Transducer nhiệt Phoenix Contact MINI MCR-SL-PT100-UI - 2864435

Transducer nhiệt Phoenix Contact MINI MCR-SL-PT100-UI - 2864435

526
Nhà sản xuất: Phoenix Contact;    Xuất xứ: Germany
Giá sỉ:Giá tốt nhất xem...0909186879 dienelectrics@gmail.com
Khuyến mãi:Có Discount
Bảo hành:12 Tháng (Chính hãng)
Thanh toán:C.O.D / Bảo lãnh TT / Link hoạt
Vận chuyển:Miễn phí Tp.HCM, vùng lân cận
Thông tin nổi bật

Transducer nhiệt Phoenix Contact MINI MCR-SL-PT100-UI - 2864435

(
No longer in product range, View replacement product:

MINI MCR-2-RTD-UI-C - 2902048

Resistance thermometer measuring transducer
Configurable temperature transducer with plug-in connection technology for connecting 2, 3, and 4-conductor resistance thermometers and resistance-type sensors. Configurable via DIP switch or software. Screw connection technology, order configuration
)
 

Product Description

The narrow, 6.2 mm wide MINI MCR-SL-PT100-UI... is a configurable, 3-way isolated temperature transducer. It is suitable for connecting Pt 100 resistance thermometers in accordance with IEC 60751 in 2-, 3-, and 4-conductor connection technology.

Electrically isolated 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V, 0 ... 5 V, 1 ... 5 V, 10 ... 0 V, 20 ... 0 mA, or 20 ... 4 mA standard analog signals are available on the output side.

The DIP switches, which can be accessed on the side of the housing, are used to configure the following parameters:
- Connection technology
- Temperature range to be measured
- Output signal
- Type of error evaluation

Power (19.2 V DC to 30 V DC) can either be supplied via the connection terminal blocks of the modules or in conjunction with the DIN rail connector.

 

Technical Data

Product properties

Product type Temperature transmitter
Product family MINI Analog
No. of channels 1
Insulation characteristics
Overvoltage category II
Pollution degree 2
 

Electrical properties

No. of channels 1
Rated insulation voltage 50 V AC/DC
Electrical isolation Basic insulation in accordance with EN 61010
Maximum power dissipation for nominal condition 235.5 mW
Test voltage, input/output/supply 1.5 kV AC (50 Hz, 60 s)
Protective circuit Transient protection
Step response (0–99%) < 160 ms
Maximum temperature coefficient < 0.02 %/K
Transmission error in the set measuring range ((100 K / set measurement range [K]) + 0.1)%
Transmission error in the full measuring range ≤ 0,2 %
Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption < 21 mA (at 24 V DC)
Power consumption < 500 mW
 

Input data

Signal: I analog
Number of inputs 1
Input signal Temperature
Measurement
Configurable/programmable Yes
Sensor types (RTD) that can be used Pt 100 (IEC 60751/EN 60751)
Temperature measuring range min. 50 K
Sensor type: -150 °C ... 850 °C (configurable)
Sensor input current 1 mA (constant)
Max. permissible overall conductor resistance 10 Ω (Per cable)
Connection technology 2-, 3-, 4-conductor
 

Output data

Signal
Number of outputs 1
Configurable/programmable Yes, preconfigured
Voltage output signal 0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Max. voltage output signal approx. 12.5 V
Non-load voltage approx. 12.5 V
Current output signal 4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
0 mA ... 20 mA (please indicate if different setting when ordering)
Max. current output signal 23 mA
Short-circuit current approx. 10 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP (at 10 kΩ)
< 20 mVPP (at 500 Ω)
 

Connection data

Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12
 

Dimensions

Dimensional drawing
Width 6.2 mm
Height 93.1 mm
Depth 102.5 mm
 

Material specifications

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT
 

Environmental and real-life conditions

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
 

Approvals

CE
Certificate CE-compliant
ATEX
Identification  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
Identification UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
Identification GL EMC 2 D
 

EMC data

Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 10 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 10 %
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 10 %
 

Standards and regulations

Electrical isolation Basic insulation in accordance with EN 61010
 

Mounting

Mounting type DIN rail mounting
Assembly instructions The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position any
 

Commercial Data

Item number 2864435
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key CK1221
Product Key CK1221
Catalog Page Page 105 (C-7-2015)
GTIN 4017918974855
Weight per Piece (including packing) 99.5 g
Weight per Piece (excluding packing) 99.5 g
Customs tariff number 85437090
Country of origin DE
 

