Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
20 ... 30 V DC |
Ripple |
≤ 10 % |
Rated current |
≤ 50 mA |
Input |
Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values |
acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Output |
Connection |
output I: terminals 7, 8 ; output II: terminals 10, 11 |
Signal level |
1-signal: (external voltage) - 2.5 V max. for 10 mA or 3 V max. for 100 mA (100 mA, short-circuit proof)
0-signal: switched off (off-state current ≤ 10 µA) |
Output I, II |
signal ; electronic output, passive |
Collective error message |
Power Rail (only on KFD2-SOT2-Ex2) |
Transfer characteristics |
Switching frequency |
≤ 5 kHz |
Galvanic isolation |
Output/power supply |
functional insulation acc. to EN 50178, rated insulation voltage 50 Veff |
Input/input |
not available |
Output/Output |
functional insulation acc. to EN 50178, rated insulation voltage 50 Veff |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 89/336/EEC |
EN 61326, EN 50081-2, NE 21 |
Conformity |
Galvanic isolation |
EN 50178 |
Electromagnetic compatibility |
NE 21 |
Degree of protection |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) |
|
Height |
118 mm |
|
Width |
20 mm |
|
Length |
115 mm |
Data for application in connection with hazardous areas |
EU-type examination certificate |
PTB 00 ATEX 2035 , for additional certificates see www.pepperl-fuchs.com |
|
Marking |
II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
|
Input |
EEx ia IIC |
|
Voltage |
10.5 V |
|
Current |
13 mA |
|
Power |
34 mW (linear characteristic) |
Supply |
|
|
Maximum safe voltage |
40 V DC (Attention! The rated voltage can be lower.) |
Output |
|
|
Maximum safe voltage |
40 V DC (Attention! The rated voltage can be lower.) |
Certificate |
TÜV 99 ATEX 1499 X , observe statement of conformity |
|
Marking |
II 3G EEx nAC IIC T4 [device in zone 2] |
Galvanic isolation |
|
|
Input/Output |
safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
|
Input/power supply |
safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
Directive conformity |
|
|
Directive 94/9/EC |
EN 50014, EN 50020, EN 50021 |