Bộ khuếch đại chuyển mạch ách ly 24VDC 4-kênh Pepperl-Fuchs KFD2-SRA-Ex4
General specifications |
Signal type |
Digital Input |
Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
19 ... 30 V DC |
Ripple |
≤ 10 % |
Rated current |
45 ... 70 mA |
Power dissipation |
1.2 W |
Input |
Connection side |
field side |
Connection |
terminals 1-, 2+, 3-; 4-, 5+, 6- |
Rated values |
acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Pulse/Pause ratio |
min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) |
Line fault detection |
breakage I ≤ 0.15 mA , short-circuit I > 6 mA |
Output |
Connection side |
control side |
Connection |
output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
Output I ... IV |
Signal I ... Signal IV ; relay |
Contact loading |
253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load; |
Energized/De-energized delay |
approx. 30 ms / approx. 30 ms |
Mechanical life |
5 x 106 switching cycles |
Collective error message |
Power Rail |
Transfer characteristics |
Switching frequency |
≤ 10 Hz (non-AC operation) ≤ 3 Hz (AC operation) |
Galvanic isolation |
Input/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output |
basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements |
LEDs |
Control elements |
DIP switch |
Configuration |
via DIP switches |
Labeling |
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
|
Directive 2014/35/EU |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Degree of protection |
IEC 60529:2001 |
Input |
EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Connection |
screw terminals |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate |
ZELM 99 ATEX 0009 |
|
Marking |
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
|
Input |
Ex ia IIC |
|
Voltage |
10 V |
|
Current |
14 mA |
|
Power |
35 mW (linear characteristic) |
Supply |
|
|
Maximum safe voltage |
40 V DC (Attention! Um is no rated voltage.) |
Output |
|
|
Contact loading |
230 V AC + 10 % / 2 A / 100 VA / cos φ ≥ 0.7; 40 V DC / 2 A resistive load |
Fault indication output |
|
|
Maximum safe voltage |
40 V DC |
Galvanic isolation |
|
|
Input/input |
not available |
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000 |
International approvals |
UL approval |
|
|
Control drawing |
116-0145 |
IECEx approval |
|
|
IECEx certificate |
IECEx TUN 04.0003 |
|
IECEx marking |
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information |
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System |
Classcode |
ECLASS 11.0 |
27210121 |
ECLASS 10.0.1 |
27210121 |
ECLASS 9.0 |
27210121 |
ECLASS 8.0 |
27210121 |
ECLASS 5.1 |
27210121 |
ETIM 8.0 |
EC001485 |
ETIM 7.0 |
EC001485 |
ETIM 6.0 |
EC001485 |
ETIM 5.0 |
EC001485 |
UNSPSC 12.1 |
32101514 |
- Tài liệu kỹ thuật Pepperl-Fuchs KFD2-SRA-Ex4
ở đây
Tham khảo thêm các model khác cùng loại:
KCD2-SOT-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SOT-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KCD2-ST-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (active), Reversible mode of operation
KFA6-ER-Ex1.W.LB
Conductive Switch Amplifier
1-channel isolated barrier, 230 V AC supply, Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Fault relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact)
KFD2-ER-Ex1.W.LB
Conductive Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Level sensing input, Adjustable range 1 kΩ ... 150 kΩ, Relay contact output, Fault relay contact output, Adjustable time delay up to 10 s, Minimum/maximum control, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 1-channel, Conductivity measurement, Min./max. control, Time delay, Rated voltage: 20 ... 30 V DC, Signal: Resistance, Line fault detection, Type: 2 x relay (change-over contact), Fault indication output
KFD2-SH-Ex1
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 40 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 35 V DC, Field device: SN/S1N sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)
KFD2-SH-Ex1.T.OP
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for approved dry contacts or SN/S1N sensors, Active voltage output, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 30 V DC, Field device: SN/S1N sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-SOT3-Ex1.LB.IO
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Isolated passive transistor output, non-polarized, Isolated passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KFD2-SOT3-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KFD2-SOT3-Ex2.IO
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KFD2-SR2-Ex1.W
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
KFD2-SR2-Ex1.W.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-SR2-Ex2.W
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
KFD2-SR3-Ex2.2S
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-SRA-Ex4
Switch Amplifier
4-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 50 % less wiring, 2:1 technology, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Housing width: 20 mm, Number of channels: 4-channel, 2:1 Method, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 4 x relay (NO contact), Reversible mode of operation
