Giao diện kết nối đầu ra cảm biến Pepperl Fuchs KCD2-E2L
- 1-channel terminal amplifier
- NAMUR sensor input
- DC 24 V supply voltage
- Standard interface for prevention of signal transmission errors
- Switching status indicator, yellow LED
- Lead breakage monitoring: The lead breakage monitoring can be disconnected by bridging terminals 1 and 3
- Short-circuit proof electronic output
- Low noise sensitivity
- Compact terminal housing
- Clips onto standard 35 mm rail to DIN EN 50 022
- Degree of protection IP20
Thông số kỹ thuật KCD2-E2L
Product Description |
Sensor output interface terminal with lead breakage monitoring |
Functional safety related parameters |
MTTFd |
1837 a |
Indicators/operating means |
LED yellow |
switching output
lead breakage: LED off, output locked |
Electrical specifications |
Operating voltage |
10 ... 30 V DC |
Ripple |
≤ 10 % |
Operating current |
approx. 22 mA |
Input |
Connection |
terminals 1+, 2- |
Connectable sensor types |
NAMUR |
Pulse length/pulse interval |
≥ 0.5 ms / ≥ 0.5 ms |
Short-circuit current |
approx. 8 mA |
Sensor supply |
8 V DC,
max. 9 V DC at input resistance min. 562 Ω |
Switching point |
1.2 ... 2.1 mA hysteresis approx. 0.2 mA |
Line fault detection |
with |
Trip value |
1 kHz |
Output |
Connection |
terminal 4+ |
Current |
200 mA short-circuit protected |
Transistor |
PNP |
Signal level |
UB - 1.1V |
Transfer characteristics |
Mode of operation |
NO contact |
Switching frequency |
1 kHz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
EN 61326-1:2013 |
Standard conformity |
Degree of protection |
EN 60529:2000 |
Noise immunity |
EN 61326-1:2013 |
Ambient conditions |
Ambient temperature |
-25 ... 70 °C (-13 ... 158 °F) |
Storage temperature |
-25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Connection |
self-opening apparatus connection terminals, max. core cross section 0.34 ... 2.5 mm2 |
Mass |
60 g |
Dimensions |
20x60x40
(in mm) |
Classifications
System |
Classcode |
ECLASS 13.0 |
27210121 |
ECLASS 12.0 |
27210121 |
ECLASS 11.0 |
27210121 |
ECLASS 10.0.1 |
27210121 |
ECLASS 9.0 |
27210121 |
ECLASS 8.0 |
27210121 |
ECLASS 5.1 |
27210121 |
ETIM 9.0 |
EC002653 |
ETIM 8.0 |
EC002653 |
ETIM 7.0 |
EC002653 |
ETIM 6.0 |
EC002653 |
ETIM 5.0 |
EC002653 |
UNSPSC 12.1 |
41111902 |
- Tài liệu kỹ thuật Pepperl Fuchs KCD2-E2L
ở đây.
Tham khảo thêm các model khác cùng loại:
KCD2-E2L
Sensor output interface terminal
Single-channel terminal amplifier with line breakage detection, input for NAMUR sensors, DC 24 V supply voltage, standardized interface to prevent signal transmission errors, switching state display, LED yellow
KCD2-R
Sensor output interface terminal
Relay output with 1 pole, yellow LED indicates switching state, Free-wheeling diode, Compact terminal housing, Clips onto standard 35 mm rail to DIN EN 50 022, Degree of protection IP20
KFU8-FSSP-1.D
Frequency voltage current converter
Limit frequency 40 kHz, Voltage or current ouptput, Incrementing output
(Spacing factor 1 ... 9999), Multi-range power pack, 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable, Rated voltage: 200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC ... 30 VDC, Connectable sensor types: NAMUR sensors according to DIN EN 60947-5-6, Connection: terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
KCD2-E1
Sensor output interface terminal
1-channel terminal amplifier, NAMUR sensor input, DC 24 V supply voltage, Standard interface for prevention of signal transmission errors, Switching status indicator, yellow LED
KCD2-E3
Sensor output interface terminal
1-channel terminal amplifier, NAMUR sensor input, DC 24 V supply voltage, Standard interface for prevention of signal transmission errors, Switching status indicator, yellow LED
KCD2-EL
Sensor output interface terminal
1-channel terminal amplifier, NAMUR sensor input, DC 24 V supply voltage, Standard interface for prevention of signal transmission errors, Switching status indicator, yellow LED
KFU8-UFT-2.D.FA
Frequency Converter with Direction and Synchronization Monitor
2-channel signal conditioner, Universal usage at different power supplies, Dry contact or NAMUR inputs, Input frequency 1 mHz ... 1 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Configurable by PACTware or keypad, Line fault detection (LFD), Rated voltage: 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz, Input I, II: 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact, Output I, II: signal, relay, Output V: analog
K23-SSI/Rx/IU-C
Signal Converter
Multifunction device with operating modes for incremental rotary encoders, SSI absolute rotary encoders, and rotary encoders with start/stop interface, 16 bit analog output, configurable for voltage or current operations, USB interface and RS232/RS485 interface for configuration and readout, Extremely short conversion times, User-definable, non-linear characteristic curve with 24 interpolation points, Operating voltage: 18 ... 30 V DC, Input type: Incremental
K23-SSI/USB/25B-C
Signal Converter
Multifunction device with operating modes for incremental rotary encoders, SSI absolute rotary encoders, and rotary encoders with start/stop interface, USB interface for configuring and reading, Extremely short conversion times, User-definable, non-linear characteristic curve with 24 interpolation points, Auxiliary voltage output 5 V DC and 24 V DC for rotary encoder supply, Operating voltage: 10 ... 30 V DC, Input type: Incremental, Input format: RS422, TTL, HTL differential, HTL PNP, or HTL NPN
KFU8-UFC-1.D.FA
Frequency Converter with Trip Values
1-channel signal conditioner, Universal usage at different power supplies, Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz ... 10 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Frequency conversion, Rotation speed monitoring, Pulse divider
KFU8-FSSP-1.D-Y322444
Frequency voltage current converter
Limit frequency 40 kHz, Voltage or current ouptput, Incrementing output
(Spacing factor 1 ... 9999), 2-, 3-, 4-wire sensors and rotary encoder can be connected, Auxiliary power output for sensors, Rated voltage: 20 ... 30 V DC, Connection: terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated), Analog voltage output: 0 ... 10 V DC; 2 ... 10 V DC; 30 mA max.; resolution: 12 mV; Ri ≅ 330 Ω (terminal 5+, 6-)