Width | 60 mm |
Height | 130 mm |
Depth | 118 mm |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Nominal input voltage range | 100 V AC ... 240 V AC |
AC input voltage range | 85 V AC ... 264 V AC (Derating < 90 V AC: 2.5%V) |
Input voltage range DC | 100 V DC ... 350 V DC (UL508: 100 ... 250 V) |
Buffer time | adjustable: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min; PC-Mode |
Current consumption | 1.1 A (230 V AC, maximum) |
1.8 A (120 V AC, maximum) | |
Inrush current limiting/I²t | < 1.3 A2s |
Mains buffering | see diagram |
Typical response time | 150 ms (230 V AC) |
200 ms (120 V AC) | |
Power factor (cos phi) | approx. 0.5 |
Protective circuit | Transient surge protection Varistor |
Input fuse, integrated | 6.3 A (slow-blow, internal) |
Nominal output voltage | 24 V DC |
Setting range of the output voltage (USet) | 22.5 V DC ... 29.5 V DC (Network operation; in the buffer mode, dependent on the battery voltage of 27.9 V DC ... 19.2 V DC) |
Nominal output current (IN) | 5 A (-25 °C ... 55 °C) |
Derating | 55 °C ... 70 °C (2.5%/K) |
Output current limit | max. 6 A (Mains operation) |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Efficiency | > 88 % (230 V AC, network operation) |
> 86 % (120 V AC, network operation) | |
> 86 % (Battery operation) | |
Residual ripple | < 10 mVPP |
Peak switching voltages nominal load | < 25 mVPP |
Connection in parallel | Yes, 2 |
Surge protection against internal surge voltages | Yes, < 35 V DC |
Feedback resistance | 35 V DC |
IQ technology | no |
Net weight | 1.1 kg |
Memory medium | External, battery 1.3 Ah / 3.4 Ah / 7.2 Ah / 12 Ah |
Operating mode | |
Insulation voltage input/output | 4 kV (type test) |
2 kV (routine test) | |
Protection class | I |
MTBF (IEC 61709, SN 29500) | |
> 596000 h (40 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | Can be aligned: Horizontally 0 mm, vertically 50 mm |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Charge characteristic curve | I/U characteristic curve |
Battery presence check/time interval | 60 s |
Charge current | 0.2 A ... 1.5 A (Default 1.0 A) |
End-of-charge voltage | 25 V DC ... 30 V DC (Default 27.6 V DC) |
Temperature compensation | 0 mV/K ... 200 mV/K (42 mV/K by default) |
Quality check of battery | 4 h ... 200 h (Default 12 h) |
Deep discharge protection | 18 V DC ... 21 V DC (Default 19.2 V DC) |
Alarm signaling threshold | 18 V DC ... 30 V DC (Default 20.4 V DC) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Noise immunity | EN 61000-6-2:2005 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Contact discharge | 6 kV |
Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 2 GHz |
Test field strength | 10 V/m |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Signal | 2 kV (Level 3 - asymmetrical) |
1 kV (Level 3 - symmetrical) | |
Standards/regulations | EN 61000-6-3 |
EN 61000-4-6 | |
Frequency range | 10 kHz ... 80 MHz |
Voltage | 10 V |
Standards/regulations | EN 61000-4-11 |
Low Voltage Directive | Conformance with LV directive 2006/95/EC |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
EN 60204 (PELV) | |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Shipbuilding approval | DNV GL (EMC B) |
UL approvals | UL/C-UL listed UL 508 |
UL/C-UL Recognized UL 60950-1 | |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
15 Hz ... 150 Hz, 2.3g, 90 min. | |
Rail applications | EN 50121-4 |
eCl@ss 4.0 | 27040603 |
eCl@ss 4.1 | 27040603 |
eCl@ss 5.0 | 27040603 |
eCl@ss 5.1 | 27040603 |
eCl@ss 6.0 | 27040603 |
eCl@ss 7.0 | 27040603 |
eCl@ss 8.0 | 27040603 |
eCl@ss 9.0 | 27040705 |
ETIM 2.0 | EC000382 |
ETIM 3.0 | EC000382 |
ETIM 4.0 | EC000382 |
ETIM 5.0 | EC000382 |
ETIM 6.0 | EC000382 |
UNSPSC 6.01 | 30211510 |
UNSPSC 7.0901 | 39121011 |
UNSPSC 11 | 39121011 |
UNSPSC 12.01 | 39121011 |
UNSPSC 13.2 | 39121011 |