SINAMICS S150 converter cabinet units are particularly suitable for all variable-speed single-axis drives with high performance requirements, i.e. drives with:
- High dynamic requirements
SINAMICS S150 offers high-performance speed control with excellent accuracy and a high dynamic response.
The following voltages and power ratings are available:
Line voltage |
Type rating |
---|---|
380 ... 480 V 3 AC |
110 ... 800 kW |
500 ... 690 V 3 AC |
75 ... 1200 kW |
Degrees of protection are IP20 (standard) and optionally IP21, IP23, IP43 and IP54.
Line and motor-side components as well as additional monitoring devices can be installed in the converter cabinet units.
A wide range of electrical and mechanical components enable the drive system to be optimized individually to suit customer requirements.
SINAMICS S150 cabinet units have been designed for variable-speed drives in machine building and plant construction. They are particularly suitable for use with variable-speed drives with high requirements regarding dynamic response and speed accuracy, frequent braking cycles with high braking energies, and four-quadrant operation.
SINAMICS S150 offers high-performance speed control with high accuracy and dynamic response.
The cabinet units are available for an output range from 75 kW to 1200 kW.
Brief overview |
|
---|---|
Electrical data |
|
Supply voltages: |
Output ranges: |
Supply systems: |
TN/TT or IT |
Line frequency: |
47 to 63 Hz |
Output frequency: |
0 to 300 Hz |
Control method: |
Vector control with and without encoder, or V/f control |
Fixed frequencies: |
15 fixed frequencies plus 1 basic frequency, programmable |
Skipped frequency bands: |
4, programmable |
Customer terminal block: |
Digital inputs/outputs |
Communications interface: |
PROFIBUS DP as standard |
Braking mode: |
4-quadrant operation possible as standard |
Degree of protection: |
IP20; optionally: IP21, IP23, IP54 |
Type of cooling: |
Internal fan (forced air cooling) |
Noise level: |
≤ 78 dB (A) with 50 Hz line frequency |
Cabinet system: |
Rittal TS 8 |
Conformity: |
CE |
Software functions: |
- Smooth connection of converter to rotating motor |
Protection functions: |
Undervoltage, overvoltage, earth fault, short-circuit, stall prevention, thermal motor protection, thermal converter protection |
Safety functions: |
STO, SS1; |
Suitable motors: |
Induction motors |
Design:
SINAMICS S150 are ready-to-connect converters in a standard control cabinet.
A comprehensive range of options permits adaptation to the respective requirements.
Different designs permit the power supply and motor connections to be located at the top or bottom. This results in high flexibility for the plant installation.
They are available with cabinet widths from 1400 mm upwards in intervals of 200 mm. The standard degree of protection of the cabinets is IP20. It can be optionally extended up to IP54.
The user-friendly AOP30 operator panel is fitted as standard in the cabinet door.
- Regenerative feedback as standard, therefore unrestricted four-quadrant operation possible
- Significant energy savings, particularly with frequent braking cycles
- Highly exact and highly dynamic mains supply through use of IGBTs; robust in the case of line voltage fluctuations
- Injection of almost sinusoidal line current through fast current control
- An innovative clean power filter means that low-frequency reactions on the system are almost negligible. Losses in the low-voltage distribution and/or mains transformer and in the power supply line resulting from harmonic currents are therefore also avoided
- Possibility for compensation of reactive power (inductive or capacitive)
- Maximum servicing friendliness with easy accessibility to all modules
- Problem-free interfacing into automation solutions using a standard PROFIBUS interface and various analog and digital interfaces
- Increase in plant availability through easy, fast replacement of individual modules and power components
- Simple start-up and parameterization using interactive menus on the user-friendly AOP30 operator panel with LCD display incorporating graphics capability and plain text display
SINAMICS S150 is used wherever maximum requirements exist for process sequences with dynamic and reproducible procedures, e.g. :
- Moving: Belt conveyors, cranes, test stands
- Processing: Mechanical presses
- Branch Chemical IndustryThe self-commutating, pulsed infeed/regenerative unit uses IGBT technology and is equipped with a Clean Power Filter. This combination guarantees extremely line-friendly behavior which is characterized by the following:
- Negligible line harmonics as a result of the innovative Clean Power Filter (<< 1 %)
In addition, factors have been considered to ensure easy handling of the drive from the planning and design phase through to operation. These factors include:
SINAMICS S150 is especially suitable for use in all applications that place the highest demands on process operations with dynamic, reproducible processes. These include, for example:
- Test standsThe SINAMICS S150 converter cabinet units are characterized by their compact, modular and service-friendly design.
Design example of a SINAMICS S150 converter cabinet unit
Basic design of a SINAMICS S150 converter cabinet unit with a number of version-specific options
The coating on the modules protects the sensitive SMD components against corrosive gases, chemically active dust and moisture.
All of the copper busbars used in the converter cabinets are nickel-plated in order to achieve the best possible immunity to environmental effects. Further, it is possible to eliminate having to clean the contacts at the customer connections, which is required for bare copper connections.
Note:
With some options, parts of the copper busbars cannot be nickel-plated for technical reasons.
The EN 60529 standard covers the protection of electrical equipment by means of housings, covers or equivalent, and includes:
- Protection of persons against accidental contact with live or moving parts within the housing and protection of the equipment against the ingress of solid foreign bodies (touch protection and protection against ingress of solid foreign bodies)The degrees of protection are specified by abbreviations comprising the code letters IP and two digits.
Degree of protection |
First digit (Touch protection and protection against foreign bodies) |
Second digit (Protection of equipment against the ingress of water) |
---|---|---|
IP20 (Standard) |
Protected against solid foreign bodies |
No water protection |
IP21 (Option M21) |
Protected against solid foreign bodies |
Protected against drip water Vertically falling water drops must not have any harmful effects. |
IP23 (Option M23) |
Protected against solid foreign bodies |
Protected against spray water Water sprayed on both sides of the vertical at an angle of up to 60° shall not have a harmful effect. |
IP43 (Option M43) |
Protected against solid foreign bodies |
Protected against spray water Water sprayed on both sides of the vertical at an angle of up to 60° shall not have a harmful effect. |
IP54 (Option M54) |
Dust protected Ingress of dust is not totally prevented, but dust must not be allowed to enter in such quantities that the functioning or safety of the equipment is impaired. |
Protected against splash water Water splashing onto the housing from any direction must not have any harmful effects. |
An Advanced Operator Panel (AOP30) is installed in the cabinet door of the converter for operation, monitoring and commissioning tasks.
The user is guided by interactive menus through the drive commissioning screens. When the drive is commissioned for the first time, only 6 motor parameters (which can be found on the motor rating plate) have to be entered on the AOP30. The closed-loop control is then optimized automatically to adapt the converter to the motor.
