The MICROMASTER 430 inverter is suitable for a variety of variable-speed drive applications. Its flexibility provides for a wide spectrum of applications. It is especially suitable for use with industrial pumps and fans.
The inverter is especially characterized by its customer-oriented performance and ease-of-use. It has more inputs and outputs than the MICROMASTER 420, an optimized operator panel with manual/automatic switchover, and adapted software functionality.
The MICROMASTER 430 inverter has a modular design. The operator panels and communication modules can be easily exchanged.
Technical data |
MICROMASTER 430 |
|||||
---|---|---|---|---|---|---|
Mains voltage and power ranges |
380 V to 480 V 3 AC ±10 % |
7.5 kW to 250 kW (variable torque) |
||||
Power frequency |
47 Hz to 63 Hz |
|||||
Output frequency |
for inverter 7.5 kW to 90 kW |
0 ... 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1) |
||||
for inverter 110 kW to 250 kW |
0 Hz to 267 Hz |
|||||
Power factor |
≥ 0.95 |
|||||
Inverter efficiency
|
for inverter 7.5 kW to 90 kW |
96 % to 97 % |
||||
for inverter 110 kW to 250 kW |
97 % to 98 % |
|||||
(Further information is available on the Internet at: |
||||||
Overload capability
|
for inverter 7.5 kW to 90 kW |
Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s |
||||
for inverter 110 kW to 250 kW |
Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s |
|||||
Inrush current |
less than rated input current |
|||||
Control method |
linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC); energy saving mode |
|||||
Pulse frequency |
for inverter 7.5 kW to 90 kW |
4 kHz (standard) |
||||
for inverter 110 kW to 250 kW |
2 kHz (standard) |
|||||
Fixed frequencies |
15, programmable |
|||||
Skip frequency ranges |
4, programmable |
|||||
Setpoint resolution |
0.01 Hz digital |
|||||
Digital inputs |
6 fully programmable isolated digital inputs; switchable PNP/NPN |
|||||
Analog inputs |
2 programmable analog inputs 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (AIN1)0 V to 10 V and 0 mA to 20 mA (AIN2) both can be used as 7th/8th digital input |
|||||
Relay outputs |
3, programmable |
|||||
Analog outputs |
2, programmable (0/4 mA to 20 mA) |
|||||
Serial interfaces |
RS-485, option RS-232 |
|||||
Motor cable length |
for inverter 7.5 kW to 90 kW |
Without output choke |
max. 50 m (shielded) |
|||
With output choke |
See variant dependent options |
|||||
for inverter 110 kW to 250 kW |
Without output choke |
max. 200 m (shielded) |
||||
With output choke |
See variant dependent options |
|||||
Electromagnetic compatibility
|
for inverter 7.5 kW to 90 kW |
Inverter with internal filter Class A available |
||||
for inverter without filter |
7.5 kW to 15 kW |
EMC filter Class B to EN 55 011 available as an option |
||||
18.5 kW to 90 kW |
EMC filter Class B from Schaffner available as an option |
|||||
110 kW to 250 kW |
EMC filter Class A available as an option |
|||||
Braking |
DC braking, compound braking |
|||||
Degree of protection |
IP20 |
|||||
Operating temperature range
|
for inverter 7.5 kW to 90 kW |
-10 °C to +40 °C (+14 °F to +104 °F) |
||||
for inverter 110 kW to 250 kW |
0 °C to +40 °C (+32 °F to +104 °F) |
|||||
Storage temperature |
-40 °C to +70 °C (-40 °F to +158 °F) |
|||||
Relative humidity |
95 % (non-condensing) |
|||||
Installation altitude
|
for inverter 7.5 kW to 90 kW |
up to 1000 m above sea level without derating |
||||
for inverter 110 kW to 250 kW |
up to 2000 m above sea level without derating |
|||||
Standard SCCR |
FSC: 100 kA |
|||||
Protection features for |
undervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection |
|||||
Conformity with standards |
for inverter 7.5 kW to 90 kW |
UL, cUL, CE, c-tick |
||||
for inverter 110 kW to 250 kW |
UL available soon, cUL available soon, CE |
|||||
CE marking |
Conformity with low-voltage directive 73/23/EEC |
|||||
Cooling-air volumetric flow required, dimensions and weights (without options)
|
Frame size (FS) |
Cooling-air volumetric flow required (l/s)/(CFM) |
H x W x D (mm) |
Weight, approx. (kg) |
||
C |
54.9/116.3 |
245 x 185 x 195 |
5.7 |
|||
D |
2 x 54.9/2 x 116.3 |
520 x 275 x 245 |
17 |
|||
E |
2 x 54.9/2 x 116.3 |
650 x 275 x 245 |
22 |
|||
F without filter |
150/317.79 |
850 x 350 x 320 |
56 |
|||
F with filter |
150/317.79 |
1150 x 350 x 320 |
75 |
|||
FX |
225/478.13 |
1400 x 326 x 356 |
116 |
|||
GX |
440/935 |
1533 x 326 x 545 |
174 |
|||
|
CFM: |
|
|
1) For further information see http://support.automation.siemens.com/WW/view/en/107669667
2) Applies to industrial control cabinet installations to NEC article 409/UL 508A.