KFD2-ST3-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (active)
KFD2-ST3-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Active transistor output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (active), Reversible mode of operation
KHA6-SH-Ex1
Switch Amplifier
1-channel isolated barrier, 115/230 V AC supply, Input for approved dry contacts or SN/S1N sensors, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Up to PL d acc. to EN/ISO 13849, Housing width: 40 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 85 ... 253 V AC , 45 ... 65 Hz, Field device: SN/S1N sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)
KFA5-SR2-Ex1.W
Switch Amplifier
1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
KFA5-SR2-Ex1.W.LB
Switch Amplifier
1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
KFA6-SOT2-Ex2
Switch Amplifier
2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KFA6-SR2-Ex1.W
Switch Amplifier
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
KFA6-SR2-Ex1.W.LB
Switch Amplifier
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
KFA6-SR2-Ex2.W
Switch Amplifier
2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
KFA6-SR2-Ex2.W.IR
Switch Amplifier
2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Latching relay contact output, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 2-channel, Interval relay, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
KCD2-SON-Ex1
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SOT-Ex2.SP
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact
KCD2-SR-Ex1
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (NO contact)
KCD2-SR-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SR-Ex1.LB.SP
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SR-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)
KCD2-SR-Ex2.SP
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)
KCD2-ST-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-SOT3-Ex1.LB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Passive fault output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive)
KFU8-SR-Ex1.W
Switch Amplifier
1-channel isolated barrier, Universal usage at different power supplies, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC / 90 ... 253 V AC 50 ... 60 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact)
KFU8-SR-Ex1.W.LB
Switch Amplifier
1-channel isolated barrier, Universal usage at different power supplies, Dry contact or NAMUR inputs, Relay contact output, Fault relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC / 90 ... 253 V AC 50 ... 60 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFU8-SR-Ex2.W
Switch Amplifier
2-channel isolated barrier, Universal usage at different power supplies, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC / 90 ... 253 V AC 50 ... 60 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
WE77/Ex-1 115V
Switch Amplifier
1-channel, Control circuit EEx ia IIC, 115 V AC supply voltage, Reversible mode of operation, Lead breakage (LB) monitoring, 1 relay contact output (change-over contact), Housing width: 40 mm, Number of channels: 1-channel, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
WE77/Ex-1 230V
Switch Amplifier
1-channel, Control circuit EEx ia IIC, 230 V AC supply voltage, Reversible mode of operation, Lead breakage (LB) monitoring, 1 relay contact output (change-over contact), Housing width: 40 mm, Number of channels: 1-channel, Rated voltage: 198 ... 253 V AC ; 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
WE77/Ex-2 115V
Switch Amplifier
2-channel, Control circuit EEx ia IIC, 115 V AC supply voltage, Reversible mode of operation, Lead breakage (LB) monitoring, 1 relay contact output (change-over contact) per channel, Housing width: 60 mm, Number of channels: 2-channel, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
WE77/Ex-2 230V
Switch Amplifier
2-channel, Control circuit EEx ia IIC, 230 V AC supply voltage, Reversible mode of operation, Lead breakage (LB) monitoring, 1 relay contact output (change-over contact) per channel, Housing width: 60 mm, Number of channels: 2-channel, Rated voltage: 198 ... 253 V AC ; 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
KCD2-SON-Ex1.R1
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive), Application-specific outputs, Line fault transparency (LFT), Usable as signal splitter (1 input and 2 outputs), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SON-Ex1.R2
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SON-Ex1.R3
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, Application-specific outputs, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SON-Ex1.SP
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SON-Ex2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SON-Ex2.R1
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive), Application-specific outputs, Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SON-Ex2.R2
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SON-Ex2.R3
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Application-specific outputs, 2 passive transistor outputs (resistive), Line fault transparency (LFT), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SON-Ex2.SP