The AOP30's two-stage safety concept prevents unintentional or unauthorized changes to settings. Operation of the drive from the operator panel can be disabled by the keyboard lock and so that only parameter values and process variables can be displayed on the operator panel. The OFF key is factory-set to "active", but can be deactivated by the customer. A password can be used to prevent the unauthorized changing of converter parameters.
German, English, French, Italian, Spanish and Chinese are stored on the CU320‑2 Control Unit CompactFlash card as operator panel languages. The desired language must be downloaded to the AOP30 prior to commissioning. In addition to these standard operator panel languages, Russian can also be retro-installed. Further languages are available on request.
Examples of plain-text displays during various phases of operation are shown below.
The first commissioning is performed via the operator panel.
Only 6 motor parameters have to be entered: Power, speed, current, cos φ, voltage and frequency of the motor.
This information can be found on the motor rating plate, and must be entered in the screens on the display by following a short, menu-assisted procedure. The motor cooling method must also be specified.
The next screen contains the parameter values that are used to automatically optimize the control.
During operation, the display shows current data, such as setpoints and actual values as absolute values or it is possible to parameterize up to 3 process variables as a quasi-analog bar display.
Any alarms that occur are signaled by flashing of the yellow ALARM LED, faults by the red FAULT LED, which is then lit. There is also an indication of the cause displayed in plain text on the display's status line (with counter/remedial measures).
A PROFIBUS or PROFINET interface on the Control Unit CU320-2 is provided as standard as the customer control interface.
This interface can be used to connect the system to the higher-level controller using analog and digital signals, or to connect additional units.
The inputs and outputs available as standard can be optionally expanded by up to two Terminal Modules TM31 (refer to the description of options, option G60 or G61). To simplify configuration and commissioning of the drive, the TM31 Terminal Module can be preset to a variety of factory settings.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
SINAMICS S150 has a high-dynamic vector control with speed and current control – with and without speed actual value feedback.
The software functions available as standard are described below:
Software and protective functions |
Description |
---|---|
Setpoint input |
The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint or jog setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the motorized potentiometer setpoint can be switched or adjusted via control commands from any interface. |
Motor identification |
The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control of the drive. |
Ramp-function generator |
A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with adjustable rounding times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked. This results in a good speed control response and plays its role in reducing the stress on the mechanical system. The down ramps can be parameterized separately for quick stop. |
Vdc max controller |
The Vdc max controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for example. This may also extend the set ramp-down time. |
Kinetic buffering (KIP) |
For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents fault trips. The drive converter remains operational as long as the drive can provide regenerative energy as a result of its motion and the DC link voltage does not drop below the shutdown threshold. When the line supply recovers within this time, the drive is again bumplessly accelerated up to its setpoint speed. |
Automatic restart |
The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the current speed setpoint. |
Flying restart |
The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing capability provided by the optional VSM10, the flying restart time for large induction motors can be significantly reduced because the motor does not need to be de-magnetized. |
Technology controller |
The technology controller function module allows simple control functions to be implemented, e.g. level control or volumetric flow control and complex tension controls. The existing D component can act both on the system deviation well as on the actual value (factory setting). The P, I, and D components are set separately. |
Free function blocks |
Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the SINAMICS drive. The blocks can be programmed at the operator panel or the STARTER commissioning tool. |
SINAMICS Drive Control Chart (SINAMICS DCC) |
SINAMICS DCC is an additional tool for the easy configuration of technological functions for SINAMICS. The block library contains a large selection of control, arithmetic and logic blocks as well as extensive open-loop and closed-loop control functions. The user-friendly DCC editor enables easy graphics-based configuration, allows control loop structures to be clearly represented and provides a high degree of reusability of charts that have already been created. SINAMICS DCC is an add-on to the STARTER commissioning tool (→ Tools and Engineering). |
I2t sensing for motor protection |
A motor model stored in the converter software calculates the motor temperature based on the current speed and load. More exact measurement of the temperature, which also takes into account the influence of the ambient temperature, is possible by means of direct temperature measurement using KTY84 sensors in the motor winding. |
Motor temperature evaluation |
Motor protection by evaluating a KTY84, PTC or Pt100 temperature sensor. When a KTY84 temperature sensor is connected, the limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction to triggering of the thermistor (alarm or trip) can be defined. |
Motor blocking protection |
A blocked motor is detected and protected against thermal overloading by a fault trip. |
Brake control |
"Simple brake control" for control of holding brakes: "Extended brake control" function module for complex brake control, e.g. for motor holding brakes and operational brakes: |
Write protection |
Write protection to prevent unintentional changing of the setting parameters (without password function). |
Know-how protection |
Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against changes and duplication (with password function). |
Web server |
The integrated web server provides information about the drive unit via its web pages. The web server is accessed using an Internet browser via unsecured (http) or secured transmission (https). |
Power unit protection |
Description |
---|---|
Ground fault monitoring at the output |
A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems. |
Electronic short-circuit protection at the output |
A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected and the converter shuts down with a "fault". |
