General specifications | ||
---|---|---|
Signal type | Analog input | |
Operation time | MTBF: 490 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
|
Supply | ||
Connection | Power Bus or terminals 1-, 2+ | |
Rated voltage | 16.8 ... 31.2 V DC | |
Power dissipation | 0.6 W | |
Power consumption | 0.8 W | |
Input | ||
Connection side | field side | |
Transmission range | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % |
|
Input I | ||
Connection | terminals 5+, 6- | |
Input signal | 0/4 ... 20 mA , 0/2 ... 10 mA , ± 10 mA, ± 20 mA , max. 50 mA | |
Input resistance | ≤ 25 Ω | |
Input II | ||
Connection | terminals 7+, 8- | |
Input signal | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V , ± 10 V , max. 30 V | |
Input resistance | > 1 MΩ | |
Output | ||
Connection side | control side | |
Connection | terminals 3-, 4+ | |
Analog voltage output | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V, ± 10 V , load ≥ 2 kΩ | |
Analog current output | 0/4 ... 20 mA, ± 10 mA, ± 20 mA, load ≤ 600 Ω | |
Ripple | ≤ 10 mV eff | |
Transfer characteristics | ||
Accuracy | max. 0.1 % of full-scale value | |
Influence of ambient temperature | < 100 ppm/K of full-scale value | |
Frequency range | 0 ... 100 Hz , 0 ... 8 kHz | |
Settling time | 7 ms , 100 µs | |
Galvanic isolation | ||
Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Indicators/settings | ||
Control elements | DIP-switch potentiometer |
|
Configuration | via DIP switches via potentiometer |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | EN 61010-1:2010 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
Mass | approx. 70 g | |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | DEMKO 16 ATEX 1750X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 | |
IECEx approval | IECEx UL 16.0116X | |
Approved for | Ex nA IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |