Thông tin nổi bật

Product Description

- The 6.2 mm wide MINI MCR-SL-RPS-I-I... repeater power supply supplies transmitters in the field and electrically isolates the input signal from the output signal. The module can be used in both isolator and repeater power supply operation.

- Electrically isolated 0...20 mA or 4...20 mA analog standard signals are available on the input and output side.

- The power supply (19.2 V DC to 30 V DC) can be supplied via connection terminal blocks on the modules or in conjunction with the DIN rail connector.

 

Your advantages

- Power supply possible via the foot element (TBUS)
- Can be used as an isolator with passive input
- Highly-compact repeater power supplies for electrical isolation, amplification, and filtering of standard analog signals
- 3-way isolation
- Supply of 2-wire and passive 3-wire sensors

   

 

Drawing


Application drawing
Repeater power supply operation with a passive sensor


Application drawing
Isolator operation with an active sensor


Application drawing
Isolator operation at the analog output module


Block diagram


Dimensional drawing

 

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area


 

Dimensions

Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm


 

Ambient conditions

Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.


 

Input data

Description of the input Current input (sensor circuit)
Number of inputs 1
Current input signal 4 mA ... 20 mA (repeater power supply and isolator operation)
  0 mA ... 20 mA (isolator operation)
Max. input current 28 mA
Input resistance current input approx. 50 Ω
Transmitter supply voltage U- max. 4.5 V for load 0 mA ... 20 mA
Transmitter supply voltage range 14.7 V DC ... 25.5 V DC


 

Output data

Output name Current output
Number of outputs 1
Current output signal 4 mA ... 20 mA (repeater power supply and isolator operation)
  0 mA ... 20 mA (isolator operation)
Max. output current 28 mA
Load/output load current output ≤ 500 Ω (I = 20 mA)
Ripple < 20 mVrms (at 500 Ω)
Transmission Behavior 1:1 to input signal


 

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Power consumption < 900 mW (at 24 V DC and in repeater power supply operation)
  < 600 mW (at 24 V DC and in isolator operation)


 

Connection data

Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12


 

General

No. of channels 1
Maximum transmission error ≤ 0.2 % (of final value)
Transmission error, typical ≤ 0.1 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Limit frequency (3 dB) approx. 100 Hz
Step response (10-90%) approx. 3.5 ms
Protective circuit Transient protection
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions To bridge the supply voltage, the DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2


 

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 10 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 10 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 10 %


 

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
  EN 61000-4-4
  EN 61000-4-5
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electrical isolation Basic insulation according to EN 61010
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
  Class I, Div. 2, Groups A, B, C, D T5
GL GL EMC 2 D


 

Conformance/approvals

Designation CE
Identification CE-compliant
Designation ATEX
Identification  II 3 G Ex nA IIC T4 Gc X
Designation UL, USA/Canada
Identification UL 508 Recognized
  Class I, Div. 2, Groups A, B, C, D T5
Designation GL
Identification GL EMC 2 D


 

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
  For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


 

Classifications

eCl@ss

eCl@ss 4.0 27210100
eCl@ss 4.1 27210100
eCl@ss 5.0 27210100
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120


 

ETIM

ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653


 

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
UNSPSC 18.0 39121008
UNSPSC 19.0 39121008
UNSPSC 20.0 39121008
UNSPSC 21.0 39121008
 

- Xem chi tiết Tài liệu kỹ thuậ, Hướng dẫn sử dụng/ Datasheet, Manuals, Catalogue Repeater power supply MINI MCR-SL-RPS-I-I - 2864422 Phoenix Contact


SẢN PHẨM XEM NHIỀU
Gọi điện thoại