Thermal overload protection |
An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either shuts down or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the cause of the fault has been eliminated (e.g. cooling has been improved), the original operating values are automatically resumed. |
The most important directives and standards are listed below. These are used as basis for the SINAMICS S150 converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
European directives |
|
---|---|
2006/95/EC |
Low Voltage Directive: |
2004/108/EC |
EMC Directive: |
2006/42/EC |
Machinery Directive: |
European standards |
|
EN ISO 3744 |
Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound pressure measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflecting plane |
EN ISO 13849‑1 |
Safety of machinery – safety-related parts of control systems; |
EN 60146‑1‑1 |
Semiconductor converters – General requirements and line-commutated converters |
EN 60204‑1 |
Safety of machinery – Electrical equipment of machines; |
EN 60529 |
Degrees of protection provided by enclosures (IP code) |
EN 61508‑1 |
Functional safety of electrical/electronic/programmable electronic safety-related systems |
EN 61800‑2 |
Adjustable speed electrical power drive systems |
EN 61800‑3 |
Adjustable speed electrical power drive systems |
EN 61800‑5‑1 |
Adjustable speed electrical power drive systems |
EN 61800‑5‑2 |
Adjustable speed electrical power drive systems |
Electrical specifications |
|||
---|---|---|---|
Line voltages |
380 … 480 V 3 AC, ±10 % (-15 % <1 min) 500 … 690 V 3 AC, ±10 % (-15 % <1 min) |
||
Line supply types |
Grounded TN/TT systems and non-grounded IT systems |
||
Line frequency |
47 ... 63 Hz |
||
Output frequency 1) |
0 ... 550 Hz |
||
Line power factor |
Adjustable (factory-set to cos φ = 1) |
||
Efficiency |
>96 % |
||
Overvoltage category |
III to EN 61800‑5‑1 |
||
Control method |
Vector control with and without encoder or V/f control |
||
Fixed speeds |
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET) |
||
Skippable speed ranges |
4, parameterizable |
||
Setpoint resolution |
0.001 rpm digital (14 bits + sign) |
||
Braking operation |
Four-quadrant operation is possible as standard |
||
Mechanical specifications |
|||
Degree of protection |
IP20 (higher degrees of protection up to IP54 optional) |
||
Protection class |
I acc. to EN 61800‑5‑1 |
||
Touch protection |
EN 50274 / BGV A3 when used for the intended purpose |
||
Cabinet system |
Rittal TS8, doors with double-bit key, three-section base plates for cable entry |
||
Paint finish |
RAL 7035 (indoor requirements) |
||
Cooling method |
Forced air cooling AF according to EN 60146 |
||
Ambient conditions |
Storage 2) |
Transport 2) |
Operation |
Ambient temperature |
-25 ... +55 °C |
-25 ... +70 °C from -40 °C for 24 hours |
0 ... 40 °C to +50 °C, see derating data |
Relative humidity (condensation not permissible) |
5 ... 95% Class 1K4 acc. to IEC 60721‑3‑1 |
5 ... 95 % at 40 °C Class 2K3 acc. to IEC 60721‑3‑2 |
5 ... 95% Class 3K3 acc. to IEC 60721‑3‑3 |
Environmental class/harmful chemical substances |
Class 1C2 acc. to IEC 60721‑3‑1 |
Class 2C2 acc. to IEC 60721‑3‑2 |
Class 3C2 acc. to IEC 60721‑3‑3 |
Organic/biological influences |
Class 1B1 acc. to IEC 60721‑3‑1 |
Class 2B1 acc. to IEC 60721‑3‑2 |
Class 3B1 acc. to IEC 60721‑3‑3 |
Degree of pollution |
2 acc. to EN 61800‑5‑1 |
||
Installation altitude |
Up to 2000 m above sea level without derating; |
||
Mechanical stability |
Storage 2) |
Transport 2) |
Operation |
Vibratory load |
Class 1M2 acc. to IEC 60721‑3‑1 |
Class 2M2 acc. to IEC 60721‑3‑2 |
– |
|
1.5 mm at 5 ... 9 Hz 3) |
3.1 mm at 5 ... 9 Hz 3) |
0.075 mm at 10 ... 58 Hz |
|
5 m/s² at >9 ... 200 Hz |
10 m/s² at 9 ... 200 Hz |
9.8 m/s2 at 58 ... 200 Hz |
Shock load |
Class 1M2 acc. to IEC 60721‑3‑1 |
Class 2M2 acc. to IEC 60721‑3‑2 |
Class 3M4 acc. to IEC 60721‑3‑3 |
|
40 m/s² at 22 ms |
100 m/s² at 11 ms |
100 m/s2 at 11 ms |
Compliance with standards |
|||
Conformances/approvals, according to |
CE (EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive No. 2006/42/EC for functional safety) |
||
Radio interference suppression |
SINAMICS drive converter systems are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800‑3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if additional measures are taken (e.g. line filter), it can also be operated in the "first environment". |
1)Please note:
- The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies on request.
- The correlation between the maximum output frequency and permissible output current (current derating).
Information is provided in the SINAMICS Low Voltage Configuration Manual.
2) In transport packaging.
Deviations from the specified classes are underlined.
Line voltage 380 ... 480 V 3 AC |
SINAMICS S150 Converter Cabinet Units |
||||||
---|---|---|---|---|---|---|---|
|
|
6SL3710-7LE32-1AA3 |
6SL3710-7LE32-6AA3 |
6SL3710-7LE33-1AA3 |
6SL3710-7LE33-8AA3 |
6SL3710-7LE35-0AA3 |
6SL3710-7LE36-1AA3 |
Type rating |
|||||||
|
kW |
110 |
132 |
160 |
200 |
250 |
315 |
|
kW |
90 |
110 |
132 |
160 |
200 |
250 |
|
hp |
150 |
200 |
250 |
300 |
400 |
500 |
|
hp |
150 |
200 |
200 |
250 |
350 |
350 |
Output current |
|||||||
|
A |
210 |
260 |
310 |
380 |
490 |
605 |
|
A |
205 |
250 |
302 |
370 |
477 |
590 |
|
A |
178 |
233 |
277 |
340 |
438 |
460 |
|
A |
307 |
375 |
453 |
555 |
715 |
885 |
Infeed/regenerative feedback current |
|||||||
|
A |
197 |
242 |
286 |
349 |
447 |
549 |
|
A |
315 |
390 |
570 |
570 |
735 |
907 |
Current demand, max. 5) |
|||||||
|
A |
Internal |
Internal |
Internal |
Internal |
Internal |
Internal |
Pulse frequency 6) |
|||||||
|
kHz |
2 |
2 |
2 |
2 |
2 |
1.25 |
|
|||||||
|
kHz |
2 |
2 |
2 |
2 |
2 |
1.25 |
|
kHz |
8 |
8 |
8 |
8 |
8 |
7.5 |
Power loss, max. 7) |
|||||||
|
kW |
6.31 |
7.55 |
10.01 |
10.72 |
13.13 |
17.69 |
|
kW |
6.49 |
7.85 |
10.45 |
11.15 |
13.65 |
18.55 |
Cooling air requirement |
m3/s |
0.58 |
0.7 |
1.19 |
1.19 |
1.19 |
1.96 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
71/73 |
71/73 |
72/74 |
72/74 |
72/74 |
77/79 |
Cable length, max. |
|||||||
|
m |
300 |
300 |
300 |
300 |
300 |
300 |
|
m |
450 |
450 |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|||||||
|
mm |
1400 |
1400 |
1600 |
1800 |
1800 |
2200 |
|
mm |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
|
mm |
600 |
600 |
600 |
600 |
600 |
600 |
Weight (without options), approx. |
kg |
708 |
708 |
892 |
980 |
980 |
1716 |
Short-circuit current rating according to IEC 8) |
kA |
65 |
65 |
65 |
65 |
65 |
65 |
Minimum short-circuit current 9) |
A |
3000 |
3000 |
4500 |
4500 |
8000 |
12000 |
Frame sizes |
|
||||||
|
|
FI |
FI |
GI |
GI |
GI |
HI |
|
|
FX |
FX |
GX |
GX |
GX |
HX |
|
|
FX |
FX |
GX |
GX |
GX |
HX |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.
3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.
7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.
8) In conjunction with the specified fuses or circuit breakers.
9) Current required for reliably triggering protective devices.
