The Power Module contains:
The line-side 6‑pulse rectifierAs standard, the Power Module has the following interfaces:
- 1 line supply connection
DRIVE-CLiQ cables for connections to further DRIVE-CLiQ devices can be ordered pre-assembled and cut to length as required (see Section Supplementary system components → Signal cables).
The scope of supply of the Power Modules includes:
- 1 DRIVE-CLiQ cable for connection to the Control UnitThe Power Module communicates with the CU320‑2 Control Unit via DRIVE-CLiQ and receives its control information via this route.
Connection example of a Power Module
Line voltage |
Power Modules |
|||||
---|---|---|---|---|---|---|
|
6SL3310-1GE32-1AA3 |
6SL3310-1GE32-6AA3 |
6SL3310-1GE33-1AA3 |
6SL3310-1GE33-8AA3 |
6SL3310-1GE35-0AA3 |
|
Type rating |
|
|
|
|
|
|
For IL at 50 Hz 400 V 1) |
kW |
110 |
132 |
160 |
200 |
250 |
For IH at 50 Hz 400 V 1) |
kW |
90 |
110 |
132 |
160 |
200 |
For IL at 60 Hz 460 V 2) |
hp |
150 |
200 |
250 |
300 |
400 |
For IH at 60 Hz 460 V 2) |
hp |
150 |
200 |
200 |
250 |
350 |
Output current |
|
|
|
|
|
|
Rated current In |
A |
210 |
260 |
310 |
380 |
490 |
Base-load current IL3) |
A |
205 |
250 |
302 |
370 |
477 |
Base-load current IH4) |
A |
178 |
233 |
277 |
340 |
438 |
Input current |
|
|
|
|
|
|
Rated input current |
A |
229 |
284 |
338 |
395 |
509 |
Input current, max. |
A |
335 |
410 |
495 |
606 |
781 |
Current requirement, 24 V DC auxiliary power supply 5) |
A |
0.8 |
0.8 |
0.9 |
0.9 |
0.9 |
Minimum short-circuit current 6) |
A |
3000 |
3600 |
4400 |
4400 |
8000 |
Power loss, max. 7) |
|
|
|
|
|
|
At 50 Hz 400 V |
kW |
2.4 |
3.2 |
3.9 |
4.3 |
5.6 |
At 60 Hz 460 V |
kW |
2.6 |
3.3 |
4.4 |
4.9 |
6.1 |
Cooling air requirement |
m3/s |
0.17 |
0.23 |
0.36 |
0.36 |
0.36 |
Cable length, max. between Power Module and motor 8) |
|
|
|
|
|
|
Shielded |
m |
300 |
300 |
300 |
300 |
300 |
Unshielded |
m |
450 |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
64/67 |
64/67 |
69/73 |
69/73 |
69/73 |
Line connection U1, V1, W1 |
|
M10 screw |
M10 screw |
M10 screw |
M10 screw |
M10 screw |
Conductor cross section, max. (IEC) |
mm2 |
2 × 185 |
2 × 185 |
2 × 240 |
2 × 240 |
2 × 240 |
Motor connection U2/T1, V2/T2, W2/T3 |
|
M10 screw |
M10 screw |
M10 screw |
M10 screw |
M10 screw |
Conductor cross section, max. (IEC) |
mm2 |
2 × 185 |
2 × 185 |
2 × 240 |
2 × 240 |
2 × 240 |
PE1/GND connection |
|
M10 screw |
M10 screw |
M10 screw |
M10 screw |
M10 screw |
Conductor cross section, max. (IEC) |
mm2 |
2 × 185 |
2 × 185 |
2 × 240 |
2 × 240 |
2 × 240 |
PE2/GND connection |
|
M10 screw |
M10 screw |
M10 screw |
M10 screw |
M10 screw |
Conductor cross section, max. (IEC) |
mm2 |
2 × 185 |
2 × 185 |
2 × 240 |
2 × 240 |
2 × 240 |
Dimensions |
|
|
|
|
|
|
Width |
mm |
326 |
326 |
326 |
326 |
326 |
Height |
mm |
1400 |
1400 |
1533 |
1533 |
1533 |
Depth |
mm |
356 |
356 |
545 |
545 |
545 |
Weight, approx. |
kg |
104 |
104 |
176 |
176 |
176 |
Frame size |
|
FX |
FX |
GX |
GX |
GX |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 400 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 460 V.
