Chi tiết thông tin đặc tính sản phẩm
Protector trip relay - Crompton Instruments - 250 Series - Combined Under/Over-Voltage and Frequency
Features
- Adjustable set point
- Adjustable time delay
- Internal differential
- LED trip indication
- Double-pole relay contacts
- Automatic reset
Benefits
- Over and under-voltage monitoring
- Over and under-speed monitoring
- Start standby generators
- Operation of mains failure units
- Switching standby supplies
- Monitors genset AVR and excitation systems
- Nuisance tripping avoidance
- Customised options
Applications
- Switchgear
- Distribution systems
- Generator sets
- Control panels
- Process control
- Motor protection
- Transformers
- Overload protection
Operation
Combined voltage and frequency protectors provide the most popular relay functions in one convenient package. The products offer user adjustable trip point (set point) for voltage and frequency, plus adjustable time delay settings. The set point adjustment range is 25%, operating between 75% and 100% of the nominal supply for under-voltage and between 100% and 125% for over-voltage. The frequency set point adjustment range is centred around the nominal 50Hz, 60Hz or 400Hz system frequency. The time delay setting adjustment range is typically 0 to 10 seconds, although longer delays are available.
As soon as the monitored signal moves outside of the set point limit, the time delay is activated, after which a trip will occur. The time delay prevents the relay from tripping for a predetermined period to prevent nuisance tripping. The products also feature an internal differential (hysteresis) setting of 1% to reduce nuisance tripping if the measured signal is noisy or unstable. The product is available for single-phase systems only and draws its operating power from the measuring input.
Over-Voltage and Frequency
When the monitored value exceeds the set point and the time delay has elapsed, the relay will energise and the red LED will illuminate to indicate the trip condition.
Under-Voltage and Frequency
The relay will de-energise after the time delay has elapsed and the red LED will extinguish to indicate the trip condition.
Options
250 series protector relays offer various customised options to suit individual requirements. Please consult factory.
- Adjustment ranges – different adjustment ranges are possible for the set point and time delay controls.
- Differential – internally fixed value between 1% and 15%.
- Relay operation – standard models are fail safe, but the relays can be customised to energise or de-energise on trip.
Product Codes
Relay |
Protection |
ANSI no. |
Cat. no. |
1-phase |
Over and under-voltage, |
27/59 |
256-PHV |
|
Over and under-frequency |
|
|
Please specify system voltage, frequency and required options at time of ordering.
Specification – Combined Under/Over and Frequency
Nominal voltage |
100V, 110V, 120V, 208V, 220V, 270V, 280V, 400V, 415V or 440V |
System frequency |
40/60Hz, 50/70Hz or 360/440Hz |
Frequency differential |
Pre-set at 0.1Hz (10Hz for 400Hz unit) |
Voltage burden |
3VA |
Overloads |
1.2 x rating continuously, 1.5 x rating for 10 x seconds |
Set point repeatability |
>0.5% of full span |
Differential (hysteresis) |
Fixed internally at 1% |
Trip level adjustment |
Over-voltage: 100 to 125% |
|
Under-voltage: 75 to 100% of nominal input voltage |
Time delay |
Adjustable 1 to 30 seconds |
Output relay |
4 independent 2-pole change over |
Relay contact rating |
AC: 240V 5A non inductive |
|
DC: 24V 5A resistive |
Relay mechanical life |
0.2 million operations at rated loads |
Relay reset |
Automatic |
Operating temperature |
0°C to +60°C (0°C to +40°C for UL models) |
Storage temperature |
–20°C to +70°C |
Temperature co-efficient |
0.05% per °C |
Interference immunity |
Electrical stress surge withstand and non-function to ANSI/IEEE C37 90a |
Enclosure style |
DIN-rail with wall mounting facility |
Material |
Flame retardant polycarbonate/ABS |
Enclosure integrity |
IP50 |
Dimensions |
Dimensions 150mm (5.9") wide x 70mm (2.8") high x 112mm (4.4") deep |
Weight 1.0Kg approx. |
Weight 1.0Kg approx. |
Connections
256-PHV
Dimensions
Model 256
Danh mục sản phẩm
System |
Input |
Protection |
Catalog Number |
Combined Under/Over Voltage and Under/Over Frequency |
Single Phase |
120V / 60 Hz |
Over & Under Voltage
Over & Under Frequency (50-70 Hz)
(4 Independent Double Pole change over relays) |
256-PHUV-PQBX-C6 |