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
Line voltage 380 ... 480 V 3 AC |
SINAMICS S150 Converter Cabinet Units |
|||||
---|---|---|---|---|---|---|
|
|
6SL3710-7LE37-5AA3 |
6SL3710-7LE38-4AA3 |
6SL3710-7LE41-0AA3 |
6SL3710-7LE41-2AA3 |
6SL3710-7LE41-4AA3 |
Type rating |
||||||
|
kW |
400 |
450 |
560 |
710 |
800 |
|
kW |
315 |
400 |
450 |
560 |
710 |
|
hp |
600 |
700 |
800 |
900 |
1150 |
|
hp |
450 |
600 |
700 |
900 |
1000 |
Output current |
||||||
|
A |
745 |
840 |
985 |
1260 |
1405 |
|
A |
725 |
820 |
960 |
1230 |
1370 |
|
A |
570 |
700 |
860 |
1127 |
1257 |
|
A |
1087 |
1230 |
1440 |
1845 |
2055 |
Infeed/regenerative feedback current |
||||||
|
A |
674 |
759 |
888 |
1133 |
1262 |
|
A |
1118 |
1260 |
1477 |
1891 |
2107 |
Current demand, max. 5) |
||||||
|
A |
Internal |
Internal |
Internal |
Internal |
Internal |
Pulse frequency 6) |
||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
kHz |
7.5 |
7.5 |
7.5 |
7.5 |
7.5 |
Power loss, max. 7) |
||||||
|
kW |
20.63 |
21.1 |
27.25 |
33.05 |
33.95 |
|
kW |
21.75 |
22.25 |
28.65 |
34.85 |
35.85 |
Cooling air requirement |
m3/s |
1.96 |
1.96 |
2.6 |
2.6 |
2.6 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
77/79 |
77/79 |
77/79 |
78/80 |
78/80 |
Cable length, max. |
||||||
|
m |
300 |
300 |
300 |
300 |
300 |
|
m |
450 |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
||||||
|
mm |
2200 |
2200 |
2800 |
2800 |
2800 |
|
mm |
2000 |
2000 |
2000 |
2000 |
2000 |
|
mm |
600 |
600 |
600 |
600 |
600 |
Weight (without options), approx. |
kg |
1731 |
1778 |
2408 |
2408 |
2408 |
Short-circuit current rating according to IEC 8) |
kA |
65 |
65 |
84 |
100 |
100 |
Minimum short-circuit current 9) |
A |
15000 |
2000 |
2500 |
3200 |
3200 |
Frame sizes |
|
|||||
|
|
HI |
HI |
JI |
JI |
JI |
|
|
HX |
HX |
JX |
JX |
JX |
|
|
HX |
HX |
JX |
JX |
JX |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.
3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.
7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.
8) In conjunction with the specified fuses or circuit breakers.
9) Current required for reliably triggering protective devices.
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
Line voltage 500 ... 690 V 3 AC |
SINAMICS S150 Converter Cabinet Units |
||||||
---|---|---|---|---|---|---|---|
|
|
6SL3710-7LG28-5AA3 |
6SL3710-7LG31-0AA3 |
6SL3710-7LG31-2AA3 |
6SL3710-7LG31-5AA3 |
6SL3710-7LG31-8AA3 |
6SL3710-7LG32-2AA3 |
Type rating |
|||||||
|
kW |
75 |
90 |
110 |
132 |
160 |
200 |
|
kW |
55 |
75 |
90 |
110 |
132 |
160 |
|
kW |
55 |
55 |
75 |
90 |
110 |
132 |
|
kW |
45 |
55 |
75 |
90 |
90 |
110 |
|
hp |
75 |
75 |
100 |
150 |
150 |
200 |
|
hp |
75 |
75 |
100 |
125 |
150 |
200 |
Output current |
|||||||
|
A |
85 |
100 |
120 |
150 |
175 |
215 |
|
A |
80 |
95 |
115 |
142 |
170 |
208 |
|
A |
76 |
89 |
117 |
134 |
157 |
192 |
|
A |
120 |
142 |
172 |
213 |
255 |
312 |
Infeed/regenerative feedback current |
|||||||
|
A |
86 |
99 |
117 |
144 |
166 |
202 |
|
A |
125 |
144 |
170 |
210 |
253 |
308 |
Current demand, max. 5) |
|||||||
|
A |
Internal |
Internal |
Internal |
Internal |
Internal |
Internal |
Pulse frequency 6) |
|||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
|||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
kHz |
7.5 |
7.5 |
7.5 |
7.5 |
7.5 |
7.5 |
Power loss, max. 7) |
|||||||
|
kW |
5.12 |
5.38 |
5.84 |
5.75 |
11.02 |
11.44 |
|
kW |
4.45 |
4.65 |
5.12 |
4.97 |
11.15 |
11.56 |
Cooling air requirement |
m3/s |
0.58 |
0.58 |
0.58 |
0.58 |
1.19 |
1.19 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
71/73 |
71/73 |
71/73 |
71/73 |
75/77 |
75/77 |
Cable length, max. |
|||||||
|
m |
300 |
300 |
300 |
300 |
300 |
300 |
|
m |
450 |
450 |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|||||||
|
mm |
1400 |
1400 |
1400 |
1400 |
1600 |
1600 |
|
mm |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
|
mm |
600 |
600 |
600 |
600 |
600 |
600 |
Weight (without options), approx. |
kg |
708 |
708 |
708 |
708 |
892 |
892 |
Short-circuit current rating according to IEC 8) |
kA |
65 |
65 |
65 |
65 |
65 |
65 |
Minimum short-circuit current 9) |
A |
1000 |
1000 |
1300 |
1800 |
2500 |
3000 |
Frame size |
|
||||||
|
|
FI |
FI |
FI |
FI |
GI |
GI |
|
|
FX |
FX |
FX |
FX |
GX |
GX |
|
|
FX |
FX |
FX |
FX |
GX |
GX |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.
3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.
7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.
8) In conjunction with the specified fuses or circuit breakers.
9) Current required for reliably triggering protective devices.