Classifications

ECLASS

ECLASS-11.0 27210129
 

ETIM

ETIM 7.0 EC002919
 

Environmental Product Compliance

 
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”
 

Compatible Products

ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail bus connectors
MINI MCR-SL-PTB - 2864134
Power terminal block
MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Power supply unit
View replacement product 2904614
MINI MCR DKL - 2308111
Transparent cover
MINI MCR-DKL-LABEL - 2810272
Marking label


- Tài liệu kỹ thuật Phoenix Contact MINI MCR-SL-PT100-UI - 2864435 ở đây.


Tham khảo thêm các model khác cùng loại:
 
SẢN PHẨM XEM NHIỀU
Hãy xem RCCB và ELCB cứu bạn thoát chết vì điện giựt thế nào!Hãy xem tầm qua trong của RCCB và ELCB trong việc cứu nạn nhân bị điện giựt thoát chết như thế nào..
Wiki - Tìm hiểu về lắp đặt hệ thống điện trong nhà máy, tòa nhà...Lắp điện là lắp đặt, đấu nối hệ thống dây, cáp điện động lực, điều khiển, truyền thông và chác thiết bị liên quan như thiết bị chuyển mạch (CB), tủ điện
Circuit Breakers (CB) hoạt động thế nào?
Bộ ngắt điện hay còn gọi là máy cắt (Circuit breaker-CB) là thiết bị được thiết kế để bảo vệ một mạch điện khỏi bị hư hỏng gây ra bởi dòng điện
Programmable logic controller
A programmable logic controller (PLC), or programmable controller is an industrial digital computer which has been ruggedisedand adapted for the control of
White paper về Lý thuyết điều khiển tự độngLý thuyết điều khiển tự động là một nhánh liên ngành của kỹ thuật và toán học, liên quan đến hành vi của
Hướng dẫn Lập trình PLC chi tiết cho người mới tìm hiểu (Part 1)Điều khiển quá trình (PLC) được sử dụng rộng rãi trong công nghiệp và cho phép sản xuất hàng loạt các sản phẩm phù hợp với các
10 Dự báo về Internet Of Things (IoT) năm 2018Trong một báo cáo mới, dự đoán năm 2018: IoT chuyển từ thử nghiệm sang kinh doanh quy mô, Forrester Research dự đoán rằng IoT sẽ trở thành xương sống của
Top 15 Loại cảm biến Sensor được dùng nhiều trong các thiết bị IoTNền tảng IoT hoạt động và cung cấp các dạng thông minh và dữ liệu có giá trị với việc sử dụng nhiều cảm biến khác nhau. Chúng phục vụ để thu
HVAC control system
HVAC (Heating, Ventilation and Air Conditioning) equipment needs a control system to regulate the operation of a heating and/or air
Năng lượng tương lai: Photovoltaic hay Hydrogen?Hydrogen là một nguyên tố chiếm tỷ lệ cao nhất so với tất cả các nguyên tố khác trên địa cầu. Nhưng hydrogen không hiện diện dưới dạng nguyên tử hay
Năng lượng tái tạo : Một loại ắc quy mới nhiều hứa hẹnNăng lượng tái tạo như điện gió và điện mặt trời có một nhược điểm căn bản, đó là không ổn định. Chúng chỉ vận hành khi có
Chất thải từ người là năng lượng tương lai?BBC Future - Hành tinh của chúng ta gặp một vấn đề. Con người, như tất cả các sinh vật sống khác, thải ra rất nhiều những chất thải không dễ chịu
Tin vui cho phái đẹp: Robot Spermbot có thể giúp điều trị ung thư cổ tử cungKhi robot sinh học này phát hiện ra khối u, bốn cánh tay trên cấu trúc vi mô tự động uốn cong, giải phóng tế bào tinh trùng, xâm
Tương lai nào cho trí tuệ nhân tạo - Artificial intelligence (AI)?
Trí thông minh nhân tạo (AI) là khả năng của một chương trình máy tính hoặc một máy tính để suy nghĩ và học hỏi. Nó
Bạn Biết Có Bao Nhiêu Loại Robot - ROBOTPARK
Các loại Robot là gì? Dưới đây là các loại robot của hệ thống vận động. Chúng tôi sẽ kiểm tra các loại này một cách
Gọi điện thoại