SMART Transmitter power supply Pepperl Fuchs HiD2022 | 239365
Thông số kỹ thuật HiD2022
General specifications |
Signal type |
Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 2 |
Systematic capability (SC) |
SC 3 |
Supply |
Connection |
SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage |
18 ... 30 V DC bus powered via Termination Board |
Ripple |
within the supply tolerance |
Power dissipation |
≤ 1.4 W |
Power consumption |
≤ 2.6 W |
Input |
Connection side |
field side |
Connection |
SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-) |
Input signal |
4 ... 20 mA , current limit 27 mA |
Input resistance |
max. 265 Ω SL2: 5b, 7a; 1b, 3b ; max. 330 Ω SL2: 5a, 7a; 1a, 3b |
Available voltage |
≥ 16 V at 20 mA , SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
Output |
Connection side |
control side |
Connection |
SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
Load |
0 ... 650 Ω |
Output signal |
4 ... 20 mA (overload > 25 mA) |
Ripple |
max. 50 µA rms |
Transfer characteristics |
Deviation |
at 20 °C (68 °F), 4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
|
Influence of ambient temperature |
≤ 0.25 µA/K |
Frequency range |
field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB) |
Settling time |
200 µs |
Rise time/fall time |
100 µs |
Galvanic isolation |
Output/power supply |
functional insulation, rated insulation voltage 50 V AC |
Output/Output |
functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements |
LED |
Labeling |
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility |
NE 21:2012
EN 61326-3-2:2008 |
Degree of protection |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Relative humidity |
5 ... 90 %, non-condensing up to 35 °C (95 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Mass |
approx. 140 g |
Dimensions |
18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D) |
Mounting |
on termination board |
Coding |
pin 1 and 3 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-type examination certificate |
CML 17 ATEX 2143X |
|
Marking |
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
|
Input |
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply |
|
|
Maximum safe voltage |
250 V (Attention! The rated voltage can be lower.) |
Equipment |
SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
|
Voltage |
26.2 V |
|
Voltage |
27.25 V |
|
Current |
93 mA |
|
Power |
634 mW |
Equipment |
SL2: 5b(+), 7a(-); 1b(+), 3b(-) |
|
Voltage |
30 V |
|
Current |
115 mA |
|
Power |
max 1 W |
|
Voltage |
2 V |
|
Current |
8.5 mA |
|
Power |
4.3 mW |
Equipment |
SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-) |
|
Voltage |
26.2 V |
|
Voltage |
27.25 V |
|
Current |
115 mA |
|
Power |
784 mW |
Certificate |
CML 17 ATEX 3144X |
|
Marking |
II 3G Ex ec IIC T4 Gc |
Galvanic isolation |
|
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V |
Directive conformity |
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
IECEx approval |
|
|
IECEx certificate |
IECEx CML 17.0072X |
|
IECEx marking |
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc |
General information |
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System |
Classcode |
ECLASS 13.0 |
27210119 |
ECLASS 12.0 |
27210119 |
ECLASS 11.0 |
27210119 |
ECLASS 10.0.1 |
27210119 |
ECLASS 9.0 |
27210119 |
ECLASS 8.0 |
27210119 |
ECLASS 5.1 |
27210119 |
ETIM 9.0 |
EC001485 |
ETIM 8.0 |
EC001485 |
ETIM 7.0 |
EC001485 |
ETIM 6.0 |
EC001485 |
ETIM 5.0 |
EC001485 |
UNSPSC 12.1 |
32101514 |
- Tài liệu kỹ thuật Pepperl Fuchs HiD2022 | 239365
ở đây.
Tham khảo thêm các model khác cùng loại:
HiC2027
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 20 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2025
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: current source
HiC2025ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2027ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: current source
HiC2441
SMART Universal Barrier
1-channel isolated barrier, 24 V DC supply (bus powered), Analog input, digital input,
analog output, digital output, No configuration required, device is self-adapting, HART transparency, Low power dissipation, 3-way isolation, Up to SIL 2 acc. to IEC/EN 61508
HiC2025HC
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Suitable for long field cables (> 1000 m), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD2022
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (bus powered), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA, current source, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter
HiD2024
SMART Transmitter Power Supply/Current Driver
Add to Watch List
4-channel isolated barrier, 24 V DC supply (bus powered), Analog in or analog out signals, Sink and source mode outputs, SMART pass-through, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 4-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
HiD2030
SMART Transmitter Power Supply
Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA or 1 V ... 5 V, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2025A
SMART Transmitter Power Supply
Add to Watch List
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Reduced intrinsically safe parameters, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD2022SK
SMART Transmitter Power Supply
Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA, current sink, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 18 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current source
HiD2030SK
SMART Transmitter Power Supply
Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA, current sink, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD-CI-AI1-SET
Adapter Set HiD Device for Contrans I socket
Add to Watch List
Set consisting of isolated barrier HiD2030 and adapter HiD-ADP-CI, 2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitter, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA or 1 V ... 5 V, Mounting to a V17111-110 Contrans I socket, Housing width: 18 mm, Number of channels: 2-channel, HART communication