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
Line voltage 500 … 690 V 3 AC |
SINAMICS S150 Converter Cabinet Units |
||||||
---|---|---|---|---|---|---|---|
|
|
6SL3710-7LG32-6AA3 |
6SL3710-7LG33-3AA3 |
6SL3710-7LG34-1AA3 |
6SL3710-7LG34-7AA3 |
6SL3710-7LG35-8AA3 |
6SL3710-7LG37-4AA3 |
Type rating |
|||||||
|
kW |
250 |
315 |
400 |
450 |
560 |
710 |
|
kW |
200 |
250 |
315 |
400 |
450 |
630 |
|
kW |
160 |
200 |
250 |
315 |
400 |
500 |
|
kW |
132 |
160 |
200 |
250 |
315 |
450 |
|
hp |
250 |
300 |
400 |
450 |
600 |
700 |
|
hp |
200 |
250 |
350 |
450 |
500 |
700 |
Output current |
|||||||
|
A |
260 |
330 |
410 |
465 |
575 |
735 |
|
A |
250 |
320 |
400 |
452 |
560 |
710 |
|
A |
233 |
280 |
367 |
416 |
514 |
657 |
|
A |
375 |
480 |
600 |
678 |
840 |
1065 |
Infeed/regenerative feedback current |
|||||||
|
A |
242 |
304 |
375 |
424 |
522 |
665 |
|
A |
370 |
465 |
619 |
700 |
862 |
1102 |
Current demand, max. 5) |
|||||||
|
A |
Internal |
Internal |
Internal |
Internal |
Internal |
Internal |
Pulse frequency 6) |
|||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
|||||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
1.25 |
|
kHz |
7.5 |
7.5 |
7.5 |
7.5 |
7.5 |
7.5 |
Power loss, max. 7) |
|||||||
|
kW |
11.97 |
12.69 |
19.98 |
20.55 |
24.05 |
30.25 |
|
kW |
12.03 |
12.63 |
18.86 |
19.47 |
22.85 |
28.75 |
Cooling air requirement |
m3/s |
1.19 |
1.19 |
1.96 |
1.96 |
1.96 |
2.6 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
75/77 |
75/77 |
77/79 |
77/79 |
77/79 |
77/79 |
Cable length, max. |
|||||||
|
m |
300 |
300 |
300 |
300 |
300 |
300 |
|
m |
450 |
450 |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|||||||
|
mm |
1600 |
1600 |
2200 |
2200 |
2200 |
2800 |
|
mm |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
|
mm |
600 |
600 |
600 |
600 |
600 |
600 |
Weight (without options), approx. |
kg |
892 |
892 |
1716 |
1716 |
1716 |
2300 |
Short-circuit current rating according to IEC 8) |
kA |
65 |
65 |
65 |
65 |
84 |
85 |
Minimum short-circuit current 9) |
A |
3000 |
4500 |
4500 |
7000 |
9000 |
15000 |
Frame size |
|
||||||
|
|
GI |
GI |
HI |
HI |
HI |
JI |
|
|
GX |
GX |
HX |
HX |
HX |
JX |
|
|
GX |
GX |
HX |
HX |
HX |
JX |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.
3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.
7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.
8) In conjunction with the specified fuses or circuit breakers.
9) Current required for reliably triggering protective devices.
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
Line voltage 500 … 690 V 3 AC |
SINAMICS S150 Converter Cabinet Units |
||||
---|---|---|---|---|---|
|
|
6SL3710-7LG38-1AA3 |
6SL3710-7LG38-8AA3 |
6SL3710-7LG41-0AA3 |
6SL3710-7LG41-3AA3 |
Type rating |
|||||
|
kW |
800 |
900 |
1000 |
1200 |
|
kW |
710 |
800 |
900 |
1000 |
|
kW |
560 |
630 |
710 |
900 |
|
kW |
500 |
560 |
630 |
800 |
|
hp |
800 |
900 |
1000 |
1250 |
|
hp |
700 |
800 |
900 |
1000 |
Output current |
|||||
|
A |
810 |
910 |
1025 |
1270 |
|
A |
790 |
880 |
1000 |
1230 |
|
A |
724 |
814 |
917 |
1136 |
|
A |
1185 |
1320 |
1500 |
1845 |
Infeed/regenerative feedback current |
|||||
|
A |
732 |
821 |
923 |
1142 |
|
A |
1218 |
1367 |
1537 |
1905 |
Current demand, max. 5) |
|||||
|
A |
Internal |
Internal |
Internal |
Internal |
Pulse frequency 6) |
|||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
|
|||||
|
kHz |
1.25 |
1.25 |
1.25 |
1.25 |
|
kHz |
7.5 |
7.5 |
7.5 |
7.5 |
Power loss, max. 7) |
|||||
|
kW |
34.45 |
34.65 |
36.15 |
42.25 |
|
kW |
32.75 |
32.85 |
34.25 |
39.25 |
Cooling air requirement |
m3/s |
2.6 |
2.6 |
2.6 |
2.6 |
Sound pressure level LpA (1 m) at 50/60 Hz |
dB |
77/79 |
77/79 |
77/79 |
77/79 |
Cable length, max. |
|||||
|
m |
300 |
300 |
300 |
300 |
|
m |
450 |
450 |
450 |
450 |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|||||
|
mm |
2800 |
2800 |
2800 |
2800 |
|
mm |
2000 |
2000 |
2000 |
2000 |
|
mm |
600 |
600 |
600 |
600 |
Weight (without options), approx. |
kg |
2408 |
2408 |
2408 |
2408 |
Short-circuit current rating according to IEC 8) |
kA |
85 |
85 |
85 |
85 |
Minimum short-circuit current 9) |
A |
2000 |
2000 |
2500 |
3200 |
Frame size |
|
||||
|
|
JI |
JI |
JI |
JI |
|
|
JX |
JX |
JX |
JX |
|
|
JX |
JX |
JX |
JX |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.
3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.
7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.
8) In conjunction with the specified fuses or circuit breakers.
9) Current required for reliably triggering protective devices.
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
When ordering a converter with options, add the suffix "-Z" to the article number and then the order code(s) for the desired option(s).
Example:
6SL3710-7LE32-1AA3-Z
M07+D60+...
See also ordering examples.
Available options |
Order code |
---|---|
Input side |
|
Use in the first environment according to EN 618003, Category C2 (TN-TT line supplies with grounded neutral point) |
L00 |
Infeed module one level lower |
L04 |
Surge suppression |
L21 |
Main switch incl. fuses or circuit breakers |
L26 |
Line filter monitoring |
L40 |
EMC shielding busbar (cable connection from below) 1) |
M70 |
Output side |
|
dv/dt filter plus Voltage Peak Limiter |
L07 |
Motor reactor |
L08 |
dv/dt filter plus Voltage Peak Limiter |
L10 |
Sine-wave filter (only for the voltage range 380 to 480 V, up to 200 kW) |
L15 |
EMC shielding busbar (cable connection from below) 1) |
M70 |
Motor protection and safety functions |
|
EMERGENCY OFF pushbutton installed in the cabinet door |
L45 |
EMERGENCY OFF category 0, 230 V AC or 24 V DC |
L57 |
EMERGENCY STOP category 1, 230 V AC |
L59 |
EMERGENCY STOP category 1, 24 V DC |
L60 |
Thermistor motor protection (alarm) |
L83 |
Thermistor motor protection (trip) |
L84 |
Pt100 evaluation unit |
L86 |
Insulation monitoring |
L87 |
Additional touch protection |
M60 |
Degree of protection increase |
|
Degree of protection IP21 |
M21 |
Degree of protection IP23 |
M23 |
Degree of protection IP43 |
M43 |
Degree of protection IP54 |
