Protector trip relay - Crompton Instruments - 250 Series - DC Millivolts/Thermocouple
Features
- High and low trip models
- Adjustable set point
- Adjustable time delay
- Internal differential
- LED trip indication
- Automatic reset
- Double-pole relay contacts
- Supports all industry standard shunts and popular thermocouples Benefits
- Under/over-temperature monitoring
- Under/over-current monitoring
- Monitoring of battery charging currents and current drain
- Detection of hotspots
- Nuisance tripping avoidance
- Customised options
Applications
- Switchgear
- Distribution systems
- Generator sets
- Control panels
- Process control
- Motor protection
- Transformers
- Overload protection
Operation
When used in conjunction with current shunts the millivolt protector can be used to monitor battery charging currents, current drain or under/over-current. Monitoring of under/over-temperature and detection of hotspots can be achieved in applications using thermocouples. All industry standard shunts and all popular thermocouples are supported.
The millivolt protector relays offer user adjustable trip point (set point) and time delay settings. The time delay setting adjustment range is typically 0 to 10 seconds, although longer delays are available. As soon as the monitored signal moves outside of the set point limit, the time delay is activated, after which a trip will occur. The time delay prevents the relay from tripping for a predetermined period
to prevent nuisance tripping. These products also feature an internal differential (hysteresis) setting of 1% to reduce nuisance tripping if the measured signal is noisy or unstable. These units require an auxiliary power supply.
Over High Trip Models
When the monitored signal exceeds the set point, the time delay is started. When the time has elapsed, the relay will energise and the red LED will illuminate to indicate the trip condition. The relay will automatically reset once the monitored signal falls below the set point minus the differential. When reset, the LED will extinguish and the relay de-energises. The time delay is not active when resetting.
Under Low Trip Models
When the monitored signal falls below the set point, the time delay is started.
When the time has elapsed, the relay will de-energise and the red LED will extinguish to indicate the trip condition. The relay will automatically reset once the monitored signal rises above the set point plus the differential. When reset, the LED will illuminate and the relay energises. The time delay is not active when resetting.
Options
250 series protector relays offer various customised options to suit individual requirements. Please consult factory.
- Adjustment ranges – different adjustment ranges are possible for the set point and time delay controls.
- Differential – internally fixed value between 1% and 15%.
- Relay operation – standard models are failsafe, but the relays can be customised to energise or de-energise on trip.
- Cold junction compensation available on request.
Product Codes
Relay |
Protection |
ANSI no. |
Cat. no. |
DC millivolt |
High trip 40 to 120% |
74 |
252-PBT |
DC millivolt |
Low trip 0 to 80% |
74 |
252-PBS |
Thermocouple |
Type J, K, R, S and T. |
49 |
252-PTO |
|
High trip 40 to 120% |
|
|
Thermocouple |
Type J, K, R, S and T. |
49 |
252-PTU |
|
Low trip 0 to 80% |
|
|
For models 252-PBS and 252-PBT please specify millivolt input, auxiliary voltage and required options at time of ordering.
For models 252-PTO and 252-PTU please specify thermocouple type, nominal temperature, auxiliary voltage and required options at time of ordering.
Specification – DC Millivolts/Thermocouple
DC input |
10mV, 50mV, 60mV, 75mV, 100mV, 150mV |
Input impedance 50KΩ |
50KΩ |
Source impedance |
100Ω maximum |
Thermocouple |
Types J, K, R, S, T 10 to 50mV |
Thermocouple TBP |
Thermocouple break protection upscale drive as standard |
Thermocouple CJC |
Cold junction compensation available on request |
Thermocouple overload |
10 x rating continuously |
Nominal frequency |
50/60Hz |
Voltage burden |
3VA maximum |
Voltage overload |
1.2 x rating continuously, 1.5 x rating for 10 seconds |
Set point repeatability |
>0.5% of full span |
Differential (hysteresis) |
Pre-set at 1% |
Values |
1 to 15% available on request |
Trip level adjustment |
Low trip: 0 to 80% |
|
High trip: 40 to 120% |
Time delay adjustable |
0 to 10 seconds |
AC auxiliary supply voltage |
100V, 110V, 120V, 208V, 220V, 240V, 480V, ±20% |
DC auxiliary supply voltage 12V, 24V, 48V, 110V or 125V, ±20%. |
12V, 24V, 48V, 110V or 125V, ±20%. Including ripple |
Auxiliary voltage burden |
4VA (max) |
Output relay |
2-pole change over |
Relay contact rating |
AC: 240V 5A non inductive |
|
DC: 24V 5A resistive |
Relay mechanical life |
0.2 million operations at rated loads |
Relay reset |
Automatic |
Operating temperature |
0°C to +60°C (0°C to +40°C for UL models) |
Storage temperature |
–20°C to +70°C |
Temperature co-efficient |
0.05% per °C |
Interference immunity |
Electrical stress surge withstand and non-function to ANSI/IEEE C37 90a |
Enclosure style |
DIN-rail with wall mounting facility |
Material |
Flame retardant polycarbonate/ABS |
Enclosure integrity |
Enclosure integrity IP50 |
Dimensions |
55mm (2.2") wide x 70mm (2.8") high x 112mm (4.4") deep |
Weight |
0.4Kg approx. |
Dimensions
Model 252
Connections
252-PBT
252-PBS
252-PTU
252-PTO
Danh mục sản phẩm
System |
Input |
Protection Aux Power |
Catalog Number |
DC Millivolts/Thermocouple |
DC Millivolt |
50 mV |
High Trip 120V |
252-PBTU-ECBX-DG-T1-EA |
DC Millivolt |
50 mV |
Low Trip 120V |
252-PBSU-ECBX-DG-T1-EA |
DC Millivolt |
100 mV |
High Trip 120V |
252-PBTU-GBBX-DG-T1-EA |
DC Millivolt |
100 mV |
Low Trip 120V |
252-PBSU-GBBX-DG-T1-EA |
Thermocouple** |
J,K,T,S,T |
High Trip 120V |
252-PTOU-T*BX-DB-T1-EA |
Thermocouple** |
J,K,T,S,T |
Low Trip 120V |
252-PTUU-T*BX-DB-T1-EB |