10/EC - 2907070
ở đây.
Compatible products
Energy storage
UPS-BAT/PB/24DC/1.2AH - 1274520
Energy storage
UPS-BAT/PB/24DC/4AH - 1274117
Energy storage
UPS-BAT/PB/24DC/7AH - 1274118
Energy storage
UPS-BAT/PB/24DC/12AH - 1274119
Energy storage
UPS-BAT/PB/24DC/20AH - 1348516
Energy storage
UPS-BAT/PB/24DC/40AH - 1354641
Energy storage
UPS-BAT/LI/24DC/128WH - 1396415
Energy storage
UPS-BAT/VRLA-WTR/24DC/13AH - 2320416
Energy storage
UPS-BAT/VRLA-WTR/24DC/26AH - 2320429