M54 |
Mechanical options |
|
Base 100 mm high, RAL 7022 |
M06 |
Cable-marshaling compartment 200 mm high, RAL 7035 |
M07 |
Line connection from above |
M13 |
Motor connection from above |
M78 |
Crane transport assembly (top-mounted) |
M90 |
Safety Integrated |
|
Safety license for 1 axis |
K01 |
Second SMC30 Sensor Module Cabinet-Mounted |
K52 |
Terminal module for controlling the Safe Torque Off and Safe Stop 1 safety functions |
K82 |
TM54F Terminal Module |
K87 |
Safe Brake Adapter SBA, 230 V AC |
K88 |
Other options |
|
CBC10 Communication Board |
G20 |
CBE20 Communication Board |
G33 |
TM150 temperature sensor evaluation unit |
G51 |
TM31 Terminal Module |
G60 |
Additional TM31 Terminal Module |
G61 |
TB30 Terminal Board |
G62 |
SMC10 Sensor Module Cabinet-Mounted |
K46 |
SMC20 Sensor Module Cabinet-Mounted |
K48 |
SMC30 Sensor Module Cabinet-Mounted |
K50 |
VSM10 Voltage Sensing Module |
K51 |
CU320‑2 PN Control Unit |
K95 |
Connection for external auxiliary equipment |
L19 |
Cabinet lighting with service socket |
L50 |
Cabinet anti-condensation heating |
L55 |
25/125 kW braking unit |
L61 |
50/250 kW braking unit |
L62 |
25/125 kW braking unit |
L64 |
50/250 kW braking unit |
L65 |
Marking of all control cable wire ends |
M91 |
Special cabinet paint finish 2) |
Y09 |
One-line label for system identification, 40 × 80 mm |
Y31 |
Two-line label for system identification, 40 × 180 mm |
Y32 |
Four-line label for system identification, 40 × 180 mm |
Y33 |
Documentation (standard: English/German) |
|
Documentation, production flowchart: one issue |
B43 |
Documentation, production flowchart: updated every two weeks |
B44 |
Documentation, production flowchart: updated every month |
B45 |
Documentation in German |
D00 |
Customer documentation (circuit diagram, terminal diagram, layout diagram) in DXF format |
D02 |
Customer documentation as hard copy |
D04 |
Preliminary version of customer documentation |
D14 |
Documentation in Russian |
D56 |
Documentation in English / French |
D58 |
Documentation in English / Spanish |
D60 |
Documentation in Italian |
D72 |
Documentation in English |
D76 |
Documentation in French |
D77 |
Documentation in Spanish |
D78 |
Documentation in English / Italian |
D80 |
Documentation in Chinese |
D84 |
Documentation in English / Chinese |
D91 |
Documentation in English / Portuguese (Brazil) |
D93 |
Documentation in English / Russian |
D94 |
Rating plate data (standard: English/German) |
|
Rating plate data in English/French |
T58 |
Rating plate data in English/Spanish |
T60 |
Rating plate data in English/Italian |
T80 |
Rating plate data in English/Portuguese (Brazil) |
T83 |
Rating plate data in English/Russian |
T85 |
Rating plate data in English/Chinese |
T91 |
Options specific to the chemical industry |
|
NAMUR terminal block |
B00 |
Protective separation for 24 V supply (PELV) |
B02 |
Outlet for external auxiliary equipment (uncontrolled) |
B03 |
Options specific to the shipbuilding industry |
|
Marine version |
M66 |
Individual certificate from Germanische Lloyd (GL) |
E11 |
Individual certificate from Lloyds Register (LR) |
E21 |
Individual certificate from Bureau Veritas (BV) |
E31 |
Individual certificate from Det Norske Veritas (DNV) |
E51 |
Individual certificate from American Bureau of Shipping (ABS) |
E61 |
Individual certificate from Chinese Certification Society (CCS) |
E71 |
Converter acceptance in presence of customer |
|
Visual acceptance |
F03 |
Function test without motor |
F71 |
Function test with test bay motor under no-load conditions |
F75 |
Insulation test |
F77 |
Customer-specific acceptance inspections (on request) |
F97 |
Converter acceptance without the customer present |
|
Function test without motor |
F72 |
Function test with test bay motor under no-load conditions |
F74 |
Insulation test |
F76 |
1) This option is listed for the input- and output-side options, but is only required once.
2) The order code Y.. requires data in plain text.
Certain options can mutually exclude one another
(options that are not involved, are also not shown).
✓ |
Possible combination |
---|---|
– |
Combination not possible |
|
L07 |
L08 |
L10 |
L15 |
L57 |
L59 |
L60 |
L61/L64 |
L62/L65 |
L87 |
K82 |
M78 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
L07 |
|
– |
– |
– |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
L08 |
– |
|
– |
– |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
L10 |
– |
– |
|
– |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
L15 |
– |
– |
– |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
L57 |
✓ |
✓ |
✓ |
✓ |
|
– |
– |
✓ |
✓ |
✓ |
✓ |
✓ |
L59 |
✓ |
✓ |
✓ |
✓ |
– |
|
– |
✓ |
✓ |
✓ |
✓ |
✓ |
L60 |
✓ |
✓ |
✓ |
✓ |
– |
– |
|
✓ |
✓ |
✓ |
✓ |
✓ |
L61/L64 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
– |
✓ |
✓ |
✓ |
L62/L65 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
|
✓ |
✓ |
✓ |
L87 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
– 1) |
✓ |
K82 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– 1) |
|
✓ |
M78 |
– |
– |
– |
– |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
1) A combination of L87 and K82 is available on request.
|
M06 |
M07 |
M13 |
M21 |
M23 |
M43 |
M54 |
M60 |
M66 |
M70 |
M78 |
---|---|---|---|---|---|---|---|---|---|---|---|
M06 |
|
– |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
M07 |
– |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
M13 |
✓ |
✓ |
|
– |
✓ |
✓ |
✓ |
✓ |
✓ |
– 2) |
✓ |
M21 |
✓ |
✓ |
– |
|
– |
– |
– |
– 3) |
– |
✓ |
– |
M23 |
✓ |
✓ |
✓ |
– |
|
– |
– |
– |
– |
✓ |
✓ |
M43 |
✓ |
✓ |
✓ |
– |
– |
|
– |
– |
– |
✓ |
✓ |
M54 |
✓ |
✓ |
✓ |
– |
– |
– |
|
– |
✓ |
✓ |
✓ |
M60 |
✓ |
✓ |
– |
– 3) |
– |
– |
– |
|
✓ |
✓ |
– |
M66 |
✓ |
✓ |
✓ |
– |
– |
– |
✓ |
✓ |
|
✓ |
– |
M70 |
✓ |
✓ |
– 2) |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
– 2) |
M78 |
✓ |
✓ |
✓ |
– |
✓ |
✓ |
✓ |
– |
– |
– 2) |
|
2) If the line connection (option M13) and the motor connection (option M78) are from above, the EMC shield bus is not required in the lower cabinet area.