3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s (see Technical specifications → Overload capability).
4) The base-load current IL is based on a load cycle of 150% for 60 s or 160% for 10 s with a load cycle duration of 300 s (see Technical specifications → Overload capability).
5) If the auxiliary supply is to be fed in separately from the load supply, e.g. if the control should be able to continue communication when the line voltage fails.
6) The minimum current required to reliably trigger 3NE1 protective devices.
7) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
8) Longer cable lengths for specific configurations are available on request.
Line voltage |
Power Modules |
||||
---|---|---|---|---|---|
|
6SL3310-1GE36-1AA3 |
6SL3310-1GE37-5AA3 |
6SL3310-1GE38-4AA3 |
6SL3310-1GE41-0AA3 |
|
Type rating |
|
|
|
|
|
For IL at 50 Hz 400 V 1) |
kW |
315 |
400 |
450 |
560 |
For IH at 50 Hz 400 V 1) |
kW |
250 |
315 |
400 |
450 |
For IL at 60 Hz 460 V 2) |
hp |
500 |
600 |
700 |
800 |
For IH at 60 Hz 460 V 2) |
hp |
350 |
450 |
600 |
700 |
Output current |
|
|
|
|
|
Rated current In |
A |
605 |
745 |
840 |
985 |
Base-load current IL3) |
A |
590 |
725 |
820 |
960 |
Base-load current IH4) |
A |
460 |
570 |
700 |
860 |
Input current |
|
|
|
|
|
Rated input current |
A |
629 |
775 |
873 |
1024 |
Input current, max. |
A |
967 |
1188 |
1344 |
1573 |
Current requirement, 24 V DC auxiliary power supply 5) |
A |
1 |
1 |
1 |
1.25 |
Minimum short-circuit current 6) |
A |
10000 |
10500 |
16000 |
18400 |
Power loss, max. 7) |
|
|
|
|
|
At 50 Hz 400 V |
kW |
7.2 |
8.5 |
9.1 |
12.7 |
At 60 Hz 460 V |
kW |
8.1 |
9.4 |
10.2 |
14.5 |
Cooling air requirement |
m3/s |
0.78 |
0.78 |
0.78 |
1.48 |
Cable length, max. between Power Module and motor 8) |
|
|
|
|
|
Shielded |
m |
300 |
300 |
300 |
300 |
Unshielded |
m |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP00 |
IP00 |
IP00 |
IP00 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
70/73 |
70/73 |
70/73 |
72/75 |
Line connection U1, V1, W1 |
|
2 × M12 screws |
2 × M12 screws |
2 × M12 screws |
3 × M12 screws |
Conductor cross section, max. (IEC) |
mm2 |
4 × 240 |
4 × 240 |
4 × 240 |
6 × 240 |
Motor connection U2/T1, V2/T2, W2/T3 |
|
2 × M12 screws |
2 × M12 screws |
2 × M12 screws |
3 × M12 screws |
Conductor cross section, max. (IEC) |
mm2 |
4 × 240 |
4 × 240 |
4 × 240 |
6 × 240 |
PE1/GND connection |
|
M12 screw |
M12 screw |
M12 screw |
2 × M12 screws |
Conductor cross section, max. (IEC) |
mm2 |
2 × 240 |
2 × 240 |
2 × 240 |
4 × 240 |
PE2/GND connection |
|
2 × M12 screws |
2 × M12 screws |
2 × M12 screws |
3 × M12 screws |
Conductor cross section, max. (IEC) |
mm2 |
4 × 240 |
4 × 240 |
4 × 240 |
6 × 240 |
Dimensions |
|
|
|
|
|
Width |
mm |
503 |
503 |
503 |
909 |
Height |
mm |
1506 |
1506 |
1506 |
1510 |
Depth |
mm |
540 |
540 |
540 |
540 |
Weight, approx. |
kg |
294 |
294 |
294 |
530 |
Frame size |
|
HX |
HX |
HX |
JX |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 400 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 460 V.
3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s (see Technical specifications → Overload capability).
4) The base-load current IL is based on a load cycle of 150% for 60 s or 160% for 10 s with a load cycle duration of 300 s (see Technical specifications → Overload capability).
5) If the auxiliary supply is to be fed in separately from the load supply, e.g. if the control should be able to continue communication when the line voltage fails.
6) The minimum current required to reliably trigger 3NE1 protective devices.
7) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
8) Longer cable lengths for specific configurations are available on request.