Pulse frequency
Output |
Rated output current in A for a pulse frequency of |
|||||||
---|---|---|---|---|---|---|---|---|
kW |
2 kHz |
4 kHz |
6 kHz |
8 kHz |
10 kHz |
12 kHz |
14 kHz |
16 kHz |
7.5 |
19.0 |
19.0 |
17.1 |
15.2 |
13.3 |
11.4 |
9.5 |
7.6 |
11.0 |
26.0 |
26.0 |
24.7 |
23.4 |
20.8 |
18.2 |
15.6 |
13.0 |
15.0 |
32.0 |
32.0 |
28.8 |
25.6 |
22.4 |
19.2 |
16.0 |
12.8 |
18.5 |
38.0 |
38.0 |
36.1 |
34.2 |
30.4 |
26.6 |
22.8 |
19.0 |
22 |
45.0 |
45.0 |
40.5 |
36.0 |
31.5 |
27.0 |
22.5 |
18.0 |
30 |
62.0 |
62.0 |
55.8 |
49.6 |
43.4 |
37.2 |
31.0 |
24.8 |
37 |
75.0 |
75.0 |
71.3 |
67.5 |
60.0 |
52.5 |
45.0 |
37.5 |
45 |
90.0 |
90.0 |
81.0 |
72.0 |
63.0 |
54.0 |
45.0 |
36.0 |
55 |
110.0 |
110.0 |
93.5 |
77.0 |
63.3 |
49.5 |
41.3 |
33.0 |
75 |
145.0 |
145.0 |
123.3 |
101.5 |
83.4 |
65.3 |
54.4 |
43.5 |
90 |
178.0 |
178.0 |
138.0 |
97.9 |
84.6 |
71.2 |
62.3 |
53.4 |
110 |
205.0 |
180.4 |
- |
- |
- |
- |
- |
- |
132 |
250.0 |
220.0 |
- |
- |
- |
- |
- |
- |
160 |
302.0 |
265.8 |
- |
- |
- |
- |
- |
- |
200 |
370.0 |
325.6 |
- |
- |
- |
- |
- |
- |
250 |
477.0 |
419.8 |
- |
- |
- |
- |
- |
- |
CE marking
The MICROMASTER inverters meet the requirements of the Low-Voltage Directive 73/23/EEC.
Low-voltage directive
The inverters comply with the following standards listed in the Official Journal of the European Communities:
EN 60 204Safety of machinery, electrical equipment of machines
EN 61 800-5-1Electrical power drive systems with variable speed - Part 5-1: Requirements regarding safety - electrical, thermal and energy requirements
Machine directive
The inverters are suitable for installation in machines. Compliance with the machine directive 89/392/EEC requires a separate certificate of conformity. This must be furnished by the plant constructor or the installer of the machine.
EMC directive
Variable-speed electric drives
Part 3: EMC product standard including special test procedure.
The new EMC product standard EN 61 800-3 applies to electrical drive systems as of July 1, 2005. The transition period for the preceding standard EN 61 800-3/A11 dated February 2001 ends on October 1, 2007. The following explanations apply to frequency inverters of the 6SE6 series from Siemens:
- The EMC product standard EN 61 800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter.
Overview of MICROMASTER components and PDS categories
|
|
---|---|
First environment
|
Category C1 |
Category C2 |
|
Second environment
|
Category C2 |
Category C3 |
|
Category C4 |
Electromagnetic compatibility
No inadmissible electromagnetic emissions occur if the installation instructions specific to the product are correctly observed.
The table below lists the results of measurements relating to the emissions and immunity to interference of MICROMASTER inverters.
The inverters were installed with shielded motor cables and shielded control cables in accordance with the directives.
EMC phenomenon |
Relevant criteria |
Limit value |
|
---|---|---|---|
Emitted interference |
Conducted via mains cable |
150 kHz to 30 MHz |
Unfiltered devices, not tested. |
Emitted by the drive |
30 MHz to 1 GHz |
All devices. |
|
ESD immunity |
ESD through air discharge |
Test severity level 3 |
8 kV |
ESD through contact discharge |
Test severity level 3 |
6 kV |
|
Immunity to electrical fields |
Electrical field applied to unit |
Test severity level 3 80 MHz to 1 GHz |
10 V/m |
Immunity to burst interference |
Applied to all cable terminations |
Test severity level 4 |
4 kV |
Surge immunity |
Applied to mains cables |
Test severity level 3 |
2 kV |
Immunity to RFI emissions, conducted |
Applied to mains, motor and control cables |
Test severity level 3 |
10 V |
UL listing
UL and cUL listed power conversion equipment of UL category NMMS, in accordance with UL508C.
UL list number E121068 and E192450
For use in environments with pollution degree 2.
Also refer to the Internet at http://www.ul.com/