3) Can only be selected for converters in the voltage range 400 V to 250 kW and 690 V to 315 kW. The M60 option is fitted as standard for higher outputs.
|
G20 |
G33 |
G62 |
K46 |
K48 |
K50 |
K51 |
K52 |
---|---|---|---|---|---|---|---|---|
G20 |
|
– |
– |
✓ |
✓ |
✓ |
✓ |
✓ |
G33 |
– |
|
– |
✓ |
✓ |
✓ |
✓ |
✓ |
G62 |
– |
– |
|
✓ |
✓ |
✓ |
✓ |
✓ |
K46 |
✓ |
✓ |
✓ |
|
– |
– |
– |
– |
K48 |
✓ |
✓ |
✓ |
– |
|
– |
– |
– |
K50 |
✓ |
✓ |
✓ |
– |
– |
|
– |
✓ |
K51 |
✓ |
✓ |
✓ |
– |
– |
– |
|
– |
K52 |
✓ |
✓ |
✓ |
– |
– |
✓ |
– |
|
|
D00 |
D02 |
D14 |
D56 |
D58 |
D60 |
D72 |
D76 |
D77 |
D78 |
D80 |
D84 |
D91 |
D93 |
D94 |
D99 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
D00 |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
D02 |
✓ |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
D14 |
✓ |
✓ |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
D56 |
✓ |
✓ |
✓ |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
– |
D58 |
✓ |
✓ |
✓ |
✓ |
|
– |
✓ |
– |
– |
✓ |
– |
✓ |
– |
– |
– |
– |
D60 |
✓ |
✓ |
✓ |
✓ |
– |
|
✓ |
– |
✓ |
– |
– |
✓ |
– |
– |
– |
– |
D72 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
✓ |
✓ |
✓ |
– |
✓ |
✓ |
✓ |
✓ |
– |
D76 |
✓ |
✓ |
✓ |
✓ |
– |
– |
✓ |
|
✓ |
✓ |
– |
✓ |
– |
– |
– |
– |
D77 |
✓ |
✓ |
✓ |
✓ |
– |
✓ |
✓ |
✓ |
|
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
D78 |
✓ |
✓ |
✓ |
✓ |
✓ |
– |
✓ |
✓ |
✓ |
|
✓ |
✓ |
✓ |
✓ |
✓ |
– |
D80 |
✓ |
✓ |
✓ |
✓ |
– |
– |
– |
– |
✓ |
✓ |
|
✓ |
– |
– |
– |
– |
D84 |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
|
– |
✓ |
✓ |
– |
D91 |
✓ |
✓ |
✓ |
✓ |
– |
– |
✓ |
– |
✓ |
✓ |
– |
– |
|
– |
– |
– |
D93 |
✓ |
✓ |
✓ |
✓ |
– |
– |
✓ |
– |
✓ |
✓ |
– |
✓ |
– |
|
– |
– |
D94 |
✓ |
✓ |
✓ |
– |
– |
– |
✓ |
– |
✓ |
✓ |
– |
✓ |
– |
– |
|
– |
D99 |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
– |
|
|
T58 |
T60 |
T80 |
T83 |
T85 |
T91 |
---|---|---|---|---|---|---|
T58 |
|
– |
– |
– |
– |
– |
T60 |
– |
|
– |
– |
– |
– |
T80 |
– |
– |
|
– |
– |
– |
T83 |
– |
– |
– |
|
– |
– |
T85 |
– |
– |
– |
– |
|
– |
T91 |
– |
– |
– |
– |
– |
|
Example 1
Task:
A drive system is required for a vehicle test stand to perform exhaust gas analysis which can simulate driving profiles and cycles as encountered in everyday traffic situations. This means for the drive system that the dynamometer must be operated both in the motoring as well as regenerating modes.
A drive with regenerative feedback into the line supply is required as regenerative operation is the predominant operating mode and dynamic switching operations are required.
The max. regenerative power is 200 kW. The drive converter must have degree of protection IP54 as a result of the environmental conditions. An installation altitude of < 1000 m and 45 °C as the maximum ambient temperature can be assumed. The windings must be equipped with Pt100 resistance thermometers and monitored by the drive converter for alarm and trip. A switch disconnector must be provided to disconnect the converter from the 400 V power supply. In addition, the cabinet is to have a special paint finish in RAL 3002.
Solution:
Taking into account the derating factors for degree of protection IP54 and the increased ambient temperature of 45 °C, a converter with a minimum power rating of 223 kW should be configured.
A converter with a power rating of at least 250 kW and options M54 (degree of protection IP54), L26 (main switch including fuses), L86 (Pt100 evaluation unit) and Y09 (special paint finish) is selected.
The ordering data are as follows:
6SL3710-7LE35-0AA3-Z
M54+L26+L86+Y09
Cabinet color RAL 3002
Example 2
Task:
A drive system is required for a conveyor belt in a brown-coal open-cast mine that is capable of both motor and generator operation. Since the conveyor belt must be capable of starting after a fault when loaded with bulk material, and it is possible for peak loads to occur where 1.5 times the power is required for up to 60 s, the drive system must be designed according to the overload requirements of such a case. The drive converter is installed in a climate-controlled container as a result of the environmental conditions typical of an open-cast mine. The installation altitude is 320 m above sea level and the maximum ambient temperature in the container is 35 °C. The drive is powered through a converter transformer from the medium-voltage system. The drive is connected to an isolated-neutral system and must have insulation monitoring. A motor with separately-driven fan is selected here as the motor is subject to a high load torque when starting and in the lower range. The fan supply voltage is 690 V and must be drawn from the drive converter.
The required motor power is 420 kW.
Solution:
Since the converter is installed in an air-conditioned container, it can be designed with degree of protection IP20. The ambient temperature of 35 °C does not necessitate any additional derating. However, due to the specified overload conditions, the base load current IH (for high overload) must be applied. This results in a power of approx. 520 kW for the drive converter. The converter with article no. 6SL3710-7LG35-8AA3 must be selected.
Option L87 (insulation monitoring) must be selected for insulation monitoring.
Option L19 (connection for external auxiliaries) must be selected for the controlled outgoing feeder to power the separately driven fan.
The ordering data are as follows:
6SL3710-7LG35-8AA3-Z
L19+L87
SINAMICS S150 converter cabinet units and the associated system components are rated for an ambient temperature of 40 °C and installation altitudes up to 2000 m above sea level.
At ambient temperatures > 40 °C, the output current must be reduced. Ambient temperatures above 50 °C are not permissible.
At installation altitudes > 2000 m above sea level, it must be taken into account that the air pressure, and therefore air density, decreases as the height increases. As a consequence, the cooling efficiency and the insulation capacity of the air also decrease.
Due to the reduced cooling efficiency, it is necessary, on the one hand, to reduce the ambient temperature and on the other hand, to lower heat loss in the converter cabinet unit by reducing the output current, whereby ambient temperatures lower than 40 °C may be offset to compensate.
The following table lists the permissible output currents depending on the installation altitude and ambient temperature for the various degrees of protection. The specified values already include a permitted compensation in respect of installation altitude and ambient temperatures < 40 °C (temperature at the air intake of the converter cabinet unit).
The values apply under the precondition that the cooling air flow stated in the technical specifications is ensured by the way the devices are installed in the cabinet.