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 passive transistor outputs (resistive acc. to EN 60947-5-6), Line fault transparency (LFT), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-SOT-Ex1.LB.SP
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 passive transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-ST-Ex1.LB.SP
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR input, 2 active transistor outputs, Usable as signal splitter (1 input and 2 outputs), Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor
KCD2-ST-Ex2.SP
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, 2 active transistor outputs, Reversible mode of operation, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact
KFD2-SOT3-Ex2.IO-Y1
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, TTL level, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KCD2-SR-Ex1.LB-AB
Switch Amplifier
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KCD2-SR-Ex2-AB
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (NO contact)
KFA5-SR2-Ex2.W
Switch Amplifier
2-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
KFD2-DU-Ex1.D
Switch Amplifier, Timer Relay
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact and transistor output, Adjustable output timer functions from 10 ms ... 60 min, Input frequency up to 80 Hz; pulse divider up to 1 kHz, Reset function, Configurable by keypad, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 1-channel, Reset function, Time function, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-SR2-Ex2.2S
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFA4-SR2-Ex2.W
Switch Amplifier
2-channel, Control circuit EEx ia IIC, Reversible mode of operation, 1 relay contact output (change-over contact) per channel, EMC acc. to NAMUR NE 21, LB/SC monitoring, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 90 ... 110 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
KFA5-DU-Ex1.D
Switch Amplifier, Timer Relay
1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Relay contact and transistor output, Adjustable output timer functions from 10 ms ... 60 min, Input frequency up to 80 Hz; pulse divider up to 1 kHz, Reset function, Configurable by keypad, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 1-channel, Reset function, Time function, Rated voltage: 115 V AC ± 10 %, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFA5-SOT2-Ex2
Switch Amplifier
2-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Passive transistor output, non-polarized, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 103.5 ... 126.5 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), Reversible mode of operation
KFA5-SR2-Ex2.W.IR
Switch Amplifier
2-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Latching relay contact output, Line fault detection (LFD), Housing width: 20 mm, Number of channels: 2-channel, Interval relay, Rated voltage: 103.5 ... 126 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact)
KFA6-DU-Ex1.D
Switch Amplifier, Timer Relay
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact and transistor output, Adjustable output timer functions from 10 ms ... 60 min, Input frequency up to 80 Hz; pulse divider up to 1 kHz, Reset function, Configurable by keypad, Line fault detection (LFD), Housing width: 40 mm, Number of channels: 1-channel, Reset function, Time function, Rated voltage: 230 V AC ± 10 %, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection
KFD2-ELD-Ex16
Ground Fault Detection
16-channel isolated barrier, 24 V DC supply (Power Rail), Analog or digtial field device inputs, Monitors leakage current, Fault relay contact output, LED status indication, Test circuit for validation, Parallel connection for easy integration, Conformal coating, Housing width: 60 mm, Number of channels: 16-channel, Conformal coating, Rated voltage: 20 ... 30 V DC, Type: 1 x relay (change-over contact)
KFD2-SOT2-Ex2.IO-Y181008
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Isolated passive transistor output, TTL level, Line fault detection (LFD), Reversible mode of operation, Housing width: 20 mm, Number of channels: 2-channel, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x Transistor (passive), splitter function (1 input and several outputs), Reversible mode of operation
KFA4-SR2-Ex1.W
Switch Amplifier
1-channel, Control circuit EEx ia IIC, Reversible mode of operation, 1 relay contact output (change-over contact), EMC acc. to NAMUR NE 21, LB/SC monitoring, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 90 ... 110 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 1 x relay (change-over contact), Reversible mode of operation
KFA4-SR2-Ex1.W.LB
Switch Amplifier
1-channel, Control circuit EEx ia IIC, Reversible mode of operation, Output I: relay contact output (change-over contact), Output II: optionally signal output/fault signal, EMC acc. to NAMUR NE 21, LB/SC monitoring, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 90 ... 110 V AC , 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection