SMART Transmitter power supply Pepperl Fuchs HiD2022 | 239365

SMART Transmitter power supply Pepperl Fuchs HiD2022 | 239365

609
Nhà sản xuất:

Pepperl-Fuchs

;   

Xuất xứ: Germany

Giá sỉ:

Giá tốt nhất xem...0909186879 dienelectrics@gmail.com

Khuyến mãi:Có Discount
Bảo hành:12 Tháng (Chính hãng)
Thanh toán:C.O.D / Bảo lãnh TT / Link hoạt
Vận chuyển:Miễn phí Tp.HCM, vùng lân cận
Thông tin nổi bật

SMART Transmitter power supply Pepperl Fuchs HiD2022 | 239365

 

Thông số kỹ thuật  HiD2022

General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage 18 ... 30 V DC bus powered via Termination Board
Ripple within the supply tolerance
Power dissipation ≤ 1.4 W
Power consumption ≤ 2.6 W
Input
Connection side field side
Connection SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
Input signal 4 ... 20 mA , current limit 27 mA
Input resistance max. 265 Ω SL2: 5b, 7a; 1b, 3b ; max. 330 Ω SL2: 5a, 7a; 1a, 3b
Available voltage ≥ 16 V at 20 mA , SL2: 5a(+), 5b(-); 1a(+), 1b(-)
Output
Connection side control side
Connection SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Load 0 ... 650 Ω
Output signal 4 ... 20 mA (overload > 25 mA)
Ripple max. 50 µA rms
Transfer characteristics
Deviation at 20 °C (68 °F), 4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
  Influence of ambient temperature ≤ 0.25 µA/K
Frequency range field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Settling time 200 µs
Rise time/fall time 100 µs
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Output/Output functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility  
  Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012
EN 61326-3-2:2008
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 140 g
Dimensions 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Mounting on termination board
Coding pin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificate CML 17 ATEX 2143X
  Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
  Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply  
  Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Equipment SL2: 5a(+), 5b(-); 1a(+), 1b(-)
  Voltage 26.2 V
  Voltage 27.25 V
  Current 93 mA
  Power 634 mW
Equipment SL2: 5b(+), 7a(-); 1b(+), 3b(-)
  Voltage 30 V
  Current 115 mA
  Power max 1 W
  Voltage 2 V
  Current 8.5 mA
  Power 4.3 mW
Equipment SL2: 5a(+), 5b, 7a(-); 1a(+), 1b, 3b(-)
  Voltage 26.2 V
  Voltage 27.25 V
  Current 115 mA
  Power 784 mW
Certificate CML 17 ATEX 3144X
  Marking Ex-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation  
  Input/Output safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
  Input/power supply safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Directive conformity  
  Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
IECEx approval  
  IECEx certificate IECEx CML 17.0072X
  IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

 

Classifications

System Classcode
ECLASS 13.0 27210119
ECLASS 12.0 27210119
ECLASS 11.0 27210119
ECLASS 10.0.1 27210119
ECLASS 9.0 27210119
ECLASS 8.0 27210119
ECLASS 5.1 27210119
ETIM 9.0 EC001485
ETIM 8.0 EC001485
ETIM 7.0 EC001485
ETIM 6.0 EC001485
ETIM 5.0 EC001485
UNSPSC 12.1 32101514


- Tài liệu kỹ thuật Pepperl Fuchs HiD2022 | 239365 ở đây.


Tham khảo thêm các model khác cùng loại:
HiC2027
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 20 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2025
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: current source
HiC2025ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Sink or source mode, Line fault detection (LFD), Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2027ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: current source
HiC2441
SMART Universal Barrier
1-channel isolated barrier, 24 V DC supply (bus powered), Analog input, digital input,
analog output, digital output, No configuration required, device is self-adapting, HART transparency, Low power dissipation, 3-way isolation, Up to SIL 2 acc. to IEC/EN 61508
HiC2025HC
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Suitable for long field cables (> 1000 m), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD2022
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (bus powered), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA, current source, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 18 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter
HiD2024
SMART Transmitter Power Supply/Current Driver
 Add to Watch List
4-channel isolated barrier, 24 V DC supply (bus powered), Analog in or analog out signals, Sink and source mode outputs, SMART pass-through, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 4-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20.4 ... 30 V DC bus powered via Termination Board
HiD2030
SMART Transmitter Power Supply
 Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA or 1 V ... 5 V, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiC2025A
SMART Transmitter Power Supply
 Add to Watch List
1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Output for 4 mA ... 20 mA or 1 V ... 5 V, Low power dissipation, Reduced intrinsically safe parameters, Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD2022SK
SMART Transmitter Power Supply
 Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 4 mA ... 20 mA, current sink, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: 18 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter, Field device [2]: 3-wire transmitter, Field device [3]: current source
HiD2030SK
SMART Transmitter Power Supply
 Add to Watch List
2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitters or current sources, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA, current sink, Line fault detection (LFD), Up to SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 18 mm, Number of channels: 2-channel, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC bus powered via Termination Board, Field device: 2-wire transmitter
HiD-CI-AI1-SET
Adapter Set HiD Device for Contrans I socket
 Add to Watch List
Set consisting of isolated barrier HiD2030 and adapter HiD-ADP-CI, 2-channel isolated barrier, 24 V DC supply (bus powered), 2-wire SMART transmitter, Usable as signal splitter (1 input and 2 outputs), Dual output 4 mA ... 20 mA or 1 V ... 5 V, Mounting to a V17111-110 Contrans I socket, Housing width: 18 mm, Number of channels: 2-channel, HART communication
SẢN PHẨM XEM NHIỀU
Gọi điện thoại