As additional measure for installation altitudes from 2000 m up to 5000 m, an isolating transformer is required in order to reduce transient overvoltages according to EN 60664‑1. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Current-derating factors for converter cabinet units depending on the ambient / air intake temperature, the installation altitude and the degree of protection
Degree of protection |
Installation altitude above sea level |
Current derating factor (as a percentage of the rated current) |
||||||
---|---|---|---|---|---|---|---|---|
|
m |
20 °C |
25 °C |
30 °C |
35 °C |
40 °C |
45 °C |
50 °C |
IP20, IP21, IP23, IP43 |
0 ... 2000 |
100 % |
100 % |
100 % |
100 % |
100 % |
93.3 % |
86.7 % |
2001 ... 2500 |
100 % |
100 % |
100 % |
100 % |
96.3 % |
|
|
|
2501 ... 3000 |
100 % |
100 % |
100 % |
98.7 % |
|
|
|
|
3001 ... 3500 |
100 % |
100 % |
100 % |
|
|
|
|
|
3501 ... 4000 |
100 % |
100 % |
96.3 % |
|
|
|
|
|
4001 ... 4500 |
100 % |
97.5 % |
|
|
|
|
|
|
4501 ... 5000 |
98.2 % |
|
|
|
|
|
|
|
IP54 |
0 ... 2000 |
100 % |
100 % |
100 % |
100 % |
93.3 % |
86.7 % |
80.0 % |
2001 ... 2500 |
100 % |
100 % |
100 % |
96.3 % |
89.8 % |
|
|
|
2501 ... 3000 |
100 % |
100 % |
98.7 % |
92.5 % |
|
|
|
|
3001 ... 3500 |
100 % |
100 % |
94.7 % |
|
|
|
|
|
3501 ... 4000 |
100 % |
96.3 % |
90.7 % |
|
|
|
|
|
4001 ... 4500 |
97.5 % |
92.1 % |
|
|
|
|
|
|
4501 ... 5000 |
93.0 % |
|
|
|
|
|
|
Current derating depending on the pulse frequency
To reduce motor noise or to increase output frequency, the pulse frequency can be increased relative to the factory setting (1.25 kHz or 2 kHz). When the pulse frequency is increased, the derating factor of the output current must be taken into account. This derating factor must be applied to the currents specified in the technical specifications.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 2 kHz
SINAMICS S150 converter cabinet unit |
Type rating |
Output current |
Derating factor at the pulse frequency |
||||
---|---|---|---|---|---|---|---|
6SL3710-... |
kW |
A |
2.5 kHz |
4 kHz |
5 kHz |
7.5 kHz |
8 kHz |
380 ... 480 V 3 AC |
|||||||
7LE32-1AA3 |
110 |
210 |
95 % |
82 % |
74 % |
54 % |
50 % |
7LE32-6AA3 |
132 |
260 |
95 % |
83 % |
74 % |
54 % |
50 % |
7LE33-1AA3 |
160 |
310 |
97 % |
88 % |
78 % |
54 % |
50 % |
7LE33-8AA3 |
200 |
380 |
96 % |
87 % |
77 % |
54 % |
50 % |
7LE35-0AA3 |
250 |
490 |
94 % |
78 % |
71 % |
53 % |
50 % |
Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 1.25 kHz
SINAMICS S150 converter cabinet unit |
Type rating |
Output current |
Derating factor at the pulse frequency |
||||
---|---|---|---|---|---|---|---|
6SL3710-... |
kW |
A |
2 kHz |
2.5 kHz |
4 kHz |
5 kHz |
7.5 kHz |
380 ... 480 V 3 AC |
|||||||
7LE36-1AA3 |
315 |
605 |
83 % |
72 % |
64 % |
60 % |
40 % |
7LE37-5AA3 |
400 |
745 |
83 % |
72 % |
64 % |
60 % |
40 % |
7LE38-4AA3 |
450 |
840 |
87 % |
79 % |
64 % |
55 % |
40 % |
7LE41-0AA3 |
560 |
985 |
92 % |
87 % |
70 % |
60 % |
50 % |
7LE41-2AA3 |
710 |
1260 |
92 % |
87 % |
70 % |
60 % |
50 % |
7LE41-4AA3 |
800 |
1405 |
97 % |
95 % |
74 % |
60 % |
50 % |
500 ... 690 V 3 AC |
|||||||
7LG28-5AA3 |
75 |
85 |
93 % |
89 % |
71 % |
60 % |
40 % |
7LG31-0AA3 |
90 |
100 |
92 % |
88 % |
71 % |
60 % |
40 % |
7LG31-2AA3 |
110 |
120 |
92 % |
88 % |
71 % |
60 % |
40 % |
7LG31-5AA3 |
132 |
150 |
90 % |
84 % |
66 % |
55 % |
35 % |
7LG31-8AA3 |
160 |
175 |
92 % |
87 % |
70 % |
60 % |
40 % |
7LG32-2AA3 |
200 |
215 |
92 % |
87 % |
70 % |
60 % |
40 % |
7LG32-6AA3 |
250 |
260 |
92 % |
88 % |
71 % |
60 % |
40 % |
7LG33-3AA3 |
315 |
330 |
89 % |
82 % |
65 % |
55 % |
40 % |
7LG34-1AA3 |
400 |
410 |
89 % |
82 % |
65 % |
55 % |
35 % |
7LG34-7AA3 |
450 |
465 |
92 % |
87 % |
67 % |
55 % |
35 % |
7LG35-8AA3 |
560 |
575 |
91 % |
85 % |
64 % |
50 % |
35 % |
7LG37-4AA3 |
710 |
735 |
87 % |
79 % |
64 % |
55 % |
35 % |
7LG38-1AA3 |
800 |
810 |
97 % |
95 % |
71 % |
55 % |
35 % |
7LG38-8AA3 |
900 |
910 |
92 % |
87 % |
67 % |
55 % |
33 % |
7LG41-0AA3 |
1000 |
1025 |
91 % |
86 % |
64 % |
50 % |
30 % |
7LG41-3AA3 |
1200 |
1270 |
87 % |
79 % |
55 % |
40 % |
25 % |
The following table lists the maximum achievable output frequency as a function of the pulse frequency:
Pulse frequency |
Max. achievable output frequency |
---|---|
1.25 kHz |
100 Hz |
2 kHz |
160 Hz |
2.5 kHz |
200 Hz |
≥4 kHz |
300 Hz |
The SINAMICS S150 converter cabinet units are equipped with an overload reserve to deal with breakaway torques, for example. If larger surge loads occur, this must be taken into account in the configuration. For drives with overload requirements, the appropriate base load current must, therefore, be used as a basis for the required load.
The criterion for overload is that the drive is operated with its base load current before and after the overload occurs on the basis of a duty cycle duration of 300 s.
For temporary, periodic duty cycles with high variations of load within the duty cycle, the relevant sections of the SINAMICS Low Voltage Engineering Manual must be observed.
The base-load current for a low overload IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s.
Low overload
The base-load current IH for a high overload is based on a load cycle of 150 % for 60 s or 160 % for 10 s.
High overload